Você está na página 1de 20

Contactors

MC-Series

Contactor 3 Pole

UL508
E108780

Standards and Certifications


UL508
IEC 60947-2 & IEC 60947-4-2
CSA C22.2 No.14

Features

8 Frame Sizes
1/2HP up to 600HP @ 480V AC
Screw Terminals (Lug Terminals Available)
Direct Mounting Overload Relays
Optional accessories
Additional Auxiliary contacts
Replacement Coils
Reversing Wiring Sets and Interlocks
Direct Wiring Adapters fro MMS
Coil surge Suppressors

General Specifications
Maximum Voltage
Rated Frequency
Operating Temperature
Degree of protection
Resistance to Vibration (5-300Hz)
Flame Resistance

600V AC
50/60Hz
-5C (23F) to +40C (104F)
IP20
> 15g
According to UL94

Terminal Size Acceptability and Torque


Wire Type
Solid
Stranded
Ferrule
Torque

22AF
18-8 AWG
18-10AWG
18-10AWG
20 lb-in.

40AF
14-8AWG
14-8AWG
18-10AWG
35 lb-in.

65-100AF
12-4AWG
12-4AWG
12-4AWG
35 lb-in.

150AF
10AWG-1/0
10AWG-1/0
10AWG-1/0
87 lb-in.

225AF
8AWG - 300kcmil
8AWG - 300kcmil
8AWG - 300kcmil
130 lb-in.

400AF
8AWG - 400kcmil
8AWG - 400kcmil
8AWG - 400kcmil
200 lb-in.

800AF
2/0 - 700kcmil
2/0 - 700kcmil
2/0 - 700kcmil
235 lb-in.

Altech Corp. 35 Royal Road Flemington, NJ 08822-6000 Phone (908)806-9400 FAX (908)806-9490 www.altechcorp.com

Contactors
includes UA-1-11
Auxiliary switch,
(1NO/1NC)

3 Pole / Frame Size 22AF

Additional Auxiliaries
and other accessories
see page 11-13
UL508
E108780

Type
Number of Poles
NEMA Size
Standard Auxiliaries

MC-9B

MC-12B

MC-18B

MC-22B

3
00
1NO/1NC

3
00
1NO/1NC

3
0
1NO/1NC

3
1
1NO/1NC

Coil Voltage

Frequency

Part. No.

Part. No.

Part. No.

Part. No.

24V
120V
208V
230V
480V

50/60 Hz
50/60 Hz
60 Hz
50/60 Hz
60 Hz

MC-9B-AC24V
MC-9B-AC120V
MC-9B-AC208V
MC-9B-AC230V
MC-9B-AC480V

MC-12B-AC24V
MC-12B-AC120V
MC-12B-AC208V
MC-12B-AC230V
MC-12B-AC480V

MC-18B-AC24V
MC-18B-AC120V
MC-18B-AC208V
MC-18B-AC230V
MC-18B-AC480V

MC-22B-AC24V
MC-22B-AC120V
MC-22B-AC208V
MC-22B-AC230V
MC-22B-AC480V

AC Coil

Other AC Coil Voltages Available:


60 Hz: 277V, 600V
50/ 60Hz: 48V, 100V, 110V, 200V, 220V, 240V, 380V, 415V, 440V, 500V, 550V

DC Coil

12V
24V

MC-9B-DC12V
MC-9B-DC24V

MC-12B-DC12V
MC-12B-DC24V

MC-18B-DC12V
MC-18B-DC24V

MC-22B-DC12V
MC-22B-DC24V

Other DC Coil Voltages Available:


20V, 48V, 60V, 80V, 100V, 110V, 125V, 200V, 220V, 250V

HP Rating / UL508
Single phase
Three phase

Overload
Relays
(Class 10A,
Differential Typical)

MT-32

Continuous current
110~120V
220~240V
200~208V
220~240V
440~480V
550~600V

HP
25A
0.5
1.5
2
3
5
7.5

Setting Ranges (A)


0.1-0.16A
0.16-0.25A
0.25-0.4A
0.4-0.63A
0.63-1A
1-1.6A
1.6-2.5A
2.4-4A
4-6A
5-8A
6-9A
7-10A
9-13A
12-18A
16-22A
18-25A
22-32A
28-40A

HP
25A
0.75
2
3
5
7.5
10

HP
40A
1
3
5
7.5
10
15

HP
40A
2
3
7.5
10
15
20

Frame Size 22AF


MT-32/3K-0.16
MT-32/3K-0.25
MT-32/3K-0.4
MT-32/3K-0.63
MT-32/3K-1
MT-32/3K-1.6
MT-32/3K-2.5
MT-32/3K-4
MT-32/3K-6
MT-32/3K-8
MT-32/3K-9
MT-32/3K-10
MT-32/3K-13
MT-32/3K-18
MT-32/3K-22
MT-32/3K-25
MT-32/3K-32
MT-32/3K-40

Contactor 3 Pole

22AF

Drawings and other technical information can be found on page 14-20.

Altech Corp. 35 Royal Road Flemington, NJ 08822-6000 Phone (908)806-9400 FAX (908)806-9490 www.altechcorp.com

Contactors
3 Pole / Frame Size 40AF / 65F

includes 2 x UA-1-11
Auxiliary switch,
(2NO/2NC)

includes 2 x UA-1-11
Auxiliary switch,
(2NO/2NC)

Additional Auxiliaries
and other accessories
see page 11-13

Additional Auxiliaries
and other accessories
see page 11-13

UL508
E108780

40AF
Type
Number of Poles
NEMA Size
Standard Auxiliaries

MC-32A

MC-40A

3
1
2NO/2NC

3
1
2NO/2NC

MC-50A*
3
2
2NO/2NC

MC-65A*
3
2
2NO/2NC

Coil Voltage

Frequency

Part. No.

