Você está na página 1de 2

VER: 1.0.2949.

26374

Select Chill Performance Report: VAPOUR ABSORPTION CHILLER

Client : PT DOVER CHEMICALS Project :

Date Model

: 3/24/2008, : SS 20C-C

Description Capacity ( + 3 %) : A 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. B 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. Chilled Water Circuit : Chilled water flow Chilled water inlet temperature Chilled water outlet temperature Evaporator passes Chilled water circuit friction loss Chilled water circuit pressure drop Chilled water Connection diameter Glycol type Chilled water glycol % Maximum working pressure Cooling Water Circuit: Heat rejected Cooling water flow Cooling water inlet temperature Cooling water outlet temperature Absorber / Condenser passes Cooling water circuit friction loss Cooling water circuit pressure drop Cooling water connection diameter Glycol type Cooling water glycol % Maximum working pressure

Unit TR 180.0

m/hr C C No. mLC mLC DN % kg/cm

108.6 12.0 7.0 2 6.8 8.2 125 NA 0.0 8

kcal/Hr m/hr C C No. mLC mLC DN % kg/cm

1323525.7 260.0 32.0 37.1 1/1 6.1 7.7 150 NA 0.0 8

VER: 1.0.2949.26374

C 1. 2. 3. 4. 5. 6. 7. 8. D 1 2. 3 4 5 E 1 2 3 4 5 6 7 8 F 1 2 3

Steam Circuit : Heat input Steam pressure Steam consumption Condensate drain temperature Condensate drain pressure Connection - Inlet diameter Connection - Drain diameter Maximum working pressure Electrical Data : Power supply Power consumption Absorbent pump rating Refrigerant pump rating Vacuum pump rating Physical Data : Length Width Height Operating weight Flooded weight Dry weight Shipping Weight Tube cleaning space Tube Metallurgy : Evaporator tube material Absorber tube material Condenser tube material

kcal/Hr kg/cm kg/hr C kg/cm DN DN kg/cm

779205.7 3.5 1379.3 80 - 100 0.2 150 40 5

kVA kW (A) kW (A) kW (A)

380 V( 10%), 50 Hz (5%), 3 Phase+N 6.9 1.5 (5.0) 0.3 (1.4) 0.75 (1.8)

mm mm mm ton ton ton ton mm

3995 1880 2830 6.60 10.00 5.20 5.90 3600

Cu Finned CuNi (90:10,95:05) Mini Finned CuNi (90:10,95:05) Plain

PS: 1. This selection is valid for insulated chiller only. 2. For non-insulated chiller, the capacity & heat source consumption will vary. 3. Plant room temperature should be from +5 deg C to +45 deg C. 4. Please contact Thermax representative/office for customized specifications