Roof Construction of Lot 2 of 883 #245 Lawrence St, Bedford

On-site training and design documentation provided by Garry Turner

2/04/13

Roof Construction of Lot 2 of 883 #245 Lawrence St, Bedford

Contents Page

Page

Part 1 : Australian Standard and Engineering details Extract from AS1684.2 Structural engineering for Job # C139463 C154312 Part 2 : Construction Scheduling guideline and roof take-offs Scheduling guideline Roof take-offs Notes

3 - 46 4 - 40 41 - 46 47 - 57 48 - 54 55 - 57 58 - 59

2/04/13

Roof Construction of Lot 2 of 883 #245 Lawrence St, Bedford

Part One : Australian Standard & Engineering details

2/04/13

1
RB18 BOLTED TO RB6 TO AS1684.EFFECTIVE MAX SPAN OF RB18 APPROX 3300mm.

CONSTRUCT SQUARE BULKHEAD AS PER 'BH7' DETAIL.

150 x 90 x 8 UA LINTEL UNDER TO INTERNAL BRICK LEAF.

CONSTRUCT AS PER 'Y11' DETAIL.

RB1 RB3 RB4

TIMBER ROOF NOTES 1. ALL TIMBERWORK TO BE IN ACCORDANCE WITH (a) AS1684 - 'RESIDENTIAL TIMBER FRAMED CONSTRUCTION'. (b) AS1720.1 - 'TIMBER STRUCTURES PART 1: DESIGN METHODS'. (c) BUILDING CODE OF AUSTRALIA 2. ALL FABRICATION AND ERECTION OF STEELWORK TO BE IN ACCORDANCE WITH AS4100 - STEEL STRUCTURES CODE. 3. ALL WELDING TO BE IN ACCORDANCE WITH AS1554 - PT 1 - WELDING OF STEEL STRUCTURES. 4. ALL DETAILS TO BE CHECKED AND SITE MEASURED, AS REQUIRED, PRIOR TO ORDERING. CHECK ANY DISCREPANCIES WITH THE ENGINEER. 5. ROOF TO BE TIED DOWN TO RESIST UPLIFT, AS REQUIRED IN AS1684 - TIMBER FRAMING CODE. 6. ALL STEELWORK (INCLUDING FASTENERS) TO BE TREATED IN ACCORDANCE WITH CLAUSE 3.4.4.4 "CORROSION PROTECTION" OF THE BUILDING CODE OF AUSTRALIA. 7. SPLAY STEEL BEAMS WHERE REQUIRED, TO SUIT ROOF PITCH. MIN END HEIGHT TO BE 60 mm. 8. TIMBER TO TIMBER CONNECTION TO BE VIA EX 10 PL ANGLE CLEAT AND 2M16 BOLTS TO EACH LEG. U.N.O. 9. TIMBER TO STEEL CONNECTION TO BE VIA EX 10 PL CLEAT FULLY WELDED TO WEB OF STEEL BEAM. 10. STEEL TO STEEL CONNECTION TO BE VIA EX 10 PL CLEAT FULLY WELDED TO WEB OF CONTINUOUS STEEL BEAM FIX INTERSECTING STEEL BEAM TO CLEAT VIA 2M16 BOLTS U.N.O. ALTERNATIVELY, STEEL BEAM MAY BE FULLY WELDED. 11. PARAPET FLASHING TO BE OVER PARAPET, NOT THROUGH. ALL GUTTERS, FLASHING AND CLADDING TO ARCHITECTURAL DETAILS. 12. ROOF BEAMS TO BE PLACED HORIZONTALLY AND MAY BE USED TO SUPPORT INDEPENDENT CEILING MEMBERS.

RB2 CANTILEVER RB6 MAX 900 TO SUPPORT HIP & UNDERPURLIN. RB15 RB18 RB6

ROOF MEMBER SCHEDULE


RB5

1
PROVIDE MIN 300mm BEARING TO END OF BEAM OVER WALL.

1
RB7 RB16 RB8 RB9 RB11

PW P

RB17

RB10 250 x 10 PL CONSTRUCT AS PER 'Y2' DETAIL. (TYPICAL)


12

50(150)