Part. No.

Part. No.

Part. No.

24V
120V
208V
230V
480V

50/60 Hz
50/60 Hz
60 Hz
50/60 Hz
60 Hz

MC-32A-AC24V
MC-32A-AC120V
MC-32A-AC208V
MC-32A-AC230V
MC-32A-AC480V

MC-40A-AC24V
MC-40A-AC120V
MC-40A-AC208V
MC-40A-AC2300V
MC-40A-AC480V

MC-50A-AC24V
MC-50A-AC120V
MC-50A-AC208V
MC-50A-AC230V
MC-50A-AC480V

MC-65A-AC24V
MC-65A-AC120V
MC-65A-AC208V
MC-65A-AC230V
MC-65A-AC480V

AC Coil

Contactor 3 Pole

65AF

Other AC Coil Voltages Available:


60 Hz: 277V, 600V
50/ 60Hz: 48V, 100V, 110V, 200V, 220V, 240V, 380V, 415V, 440V, 500V, 550V

DC Coil

12V
24V

MC-32A-DC12V
MC-32A-DC24V

MC-40A-DC12V
MC-40A-DC24V

MC-50A-DC12V
MC-50A-DC24V

MC-65A-DC12V
MC-65A-DC24V

Other DC Coil Voltages Available:


20V, 48V, 60V, 80V, 100V, 110V, 125V, 200V, 220V, 250V
HP Rating / UL508
Single phase
Three phase

Overload
Relays
(Class 10A,
Differential Typical)

MT-63

Continuous current
110~120V
220~240V
200~208V
220~240V
440~480V
550~600V
Setting Ranges (A)
0.1-0.16A
0.16-0.25A
0.25-0.4A
0.4-0.63A
0.63-1A
1-1.6A
1.6-2.5A
2.4-4A
4-6A
5-8A
6-9A
7-10A
9-13A
12-18A
16-22A
18-25A
22-32A
28-40A
34-50A
45-65A

HP
50A
2
5
7.5
10
20
25

HP
60A
3
7.5
15
15
30
30
Frame Size 40AF
MT-32/3K-0.16
MT-32/3K-0.25
MT-32/3K-0.4
MT-32/3K-0.63
MT-32/3K-1
MT-32/3K-1.6
MT-32/3K-2.5
MT-32/3K-4
MT-32/3K-6
MT-32/3K-8
MT-32/3K-9
MT-32/3K-10
MT-32/3K-13
MT-32/3K-18
MT-32/3K-22
MT-32/3K-25
MT-32/3K-32
MT-32/3K-40
-

HP
70A
3
10
20
25
40
50

HP
100A
5
15
25
30
50
60

Frame Size 65AF


MT-63/3K-6
MT-63/3K-8
MT-63/3K-9
MT-63/3K-10
MT-63/3K-13
MT-63/3K-18
MT-63/3K-22
MT-63/3K-25
MT-63/3K-40
MT-63/3K-50
MT-63/3K-60

* Lug terminals available; please add -L to part number, e.g. MC-75A-AC24V-L.


Drawings and other technical information can be found on page 14-20.

Altech Corp. 35 Royal Road Flemington, NJ 08822-6000 Phone (908)806-9400 FAX (908)806-9490 www.altechcorp.com

Contactors

includes 2 x UA-1-11
Auxiliary switch,
(2NO/2NC)

3 Pole / Frame Size 100AF

Additional Auxiliaries
and other accessories
see page 11-13
UL508
E108780

Type
Number of Poles
NEMA Size
Standard Auxiliaries

MC-75A*

MC-85A*

MC-100A*

3
2
2NO/2NC

3
3
2NO/2NC

3
3
2NO/2NC

Coil Voltage

Frequency

Part. No.

Part. No.

Part. No.

24V
120V
208V
230V
480V

50/60 Hz
50/60 Hz
60 Hz
50/60 Hz
60 Hz

MC-75A-AC24V
MC-75A-AC120V
MC-75A-AC208V
MC-75A-AC230V
MC-75A-AC480V

MC-85A-AC24V
MC-85A-AC120V
MC-85A-AC208V
MC-85A-AC230V
MC-85A-AC480V

MC-100A-AC24V
MC-100A-AC120V
MC-100A-AC208V
MC-100A-AC230V
MC-100A-AC480V

AC Coil

Other AC Coil Voltages Available:


60 Hz: 277V, 600V
50/ 60Hz: 48V, 100V, 110V, 200V, 220V, 240V, 380V, 415V, 440V, 500V, 550V

DC Coil

12V
24V

MC-75A-DC12V
MC-75A-DC24V

MC-85A-DC12V
MC-85A-DC24V

MC-100A-DC12V
MC-100A-DC24V

Other DC Coil Voltages Available:


20V, 48V, 60V, 80V, 100V, 110V, 125V, 200V, 220V, 250V
HP Rating / UL508
Single phase
Three phase

Overload
Relays
(Class 10A,
Differential Typical)

MT-95

Continuous current
110~120V
220~240V
200~208V
220~240V
440~480V
550~600V

HP
110A
5
15
25
30
50
60

Setting Ranges (A)


7-10A
9-13A
12-18A
16-22A
18-25A
22-32A
24-36A
28-40A
34-50A
45-65A
54-75A
63-85A
70-95A
80-100A

HP
135A
7.5
15
30
40
60
75

HP
160A
10
20
30
40
75
75

Frame Size 100AF


MT-95/3K-10
MT-95/3K-13
MT-95/3K-18
MT-95/3K-22
MT-95/3K-25
MT-95/3K-32
MT-95/3K-36
MT-95/3K-40
MT-95/3K-50
MT-95/3K-65
MT-95/3K-75
MT-95/3K-85
MT-95/3K-95
MT-95/3K-100

Contactor 3 Pole

100AF

* Lug terminals available; please add -L to part number, e.g. MC-75A-AC24V-L.


