NOTES:

1. WHERE FIBERGLASS STRAIN INSULATOR IS REQUIRED, SUBSTITUTE FOR ITEM #8 AND ITEM #12.

BILL OF MATERIAL
AMS STOCK ITEM NO. NO. REQD. NUMBER
1 2 3 4 ** 5 6 7 * 8 9 10 11 12 2 2 4 (2) 1 LOT 2 LOT 1 (0) 2 1 1 1 14-489-XXX 10-891-214 14-531-XXX 14-542-250 07-135-XXX 10-889-280 14-659-420 14-382-175 14-511-750 14-112-769 14-112-XXX 14-509-359

BOLT: MACHINE;

WASHER: SPRING; FOR GUY: DEAD END; PREFORMED

PLATE: POLE EYE; HEAVY DUTY GUY STRAND WASHER: CURVED; FOR #4 COPPER: DEAD SOFT INSULATOR: GUY STRAIN; ANSI CLASS 54-3 CLIP: GROUND; UNIVERSAL BONDING CONNECTOR: GROUND CONNECTOR: GROUND CLEVIS: THIMBLE 1 12 3 4 6 2 9 5/8 " BOLT 1 11 7 10

10

* FOR GROUNDED GUYS, REFER TO QUANTITY IN PARENTHESIS ** SEE TABLE BELOW: 14,500 POUNDS STEEL 18,800 POUNDS STEEL 3 5

102mm (4")

GROUND LINE

PLANT NO.

990
DESCRIPTION
5/8 " x LENGTH TO SUIT 5/8 " BOLT

INDEX

AD-036023
DRAWING NUMBER

SHEET NO.

003

REV. NO.

03

2.

FOR 18.8K GUY STRANDS, THE GUY SLOPE SHALL BE 1 TO 1, MINIMUM. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED OTHERWISE. 3. MINIMUM ANGLE SHALL BE 30^.

DRAWING RESPONSIBILITY:

ELECT. STD. REVIEW COMMITTEE


03 DEC95 ESSD CAB
ESSD MAQ GENERAL REVISION. REDRAWN AND ADDED MANDATORY DWG. NOTE. JO/EWO DESCRIPTION CHKD. CERT. APPD.

REVISED LM. CHNGD. MANDATORY


TO DWG. RESPONSIBILITY.
ORIGINAL ORIGINAL ORIGINAL SIGNED SIGNED SIGNED

02

MAR93

8
01 REV. NO. 04-15-87 DATE RLO BY

SAUDI
5
DRAWN BY DATE STARTED OPRG. DEPT. APPD. FOR CONSTR.

ARABIAN
CHECKED BY

OIL COMPANY
NAK 11/86
SCALE

LEMCO 11-02-82

NONE

DATE COMPLETED ENG. DEPT.

THIS DRAWING IS NOT TO BE USED FOR CONSTRUCTION OR FOR ORDERING MATERIAL UNTIL CERTIFIED AND DATED

CERTIFIED BY DATE

SEE NOTE 3

GUY AND ANCHORS

14.5K OR 18.8K, DOWN GUYS


FOR ANCHOR SEE DWG. AD-036064, AD-036066 & AD-036070

STD. DWG.
PLANT NO. INDEX DRAWING NUMBER

METRIC
SHEET NO. REV. NO.

990
CopyrightSaudi Aramco 2009. All rights reserved.

AD-036023 003