1
180 x 10 PL

T1

RB1 RB2 RB3 RB4 RB5 RB6 RB7 RB8 RB9 RB10 RB11 RB12 RB13 RB14 RB15 RB16 RB17 RB18

300 x 63 WESBEAM LVL 300 x 45 WESBEAM LVL 300 x 63 WESBEAM LVL 200 UB 18 300 x 45 WESBEAM LVL 360 x 63 WESBEAM LVL 240 x 45 WESBEAM LVL 240 x 45 WESBEAM LVL 240 x 45 WESBEAM LVL 240 x 45 WESBEAM LVL 200 x 45 WESBEAM LVL 200 x 45 WESBEAM LVL 200 x 45 WESBEAM LVL 250 UB 25 300 x 63 WESBEAM LVL 300 x 45 WESBEAM LVL 200 x 45 WESBEAM LVL 200 x 45 WESBEAM LVL

PW P

PW P

R B 12

*
RB13 RB14 T-LINTEL T1 UNDER.

B 12

T-LINTELS
- 250 END BEARING - 2 L6 GALV HD WIRES IN FIRST 2 BED JOINTS OF EACH LEAF, 500 LAPS, 20 SIDE COVER. (SPANS OVER 4.8m ONLY) - 180 x 10 PL BOTTOM FLANGE AT 190 BRICKWORK LOCATIONS. - ALL STEELWORK TO BE TREATED IN ACCORDANCE WITH CLAUSE 3.4.4.4 "CORROSION PROTECTION" OF THE BUILDING CODE OF AUSTRALIA. - MITRE CUT & FULLY WELD INTERSECTING LINTELS AT CORNERS. USE MESH. ALL OTHER SLAB AND FOOTING DETAILS AS PER PREVIOUSLY ISSUED DETAIL. PWP = PERTH WIND POST. REFER TO "GP205 - SUPPORT TO WALL" DETAIL FOR FIXING DETAILS. CERTIFICATION OF MASONRY WALLS DESIGNED TO COMPLY WITH AS3700 AND PROVISION p2.1 OF THE BCA. IT IS THE RESPONSIBILITY OF THE BUILDER TO INFORM THE OWNER OF THE IMPORTANCE OF MAINTAINING EXTERNAL STRUCTURAL TIMBERS BY WAY OF PAINTING OR SIMILAR PROTECTION.

WIND CLASSIFICATION = N1 MASONRY WALL INCLUDING GARAGE PIERS AND ROOF BEAM CERTIFICATION
1 REVISION PROJECT GTU ENG. ROOF BEAMS AMENDED & FREE STANDING PIER DETAILS ADDED DETAILS C154312 JOB No. 08/03/13 DATE

CLIENT

LOT 2 of LOT 883 (#245) LAWRENCE ST BEDFORD G H F T BUILDING SERVICES for TURNER

SL63

*
PROVIDE 1L10 GALV ROD CENTRAL TO PIER. WELD ROD TO A 150 x 50 x 8PL BASEPLATE FIXED TO FOOTING VIA 2M10 MASONRY ANCHORS. ALTERNATIVELY, BEND ROD AT TOP OF FOOTING LEVEL AND HOOK INTO GRANO SLAB. SECURELY FIX TO ROOF MEMBER OVER (TYPICAL AT LOCATIONS) ALTERNATIVELY, PROVIDE PIERS AS PER PART 3.3.1 OF THE NCC.

APPROVED Zemla Pty Ltd (ABN 71 349 772 837) ATF the Young Purich and Higham Unit Trust trading as Structerre Consulting Engineers

ROOF PLAN
(METAL ROOF)

1:100

B.E. M.I.E. (AUST) APPROVED FOR ISSUE

1 ERINDALE ROAD, BALCATTA W.A. 6021 TEL 9205 4500 FAX 9205 4501 EMAIL: residential@structerre.com.au
SCALE ON A3 DESIGNED

DATE

SHEET N

PROJECT N

1:100

Garry Turner

27/04/12

1 of 6

C139463

MIN 90 x 90 x 2.0 SHS COLUMN, 2M10 BOLTS TO BEAM OVER. MIN 90 x 90 x 2.0 SHS COLUMN, 2M10 BOLTS TO BEAM OVER. MIN 90 x 90 x 2.0 SHS COLUMN BEYOND WHERE APPLICABLE. BRICKWORK TO BUILDER'S DETAIL, WHERE REQUIRED.

MIN 90 x 90 x 2.0 SHS COLUMN, 2M10 BOLTS TO BEAM OVER.