Drawings and other technical information can be found on page 14-20.

Altech Corp. 35 Royal Road Flemington, NJ 08822-6000 Phone (908)806-9400 FAX (908)806-9490 www.altechcorp.com

Contactors
3 Pole /Frame Size 150AF/225AF

includes 2 x UA-1-11
Auxiliary switch,
(2NO/2NC)

includes 2 x AU-100-11
Auxiliary switch,
(2NO/2NC)

Additional Auxiliaries
and other accessories
see page 11-13

Additional Auxiliaries
and other accessories
see page 11-13

UL508
E108780

150AF with Lug Terminals


Type
Number of Poles
NEMA Size
Standard Auxiliaries

Contactor 3 Pole

Coil Voltage

Frequency

AC Coil

24V
110V
220V
300V
400V
500V

50/60
50/60
50/60
50/60
50/60
50/60

DC Coil

12V
24V
110V
220V

AC/DC
Common Coil

Coil Voltage
AC 50/60Hz
DC
24-25V
24V
48-50V
48V
100-240V
100-220V
265-347V

380-450V

440-575V

HP Rating / UL508
Single phase
Three phase

Overload
Relays
(Class 10A,
Differential Typical)

MT-150

Hz
Hz
Hz
Hz
Hz
Hz

Continuous current
110~120V
220~240V
200~208V
220~240V
440~480V
550~600V

Setting Ranges (A)


34-50A
45-65A
54-75A
63-85A
65-100A
80-105A
85-125A
95-130A
110-150A
100-160A
120-185A
160-240A

225AF

MC-130A*

MC-150A*

MC-185A

MC-225A

3
3
2NO/2NC

3
4
2NO/2NC

3
4
2NO/2NC

3
4
2NO/2NC

Part. No.

Part. No.

Part. No.

Part. No.

MC-130A-AC24V-L
MC-130A-AC110V-L
MC-130A-AC220V-L
MC-130A-AC300V-L
MC-130A-AC400V-L
MC-130A-AC500V-L

MC-150A-AC24V-L
MC-150A-AC110V-L
MC-150A-AC220V-L
MC-150A-AC300V-L
MC-150A-AC400V-L
MC-150A-AC500V-L

MC-130A-DC12V-L
MC-130A-DC24V-L
MC-130A-DC110V-L
MC-130A-DC220V-L

MC-150A-DC12V-L
MC-150A-DC24V-L
MC-150A-DC110V-L
MC-150A-DC220V-L

HP
160A
10
20
40
40
75
75

HP
210A
15
25
40
50
100
75

Frame Size 150AF


MT-150/3K-50
MT-150/3K-65
MT-150/3K-75
MT-150/3K-85
MT-150/3K-105
MT-150/3K-130
MT-150/3K-150
-

MC-185A-24V
MC-225A-24V
MC-185A-48V
MC-225A-48V
MC-185A-100/200V MC-225A-100/200V
MC-185A-300V
MC-225A-300V
MC-185A-400V
MC-225A-400V
MC-185A-500V
MC-225A-500V

HP
230A
15
30
60
60
125
125

HP
275A
15
40
60
75
150
150

Frame Size 225AF


MT-225/3K-100
MT-225/3K-125
MT-225/3K-160
MT-225/3K-185
MT-225/3K-240

* Screw terminals available; please remove -L from part number, e.g. MC-75A-AC24V.
Drawings and other technical information can be found on page 14-20.

Altech Corp. 35 Royal Road Flemington, NJ 08822-6000 Phone (908)806-9400 FAX (908)806-9490 www.altechcorp.com

Contactors

includes 2 x AU-100-11
Auxiliary switch,
(2NO/2NC)

3 Pole / Frame Size 400AF

Additional Auxiliaries
and other accessories
see page 11-13
UL508
E108780

Type
Number of Poles
NEMA Size
Standard Auxiliaries
Coil Voltage

AC/DC
Common Coil

AC 50/60Hz
100-240V
265-347V
380-450V
440-575V

DC
100-220V

HP Rating / UL508
Single phase
Three phase

Overload
Relays
(Class 10A,
Differential Typical)

Continuous current
110~120V
220~240V
200~208V
220~240V
440~480V
550~600V

MC-265A

MC-330A

MC-400A

3
5
2NO/2NC

3
5
2NO/2NC

3
5
2NO/2NC

Part. No.

Part. No.

Part. No.

MC-265A-100/200V
MC-265A-300V
MC-265A-400V
MC-265A-500V

MC-330A-100/200V
MC-330A-300V
MC-330A-400V
MC-330A-500V

MC-400A-100/200V
MC-400A-300V
MC-400A-400V
MC-400A-500V

HP
300A

75
100
200
200

HP
350A

100
125
250
250

Setting Ranges (A)


85-125A
100-160A
120-185A
160-240A
200-330A
260-400A

Frame Size 400AF


MT-400/3K-125
MT-400/3K-160
MT-400/3K-185
MT-400/3K-240
MT-400/3K-330
MT-400/3K-400

Part. No.
AJ-220
AJ-400
AJ-800

Frame Size
225AF
400AF
800AF

HP
450A

125
150
300
300

Contactor 3 Pole

400AF

MT-400

Lug
Terminals

Drawings and other technical information can be found on page 14-20.

