Delete it, this is irrelevant.

Change to SP-P-1004.01-5030-001

Change to personnel

To check against requirement,it should be 1.bar min.

Please clarify. - SW

Please clarify.

9) Re-instatement format to be sign off by PMC.

Please describe the criteria of categories "C" punch for guidances if M/C was over. Please describe the process of manual cleaning with acceptance condition after Hydro-Test.

Please describe the internal pipe preservation after cleaning before shippingto offshore for installation and Tie-In.