COMPARISON OF CAESAR -II & ROHR2 STRESS ANALYSIS REPORTS MAIN STEAM PIPE (HAH91-LBA10)

Description Direction FX North (N) = FY Vertical (N) = MAX INDUCED FORCES FZ West (N) = AND MOMENTS AT MX NORTH (N.M) = TERMINAL POINT MY Vertical (N.M) = MZ West (N.M) = DX North (mm) = THERMAL MOVEMENT AT TERMINAL POINT DY Vertical (mm) = DZ West (mm) = Induced in CAESAR-II 0 -30112 0 0 0 0 15.915 8.404 -75.236 -26.9 Induced in ROHR2 Allowable Forces & Moments AT Terminal Point F_North Max = Not critical F_ East_Max = 65 KN M_North Max = 15 KNm M_elev Max = 10 KNm M_ East_Max = 15 KNm Allowable Forces & Moments AT Terminal Point F_North Max = 35 KN F_elev Max = No Lift F_ East_Max = 35 KN M_North Max = 40 KNm M_elev Max = 15 KNm M_ East_Max = 40 KNm Allowable Forces & Moments AT Terminal Point F_North Max = 70 KN 30455 F_elev Max = 70 KN -6 F_ East_Max = 70 KN M_North Max = 35 KNm M_elev Max = 35 KNm M_ East_Max = 35 KNm -

-36852 F_elev Max = Not critical

HOT REHEAT PIPE (HAJ31-LBB10)


Description Direction FX North (N) = FY Vertical (N) = MAX INDUCED FORCES FZ West (N) = AND MOMENTS AT MX NORTH (N.M) = TERMINAL POINT MY Vertical (N.M) = MZ West (N.M) = DX North (mm) = THERMAL MOVEMENT AT TERMINAL POINT DY Vertical (mm) = DZ West (mm) = Induced in CAESAR-II -2051 -15963 4327 0 0 0 -26.803 0 59.43 Induced in ROHR2 -

COLD REHEAT (HAJ11-LBC10)


Description Direction FX North (N) = FY Vertical (N) = MAX INDUCED FORCES FZ West (N) = AND MOMENTS AT MX NORTH (N.M) = TERMINAL POINT MY Vertical (N.M) = MZ West (N.M) = DX North (mm) = THERMAL MOVEMENT AT TERMINAL POINT DY Vertical (mm) = DZ West (mm) = Induced in CAESAR-II -113 -398 40 0 0 0 -8.903 9.572 23.11 Induced in ROHR2 -