Altech Corp. 35 Royal Road Flemington, NJ 08822-6000 Phone (908)806-9400 FAX (908)806-9490 www.altechcorp.com

Contactors

includes 2 x AU-100-11
Auxiliary switch,
(2NO/2NC)

3 Pole / Frame Size 800AF

Additional Auxiliaries
and other accessories
see page 11-13
UL508
E108780

800AF
Type
Number of Poles
NEMA Size
Standard Auxiliaries
Coil Voltage

AC/DC

Contactor 3 Pole

Common Coil

AC 50/60Hz
100-127V
200-240V
265-347V
380-450V
440-575V

DC
100-110V
200-220V

Three phase

Overload
Relays
(Class 10A,
Differential Typical)

MC-630A

MC-800A

3
6
2NO/2NC

3
6
2NO/2NC

3
7
2NO/2NC

Part. No.

Part. No.

Part. No.

MC-500A-100V
MC-500A-200V
MC-500A-300V
MC-500A-400V
MC-500A-500V

MC-630A-100V
MC-630A-200V
MC-630A-300V
MC-630A-400V
MC-630A-500V

MC-800A-100V
MC-800A-200V
MC-800A-300V
MC-800A-400V
MC-800A-500V

Rating / UL508
Single phase

MC-500A

Continuous current
110~120V
220~240V
200~208V
220~240V
440~480V
550~600V

Setting Ranges (A)


200-330A
260-400A
400-630
520-800A

HP
580A

150
200
400
400

HP
660A

200
250
500
500

HP
900A

200
300
600
600

Frame Size 800AF


MT-800/3K-330
MT-800/3K-400
MT-800/3K-630
MT-800/3K-800

MT-800

Lug
Terminals

Part. No.
AJ-220
AJ-400
AJ-800

Frame Size
225AF
400AF
800AF

Drawings and other technical information can be found on page 14-20.

Altech Corp. 35 Royal Road Flemington, NJ 08822-6000 Phone (908)806-9400 FAX (908)806-9490 www.altechcorp.com

10

Reversing contactor consists of:


Two AC or DC contactors
Mechanical Interlock
Wire Set (up to frame size 100A)

Reversing
Contactors
Type
MC-9B/R
MC-12B/R
MC-18B/R
MC-22B/R
MC-32A/R
MC-40A/R
MC-50A/R
MC-65A/R
MC-75A/R
MC-85A/R
MC-100A/R

Type
MC-130A/R
MC-150A/R
MC-185A/R
MC-225A/R
MC-265A/R
MC-330A/R
MC-400A/R
MC-500A/R
MC-630A/R
MC-800A/R

MC-40A/R

MC-65A/R

MC-100A/R

To create Part No. add /R after frame size,


eg. MC-32A/R-AC120V, MC-32A/R-DC24V, etc.
For available coil voltages see contactor pages 5-10.

Individual Components
Mechanical Interlocks
Interlock Part#
UR-02
AR-180
AR-600

Contactor Type
MC-9B to MC-100A
MC-180A to MC-400A
MC-500A to MC-800A

Auxiliary Contacts
2 x NC
-

Interlock unit

UR-02

AR-180

Wire Kits
Interlock Part#
UW-22
UW-32
UW-63
UW-95

Contactor Frame Size


MC-9B to MC-22B
MC-32A to MC-40A
MC-50A, MC-65A
MC-75A, MC-100A

Wire kit

UW-XX

Installation of Interlock and Wire Kits

Reversing Contactors

Assembled Reversing Contactors

Click
2

1
Click
2

Install the interlock unit on


the side of a contactor first.
Fit each part as indicated in
the figure above.

And then install the other


contactor on the other side
of the interlock unit as shown.

After installing interlock unit wiring kit can be assembled.


Wiring kit contains two molded wires - one for line side
and the other for load side.

Altech Corp. 35 Royal Road Flemington, NJ 08822-6000 Phone (908)806-9400 FAX (908)806-9490 www.altechcorp.com

11

Contactors
Accessories
UA-1

AUXILIARY CONTACTS
UA-1

AU-2

Frame Sizes 22AF - 150AF

AU-4

Part No.

Poles

Configuration

Mounting

UA-1-11

1NO/1NC

Side

Contact Arrangement
13(43)

21(31)

14(44)

22(32)

Accessories

1NO/1NC

AU-2-20
AU-2-11
AU-2-02

2
2
2

2NO
1NO/1NC
2NC

Front
Front
Front

53

63

54

64

2NO

AU-4-40
AU-4-31
AU-4-22
AU-4-13
AU-4-04

4
4
4
4
4

4NO
3NO/1NC
2NO/2NC
1NO/3NC
4NC

Front
Front
Front
Front
Front

51

63

51

61

52

64

52

62

1NO/1NC

2NC

51 61 71 81

51 63 71 81

53 61 71 83

53 61 73 83

53 63 73 83

52 62 72 82

52 64 72 82

54 62 72 84

54 62 74 84

54 64 74 84

4NO

3NO/1NC

2NO/2NC

1NO/3NC

4NC

Frame Sizes 225AF - 800AF


Part No.