200 x 200 x 10 BASE PLATE 2M12 MEDIUM DUTY ANCHORS GROUT BED.

BRICKWORK TO BUILDER'S DETAIL, WHERE REQUIRED.

200 x 100 x 10 BASE PLATE 2M12 MEDIUM DUTY ANCHORS GROUT BED.

300 MIN

300 MIN

MASS CONCRETE

EX 10 PL BASEPLATE WITH MEDIUM DUTY ANCHORS AS PER SECTION X. GROUT BED.

X
450 MASS CONCRETE

600 (x 600) MIN (TO SUIT PIER SIZE)

300 MIN

300 MIN

MASS CONCRETE 450 (x 450) 600 (x 600) MIN (TO SUIT PIER SIZE)

FOOTING AND STEEL POST


M12 MEDIUM DUTY ANCHORS. M12 MEDIUM DUTY ANCHORS.

NOTES:
1. DETAIL SUITABLE FOR TILED OR METAL ROOFS ON GENERAL VERANDAHS AND CARPORTS. 2. THE DETAIL ONLY PROVIDES LIMITED LATERAL STABILITY. IF THE OVERALL ROOF STRUCTURE DOES NOT PROVIDE LATERAL STABILITY TO THE STRUCTURE, CONTACT THE ENGINEER FOR ADVICE. 3. REFER TO THE ARCHITECTURAL DRAWINGS FOR PIER, POST AND BEAM SIZES. 4. MAXIMUM ROOF AREA SUPPORTED BY POST TO BE 10m 2. 5. ALL STEELWORK TO BE TREATED IN ACCORDANCE WITH CLAUSE 3.4.4.4 "CORROSION PROTECTION" OF THE BUILDING CODE OF AUSTRALIA.

SECTION X
(TWO POST LOCATIONS)

SECTION X
(THREE POST LOCATIONS)

FOOTING AND STEEL POST


THIS DETAIL IS ONLY TO BE USED WHEN CARPORT/VERANDAH IS SUBSTANTIALLY CONNECTED TO HOUSE ROOF NOTE: MIN 450mm SAND UNDER FOOTING FOR CLASS M SITES (SEE NOTE 5 BELOW) NOTES:
1. REMOVE ALL TOPSOIL, VEGETATION AND DELETERIOUS FILL MATERIAL FROM THE BUILDING AREA. 2. ROOF AND SURFACE WATER TO BE TAKEN AWAY FROM FOUNDATION AREA TO SITE DRAIN. (DRAIN TO LOCAL AUTHORITY STORM WATER SYSTEM WHERE APPROPRIATE). 3. EXCAVATIONS FOR PLUMBING NOT TO UNDERMINE FOOTINGS. IF UNDERMINING IS LIKELY TO OCCUR, CONTACT THE ENGINEER. 4. CONCRETE TO CONFORM WITH AS 3600. 5. ALL CONCRETE TO BE N20/20/80. 6. DETAIL SUITABLE FOR TILED OR METAL ROOFS ON GENERAL VERANDAHS AND CARPORTS. 7. THE DETAIL ONLY PROVIDES LIMITED LATERAL STABILITY. IF THE OVERALL ROOF STRUCTURE DOES NOT PROVIDE LATERAL STABILITY TO THE STRUCTURE, CONTACT THE ENGINEER FOR ADVICE. 8. REFER TO THE ARCHITECTURAL DRAWINGS FOR PIER, POST AND BEAM SIZES. 9. MAXIMUM ROOF AREA SUPPORTED BY POST TO BE 10m 2. 10. A MIN OF 150mm OF SAND REQUIRED UNDER FOOTINGS FOR CLASS A & S SITES. MIN 450 SAND REQUIRED UNDER FOOTING FOR CLASS M SITES. 11. ALL STEELWORK TO BE TREATED IN ACCORDANCE WITH CLAUSE 3.4.4.4 "CORROSION PROTECTION" OF THE BUILDING CODE OF AUSTRALIA.

1 REVISION PROJECT

GTU ENG.

ROOF BEAMS AMENDED & FREE STANDING PIER DETAILS ADDED DETAILS

C154312 JOB No.

