OPERATION
IN TEST POSITION The switching device is disconnected from the bus bars and the outgoing circuit. The compartment door may be open or closed and the auxiliary circuit plug may be inserted or not. When the auxiliary circuit plug is inserted and the chassis is locked in the test position following operation is possible. i) To open the door of the breaker compartment. ii) To operate earthing switch. iii) To test operate the breaker from local, electrically, manually, also remotely to check operation of breaker. iv) To check the function of switch position, indication electrical interlocks. When the auxiliary circuit plug is disconnected the breaker is locked in test position. a) The earthing switch can be operated but the door of the breaker compartment cannot be closed. b) The operating mechanism is of the stored energy type. Its motor automatically charges the closing spring after each switching operation. If the motor supply fails, closing spring can be charged by hand lever. With spring fully charged, it is rated for one make and on break operation.
OPERATIONAL PROCEDURE
INTERLOCK: Mechanical & Electro Mechanical Interlocks: Mechanical Interlocks: ACTUAL CONDITIONS Chassis interlocked in service or test position breaker is closed TYPE OF INTERLOCKS Breaker trolley cannot be released from its position and cannot be moved in test or service position
Chassis in between test and service position Breaker cannot be closed breaker is open
Chassis is in service position or between service and test position Chassis in service position or between service and test position Chassis in test position and earth switch is closed Door closed Auxiliaries disconnected Door cannot be open Earth switch cannot be closed Chassis cannot be released from test position and moved in service position Auxiliaries cannot be disconnected Door cannot be closed
PROTECTIONS
Over Current And Thermal Over Load Relay (7SJ50): Application: i) Over Current and earth fault for ring transformers and generators. ii) Back up protection for differential relays and EHV system protection. iii) Thermal over load and short circuit protection for motor cables and transformers. Main Features: Five Selectable Characterization: i) Normal inverse, very inverse, extremely inverse, definite time and thermal overload. ii) Phase unbalance protection if set on thermal overload relay. iii) Thermal overload considers motor preload. iv) DC fail monitoring, self monitoring of relay circuits, instantaneous low set O/C and E/F indication.
i) BBG03 E/S Open. ii) BBE06 E/S Open. iii) BBG04 E/S is Open.