Poles

Configuration

Mounting

1NO/ 1NC

Side

Contact Arrangement
13(43)

AU-100-11

21(31)

AU-100

1NO1NC

14(44)

22(32)

Installation Instructions

UA-1

AU-2, 4

To install side mounting unit remove the indicated


part in the circle in the fig. first. And then fit each
part as shown. To separate push forward and pull.

To install front mounting unit fit it on the upper


part of the front of the contactor and push it
down. To separate pull the lever of the unit and
push the unit upward.

Altech Corp. 35 Royal Road Flemington, NJ 08822-6000 Phone (908)806-9400 FAX (908)806-9490 www.altechcorp.com

12

Contactors
Accessories
MC

Surge Units (for use with frame sizes 22AF-100AF)


Part No.

Rated Voltage
Varistor

Internal Ratings
Resistor

Capacitor

120V
270V
470V
120V
270V
470V
120V
270V
470V
1000V
-

100
100
100
100
100
100
56

0.1F
0.1F
0.1F
0.47F
0.47F
0.47F
0.1F

Varistor
C
R

24-48VAC
100-125VAC
200-240VAC
24-48DC
100-125VDC
200-220VDC
24-48V AC/DC
100-125V AC/DC
200-240V AC/DC
380-440V AC/DC
100-125VAC

US-1~6
MC

Varistor

US-11~14
MC

C
R

US-22

Terminal Covers

Insulation Barriers

Part No.

Frame Size

AP-220
AP-400
AP-600

225AF
400AF
800AF

Part No.
AI-180
AI-600

Frame Size
225AF, 400AF
800AF

Accessories

US-1
US-2
US-3
US-4
US-5
US-6
US-11
US-12
US-13
US-14
US-22

Safety Cover*
Part No.
AP-9

(Fits all sizes)

Bases for Separate


Mounting Overload Relay
Part No.

Overload Relay

UZ-32
UZ-63/S
UZ-95/S
UZ-150/S

MT-32
MT-63
MT-95
MT-150A

Remote Reset Units


for Overload Relay
Part No.
UM-4R
UM-5R
UM-6R

Cable Length
(L)
400 mm
500 mm
600 mm

Altech Corp. 35 Royal Road Flemington, NJ 08822-6000 Phone (908)806-9400 FAX (908)806-9490 www.altechcorp.com

13

Dimensions
Contactors
36.5

86

45

65

0.66 lb.

36.5

117.7

45

33.5

65

49.5

MC-9b~22b DC

73.5

1.1 lb.

MC-32a~40a AC

69

90

45

35

75

60

2a2b
83

Contactor Specifications

49.5

33.5

73.5

MC-9b~22b AC

1.1 lb.

69

MC-32a~40a DC

117.1

45

35

75

60

83

2a2b

1.76 lb.

Dimensions in mm (to convert to inches multiply by 0.03937).

Altech Corp. 35 Royal Road Flemington, NJ 08822-6000 Phone (908)806-9400 FAX (908)806-9490 www.altechcorp.com

14

Dimensions
Contactors
79

2.2 lb.
79

47
41

146.4

55

92

100

106

MC-50a~65a DC

2.87 lb.
94
70

135.8

60
55

130

140

MC-75a~100a AC

4.19 lb.

94
172.3

60
55

130

70

140

MC-75a~100a DC

Contactor Specifications

92

106

100

47
41

119

55

MC-50a~65a AC

6.17 lb.

Dimensions in mm (to convert to inches multiply by 0.03937).

Altech Corp. 35 Royal Road Flemington, NJ 08822-6000 Phone (908)806-9400 FAX (908)806-9490 www.altechcorp.com

15

Dimensions
Contactors
119

83

95

130.3

72.7

148

5.29 lb.

(162)*1

185.1
M4(Coil terminal)

138

118

120
45

4-M6

203

190

93

164

MC-185a
MC-225a

M10 Bolt

11.9 lb.

25

M4(Coil terminal)

145

204.4
132.5

60
50

4-M8

243

210

110

220

163

225

(187)*1

MC-265a
MC-330a
MC-400a

201

M12 Bolt

30

245.3
M16 Bolt

40

312

160

4-M10
149

250

250

285

290

MC-500a
MC-630a
MC-800a

20.28 lb.

272

Contactor Specifications

158

MC-130a
MC-150a

49.38 lb.

Dimensions in mm (to convert to inches multiply by 0.03937).

Altech Corp. 35 Royal Road Flemington, NJ 08822-6000 Phone (908)806-9400 FAX (908)806-9490 www.altechcorp.com

16

Dimensions
Overload Relays
45

MT-12

63.7

0.22 lb.

MT-32

3.7

86.3

74.6

17.5

65

95-NC-96

97-NO-98

M3.5
(Aux terminal)
M4/M5
(Main terminal)

Aux terminal

2T1
11.8

4T2
6T3
14.3
45

32.6

Main terminal
70.5

3.7

MT-63

0.37 lb.

96.3

80.6

17.5

57.5

97-NO-98

95-NC-96

M6
(Main terminal)

2T1

4T2

6T3

Aux terminal
14

18
55

31

Main terminal

5.3

M3.5
(Aux terminal)

80.5

0.67 lb.
3.7

106.3

MT-95

97.2

17.5

64.8

Overload Relay Specifications

60.1

73.2

43.1

95-NC-96

97-NO-98

M3.5
(Aux terminal)

Aux terminal

M8
(Main terminal)

4T2

17

6T3

22.5
70

2T1

42

Main terminal
90.5

1.04 lb.

Dimensions in mm (to convert to inches multiply by 0.03937).