08/03/13 DATE

CLIENT

LOT 2 of LOT 883 (#245) LAWRENCE ST BEDFORD G H F T BUILDING SERVICES for TURNER

APPROVED Zemla Pty Ltd (ABN 71 349 772 837) ATF the Young Purich and Higham Unit Trust trading as Structerre Consulting Engineers

B.E. M.I.E. (AUST) APPROVED FOR ISSUE

1 ERINDALE ROAD, BALCATTA W.A. 6021 TEL 9205 4500 FAX 9205 4501 EMAIL: residential@structerre.com.au

Y2

Y11

SCALE ON A3

DESIGNED

DATE

SHEET N

PROJECT N

1:20

Garry Turner

27/04/12

2 of 6

C139463

NOTES:

1. THIS DETAIL IS TO PROVIDE LINTEL SIZES ONLY. 2. REFER TO BUILDER'S SPECIFICATIONS FOR ROOF & CEILING MEMBER SIZES AND SPACINGS. 3. REFER TO TRUSS MANUFACTURER'S SPECIFICATIONS FOR DETAILS OF ROOF TRUSS SIZES AND SPACINGS. 4. LINTELS ARE DESIGNED TO SUPPORT UP TO 10c OF BRICKWORK & UP TO 3.6m OR 6.6m OF TILED OR METAL ROOF & A CEILING. 5. DO NOT SUPPORT ROOF STRUTTING BEAMS OR OTHER POINT LOADS OVER THE LINTEL. 6. MINIMUM REINFORCEMENT TO BRICKWORK OVER LINTELS TO BE AS PER THE SPECIFIED FOOTING DETAIL OR AS PER THE NOTE SHOWN ON THE DETAIL. 7. REINFORCEMENT SHALL BE IN ACCORDANCE WITH THE FOLLOWING STANDARDS; L INDICATES PLAIN OR DEFORMED WIRE R500L OR D500L TO AS/NZS 4671. ALL STEELWORK TO BE TREATED IN ACCORDANCE WITH CLAUSE 3.4.4.4 "CORROSION PROTECTION" OF THE BUILDING CODE OF AUSTRALIA. 8. A BRICK COURSE, AS REFERRED TO IN THIS DOCUMENT IS STANDARD 86mm HIGH. 9. IT IS PERMISSIBLE TO ADJUST THE SPAN BY ROUNDING TO THE NEAREST BRICK LENGTH, SUBJECT TO IT BEING NO MORE THAN 20mm.

TILED OR METAL

PARGE TO BUILDERS DETAIL

1c MAX

ROOF CONSTRUCTION TO ARCHITECTURAL REQUIREMENTS EAVES SOFFIT SUPPORT AND FASCIA TO BUILDER'S DETAIL.

ROOF CONSTRUCTION TO ARCHITECTURAL REQUIREMENTS WALL PLATE AS PER MANUFACTURERS 10c SPECIFICATION. MAX REINFORCEMENT EFFECTIVE WIDTH 3.6m : SPANS OVER 4400. EFFECTIVE WIDTH 6.6m : SPANS OVER 3000. (SEE NOTE 6 ABOVE). REINFORCEMENT TO BE 2L6 H.D. WIRES, 20 SIDE COVER & CONTINUE 500 PAST EDGE OF OPENING. STEEL ANGLE LINTEL. SEE TABLE BELOW. SLAB THICKNESS & REINFORCEMENT TO SEPERATE DETAIL.

190 MIN 290 MIN 50 MIN 490 MIN 390 MIN 50 MIN

2c MAX 2c MAX

3c MAX

WALL POSITION FOR SQUARE BULKHEAD OR NO EAVES.

2c MAX

WALL POSITION FOR STANDARD EAVES.

280 MASS CONCRETE

SQUARE BULKHEAD / EAVES LINTEL DETAIL LINTEL SPANS


TILED ROOF
EFFECTIVE WIDTH 3600 mm 6600 mm LINTEL BEARING LINTEL BEARING
100 100 110 120 135 150 165 180 200 220 250 90 x 90 x 8.0 EA 100 x 100 x 8.0 EA 150 x 90 x 8.0 UA 150 x 90 x 8.0 UA 150 x 90 x 10.0 UA T-LINTEL T1 T-LINTEL T1 T-LINTEL T1 T-LINTEL T1 T-LINTEL T2 T-LINTEL T2 100 120 150 165 180 200 250 280 300 320 350

1:20
TO SUIT HEIGHT (500 MIN)