Altech Corp. 35 Royal Road Flemington, NJ 08822-6000 Phone (908)806-9400 FAX (908)806-9490 www.altechcorp.com

17

Dimensions
Overload Relays
61

67

109

95

113

1.54 lb.

M8(Main screw)

47

113.5

47

141

MT-225

65.5

147
184

M10(Main screw)

5.51 lb.
127

110

171

143

MT-400

85

121
M12(Main screw)

198

151

360

5.73 lb.

320
250

MT-800

200

160

500
530

Overload Relay Specifications

MT-150

40
M16(Main screw)

160

179
212

25.35 lb.

Dimensions in mm (to convert to inches multiply by 0.03937).

Altech Corp. 35 Royal Road Flemington, NJ 08822-6000 Phone (908)806-9400 FAX (908)806-9490 www.altechcorp.com

18

Specifications
COIL CHARACTERISTIC AND DATA - MC SERIES
Type MC-9B~150A AC Coils
Rated
Inrush Current (A)
Voltage AC50HZ
AC60HZ

MC-9B~22B
(50/60Hz)

MC-9B~22B
(60Hz)
MC-32A, 40A
(50/60Hz)

MC-32A, 40A
(60Hz)
MC-50A,60A
(50/60Hz)

MC-50A, 60A
(60Hz)
MC-75A~100A
(50/60Hz)

MC-75A~100A
(60Hz)
MC-130A, 150A
(50/60Hz)

24
110
220
240
208
480
24
110
220
240
208
480
24
110
220
240
208
480
24
110
220
240
208
480
24
48
110
220
300
400
500

2.975
0.657
0.340
0.286
2.935
0.652
0.335
0.289
4.597
1.025
0.608
0.474
7.956
1.782
1.018
0.870
8.800
3.950
1.500
0.720
0.690
0.490
0.310

Holding Current (A) Closing


Opening Inrush Holding Consumption(W)
AC50HZ AC60HZ Time (ms) Time (ms) (VA)
(VA) AC50HZ AC60HZ

2.915
0.636
0.320
0.264
0.340
0.106
2.842
0.631
0.316
0.264
0.340
0.108
4.411
0.994
0.592
0.425
0.600
0.198
7.765
1.710
0.980
0.820
1.013
0.460
9.190
4.240
1.580
0.760
0.710
0.500
0.320

0.430
0.095
0.040
0.038
0.460
0.100
0.050
0.046
0.524
0.114
0.058
0.053
0.768
0.176
0.078
0.082
0.350
0.168
0.205
0.085
0.050
0.040
0.027

0.330
0.074
0.028
0.027
0.042
0.018
0.360
0.077
0.040
0.035
0.044
0.020
0.401
0.085
0.046
0.039
0.048
0.020
0.645
0.145
0.062
0.066
0.065
0.035
0.410
0.198
0.231
0.099
0.059
0.046
0.032

12~22ms
12~22ms
12~22ms
12~22ms
12~22ms
12~22ms
12~22ms
12~22ms
12~22ms
12~22ms
12~22ms
12~22ms
12~22ms
12~22ms
12~22ms
12~22ms
12~22ms
12~22ms
15~30ms
15~30ms
15~30ms
15~30ms
15~30ms
15~30ms
20~40ms
20~40ms
20~40ms
20~40ms
20~40ms
20~40ms
20~40ms

4~19ms
4~19ms
4~19ms
4~19ms
4~19ms
4~19ms
4~19ms
4~19ms
4~19ms
4~19ms
4~19ms
4~19ms
4~19ms
4~19ms
4~19ms
4~19ms
4~19ms
4~19ms
10~30ms
10~30ms
10~30ms
10~30ms
10~30ms
10~30ms
60~70ms
60~70ms
60~70ms
60~70ms
60~70ms
60~70ms
60~70ms

90
90
90
90
90
90
115
115
115
115
115
115
160
160
160
160
160
160
190
190
190
190
190
190
220
220
220
220
220
220
220

11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
16
16
16
16
16
16
25
25
25
25
25
25
25

2.1
2.1
2.1
2.1
2.7
2.7
2.7
2.7
2.8
2.8
2.8
2.8
5.4
5.4
5.4
5.4
2.7
2.7
2.7
2.7
2.7
2.7
2.7

1.5
1.5
1.5
1.5
1.5
1.5
2.2
2.2
2.2
2.2
2.2
2.2
2.4
2.4
2.4
2.4
2.4
2.4
4.7
4.7
4.7
4.7
4.7
4.7
3.6
3.6
3.6
3.6
3.6
3.6
3.6

Pick-up Voltage
AC50HZ
AC60HZ
16.0
72.0
140.0
145.0
16.0
75.0
150.0
145.0
16.0
69.0
150.0
145.0
16.0
66.0
150.0
133.0
18.0
34.0
84.0
165.0
210.0
280.0
360.0

18.5
75.0
142.0
155.0
133.0
350.0
18.5
75.0
142.0
155.0
133.0
350.0
18.5
77.0
155.0
165.0
85.0
315.0
17.5
75.0
160.0
170.0
135.0
330.0
17.5
37.1
80.0
160.0
200.0
270.0
340.0

Drop-out Voltage
AC50HZ
AC60HZ
11.00
49.00
100.00
110.00
11.00
48.00
100.00
110.00
9.00
53.00
100.00
115.00
11.50
51.00
100.00
105.00
14.00
25.00
60.00
105.00
165.00
240.00
290.00

11.0
58.0
105.0
125.0
100.0
255.0
11.0
57.0
105.0
125.0
100.0
255.0
12.0
59.0
105.0
125.0
100.0
230.0
14.0
60.0
105.0
115.0
100.0
265.0
13.0
23.0
55.0
100.0
160.0
200.0
270.0

Type MC-9B~150A DC Coils


Frame
Type

Rated
Voltage

Inrush
Current(A)

Holding
Current (A)

Pick-up
Voltage

Drop-out
Voltage

Closing
time (ms)

Opening
time (ms)

MC-6A~22B

12
24
12
24
12
24
12
24
24
48
110
220

0.790
0.380
0.702
0.350
0.790
0.380
0.790
0.380
6.700
3.300
2.000
0.950

0.790
0.380
0.702
0.350
0.790
0.380
1.450
0.740
0.240
0.155
0.068
0.040

7.5
16.0
8.5
16.3
8.7
17.5
8.1
17.5
17.5
33.0
75.0
150.0

3.0
5.5
3.4
6.3
2.6
5.0
2.5
4.4
4.5
11.0
25.0
50.0

35~50ms

4~19ms

50~65ms

4~19ms

50~65ms

4~19ms

100~120ms

10~25ms

70~80ms

60~70ms

MC-32A, 40A
MC-50A, 65A
MC-75A~100A
MC-130A, 150A

Contactor Specifications

Frame
Type

Type MC-185A~800A AC/DC Common Coils


Frame
Type

Rated
Voltage

Voltage

MC-185A,225A

24V
48V
100~240V
100~240V
100~240V
100~240V
100V
200V

24
48
110
220
110
220
110
220

MC-265A~400A
MC-500A~800A

Inrush Current (A)


AC50HZ AC60HZ DC
9.53
3.836
2.108
1.256
4.3
4.1
11.2
5.2

9.6
7
3.774 2.71
2.092 1.532
1.22 1.34
4.33
4.2
4
4.4
10.7 18.2
4.9
6.1

Holding Current (mA)


AC50HZ AC60HZ DC
307
70
57
42
443
329
91
68

319
72
57
43
434
310
91
67

143
39
36
22
439
278
46
34

Closing Time (ms)


AC50HZ AC60HZ DC
41
51.7
53.38
43.5
47.8
42
55.2
56.3

40
45.7
52.2
41.7
50.3
41
56
55.7

38.1
43.8
53.3
41
48.7
39
50.5
55.3

Opening Time (ms)


AC50HZ AC60HZ
DC
65.3
38.6
66.1
67.2
57
57.6
41
38

35
40.7
64.4
67.6
56
58.3
40
35.5

39.9
46.8
67.8
68.8
55.8
56.5
41
37.2

Coli Consumption(W)
AC50HZ AC60HZ DC
3.6
2.2
4.1
6.3
5.8
6.2
5.3
8.3

3.6
2.3
4.1
6.2
5.7
6
5.3
8.5

3.5
1.9
4.3
5.8
6.3
6.2
6
8.6

Altech Corp. 35 Royal Road Flemington, NJ 08822-6000 Phone (908)806-9400 FAX (908)806-9490 www.altechcorp.com

19

IEC Ratings
MC Series

IEC Ratings (AC-1, AC-3) MC - Series


Type
IEC60947-4
Ratings
AC-1

IEC RATINGS

AC-3

200/240V
380/440V
500/550V
690V

Type
IEC60947-4
Ratings
AC-1
AC-3

200/240V
380/440V
500/550V
690V

Type
IEC60947-4
Ratings
AC-1
AC-3

200/240V
380/440V
500/550V
690V

MC-9B

MC-12B

MC-18B

MC-22B

MC-32A

MC-40A

MC-50A

kW

kW

kW

kW

kW

kW

kW

25

25

32

40

50

60

70

2.5
4
4
4

11
9
7
6

3.5
5.5
7.5
7.5

13
12
12
9

4.5
7.5
7.5
7.5

18
18
13
9

5.5
11
15
15

22
22
20
18

7.5
15
18.5
18.5

32
32
28
20

11
18.5
22
22

40
40
32
23

15
22
30
30

55
50
43
28

MC-65A

MC-75A

MC-85A

MC-100A

MC-130A

MC-150A

MC-185A

kW

kW

kW

kW

kW

kW

kW

100

110

135

160

160

210

230

18.5
30
33
33

65
65
60
35

22
37
37
37

75
75
64
42

25
45
45
45

85
85
75
45

30
55
55
45

105
105
85
65

37
60
60
55

130
130
90
60

45
75
70
55

150
150
100
60

55
90
110
110

185
185
180
120

MC-225A

MC-265A

MC-330A

MC-400A

MC-500A

MC-630A

MC-800A

kW

kW

kW

kW

kW

kW

kW

275

300

350

450

580

660

900

75
132
132
140

225
225
200
150

80
147
147
160

265
265
225
185

90
160
160
200

330
330
280
225

125
200
225
250

400
400
350
300

147
265
265
300

500
500
400
380

190
330
330
400

630
630
500
420

220
440
500
500

800
800
720
630

Altech Corp. 35 Royal Road Flemington, NJ 08822-6000 Phone (908)806-9400 FAX (908)806-9490 www.altechcorp.com

20

Katko Motor Disconnect Switches

ABL UL508 Manual Motor Controllers,


UL489 Minature Molded Case Circuit Breakers,
and UL1077 Supplementary Protectors

Altechs UL508 Manual Motor Controllers


UL489 Minature Molded Case Circuit Breakers
and UL1077 Supplementary Protectors
PLUS
Molded Case Circuit Breakers, Three Phase
Adjustable Trip Miniature Circuit Breakers/ Manual
Motor Controllers, Three Phase Adjustable Trip
Economy Manual Motor Controllers and Earth
Leakage Circuit Breakers

Altech Corp. 35 Royal Road Flemington, NJ 08822-6000 Phone (908)806-9400 FAX (908)806-9490 www.altechcorp.com

21

Mini Contactors

UL508
E108780

Mini Contactors

Type

6A

Coil Voltage Frequency

Mini Contactors

AC Coil
Other AC Coil
Voltages Available

50/ 60Hz:
42V, 48V,
110V, 220V,
277V, 400V,
480V, 600V

DC Coil

24V
120V
208V
230V

12A

50/60 Hz
50/60 Hz
60 Hz
50/60 Hz

Screw Clamp
00
1NO

Part. No.

Part. No.

Part. No.

GMC-6M-10-AC24V
GMC-6M-10-AC120V
GMC-6M-10-AC208V
GMC-6M-10-AC230V

GMC-9M-10-AC24V
GMC-9M-10-AC120V
GMC-9M-10-AC208V
GMC-9M-10-AC230V

GMC-12M-10-AC24V
GMC-12M-10-AC120V
GMC-12M-10-AC208V
GMC-12M-10-AC230V

Coil Characteristics and Data


Pick-up Voltage Limit
Drop-out Voltage Limit
Coil Consumption (W)
Inrush [VA]
Holding [VA]
Closing Time [ms]
Opening Time [ms]

12V
24V

9A

3 NO main Contacts, 1 Auxiliary Contact


Screw Clamp
Screw Clamp
00
00
1NO
1NO

Number of Poles
Terminal Type
NEMA Size
Standard Auxiliary*

80-110%
30-40%
2
32
6
1020
3545

GMD-6M-10-DC12V
GMD-6M-10-DC24V

GMD-9M-10-DC12V
GMD-9M-10-DC24V

GMD-12M-10-DC12V
GMD-12M-10-DC24V

Coil Characteristics and Data


Pick-up Voltage Limit
Other DC Coil
Voltages Available Drop-out Voltage Limit
48V, 60V,
120V, 125V,
220V, 240V,
250V

Coil Consumption (W)


Inrush [W]
Holding [W]
Closing Time [ms]
Opening Time [ms]

HP Rating / UL508
Continuous current
Single phase
110~120V
220~240V
Three phase
240V
480V
600

Overload
Relays
(Class 10A,
Differential Typical)

80-110%
10-30%
3
3
3
40-50
35-45
HP
20A
0.5
1
1.5
3
3

Setting Ranges (A)


0.1-0.16A
0.16-0.25A
0.25-0.4A
0.4-0.63A
0.63-1A
1-1.6A
1.6-2.5A
2.4-4A
4-6A
5-8A
6-9A
7-10A
9-13A
12-16A

HP
20A
0.5
1.5
3
5
5

HP
20A
1
2
3
7.5
10

Frame Size 22AF


GTK-12M-0.16
GTK-12M-0.25
GTK-12M-0.4
GTK-12M-0.63
GTK-12M-1
GTK-12M-1.6
GTK-12M-2.5
GTK-12M-4
GTK-12M-6
GTK-12M-8
GTK-12M-9
GTK-12M-10
GTK-12M-13
GTK-12M-16

* For built-in NC Auxiliary Switch change part number to -01; e.g. GMC-6M-01-AC24V.

Altech Corp. 35 Royal Road Flemington, NJ 08822-6000 Phone (908)806-9400 FAX (908)806-9490 www.altechcorp.com

22

Mini Contactors
Accessories

Reversing Mini Contactor


Separate parts for assembling Reversing Contactors

MIni Contactor Accessories

For Pre-assembled Reversing Mini Contactors please consult Altech.

Interlock Kit
Part No.
AR-12M

Mini Contactor Type


6A - 12A

Auxiliary Contacts
Part No.
AU-1M-10
AU-1M-01
AU-2M-20
AU-2M-02
AU-2M-11
AU-4M-40
AU-4M-31
AU-4M-22
AU-4M-13
AU-4M-04

Poles
1
1
2
2
2
4
4
4
4
4

Configuration
1NO
1NC
2NO
2NC
1NO/1NC
4NO
3NO/1NC
2NO/2NC
1NO/3NC
4NC

Mounting
Side
Side
Front
Front
Front
Front
Front
Front
Front
Front

Part No.
AS-12M/1
AS-12M/2
AS-12M/3

Rated Voltage
24-48VAC
60-127VAC
200-240VAC

Internal Element
Varistor
Varistor
Varistor

Contactor Type
GMC-6M-12M
GMC-6M-12M
GMC-6M-12M

AS-12M/4
AS-12M/5
AS-12M/6
AS-12M/7

12-24VDC
30-72VDC
100-127VDC
200-250VDC

Varistor
Varistor
Varistor
Varistor

GMD-6M-12M
GMD-6M-12M
GMD-6M-12M
GMD-6M-12M

Interlock Kit

Surge Units

Base for Separate


Mounting Overload Relay
Part No.
AZ-12MH

Specifications

4xM4(mouting Hole)

57

45

37.7
35
4

43.3

M3.5(Coil terminal)

7.6

50

58

33.5

M3.5

8.7

0.37 lb.

Dimensions in mm (to convert to inches multiply by 0.03937).

Altech Corp. 35 Royal Road Flemington, NJ 08822-6000 Phone (908)806-9400 FAX (908)806-9490 www.altechcorp.com

23

Você também pode gostar