METAL ROOF
EFFECTIVE WIDTH 3600 mm 6600 mm LINTEL BEARING LINTEL BEARING
75 x 75 x 6.0 EA 75 x 75 x 8.0 EA 100 x 100 x 6.0 EA 100 x 100 x 8.0 EA 125 x 75 x 8.0 UA 125 x 75 x 10.0 UA 150 x 90 x 8.0 UA 150 x 90 x 10.0 UA T-LINTEL T1 T-LINTEL T1 T-LINTEL T2 50 x 50 x 4.0 RHS 100 100 110 120 135 150 165 180 200 220 250 75 x 75 x 6.0 EA 90 x 90 x 6.0 EA 125 x 75 x 6.0 UA 125 x 75 x 8.0 UA 125 x 75 x 10.0 UA 150 x 90 x 8.0 UA 150 x 100 x 10.0 UA T-LINTEL T1 T-LINTEL T1 T-LINTEL T1 T-LINTEL T2 100 120 150 165 180 200 250 280 300 320 350

NOTES:
1. THIS WALL IS DESIGNED FOR USE IN STABLE SAND OR ROCK SOILS WITH FREE DRAINING GRANULAR BACKFILL. MAXIMUM WATER TABLE TO BE BELOW FOOTING LEVEL. IF OTHER CONDITIONS ENCOUNTERED ON SITE CONTACT THE ENGINEER. 2. REMOVE ALL TOPSOIL, VEGETATION & DELETERIOUS FILL MATERIAL FROM THE FOUNDATION AREA. 3. COMPACT THE FOUNDATION LINE TO MIN 6 BLOWS / 300mm (AS TESTED WITH THE PERTH SAND PENETROMETER) FOR A DEPTH OF AT LEAST 750mm BELOW FOOTING. 4. RECOMPACT SAND IN FRONT OF WALL AFTER COMPLETION TO MIN 5 BLOWS / 300mm 5. CONCRETE TO BE N20/20/80. 6. ALL BRICKWORK TO BE TO AS 3700. MIN UNCONFINED COMPRESSIVE STRENGTH OF BRICKS TO BE 10MPa. MIN DENSITY OF BRICKS TO BE 1800kg/m3 . 7. A BRICK COURSE, AS REFERRED TO IN THIS DOCUMENT IS STANDARD 86mm HIGH. 8. ALL JOINTS TO BE MORTARED. MORTAR TO BE M3 CLASSIFICATION, EXCEPT PROJECTS LOCATED WITHIN 1km OF THE OCEAN MORTAR TO BE M4 CLASSIFICATION. CEMENTS OTHER THAN TYPE GP PORTLAND CEMENT & 100% WHITE PORTLAND CEMENT SHALL NOT BE USED. 9. PROVIDE MASONRY TIES IN VERTICAL JOINTS BETWEEN LEAVES, AT MAX 4c CENTRES VERTICALLY AND MAX 600mm CENTRES HORIZONTALLY. 10.PROVIDE 10mm EXPANSION JOINTS AT MAX 7000 CENTRES IN STRAIGHT LENGTHS OF WALL. 11.DO NOT BACKFILL WALL UNTIL AT LEAST 5 DAYS AFTER COMPLETION. 12.BACKFILL TO BE COMPACTED TO MIN 6 BLOWS/300mm. BACKFILL WITHIN 1m OF WALL MAY BE COMPACTED TO MIN 4 BLOWS/300mm. 13.ENSURE NO DEAD LOAD (INCLUDING BUILDINGS) IS PLACED CLOSER TO THE UPHILL FACE OF THE WALL THAN A DISTANCE EQUAL TO THE TOTAL HEIGHT OF THE WALL. MAXIMUM SURCHARGE LOAD TO BE 5 kPa WHICH INCLUDES LIGHT VEHICLE SURCHARGE LOAD. 14.ENSURE THE WALL DOES NOT SURCHARGE OR UNDERMINE ANY ADJACENT RETAINING WALLS OR STRUCTURES EITHER ON THIS OR ADJOINING PROPERTIES. 15.DO NOT BUILD OVER OR ADJACENT TO ANY WATER AUTHORITY SEWERS WITHOUT WATER CORPORATION APPROVAL. 16.REINFORCEMENT SHALL BE IN ACCORDANCE WITH THE FOLLOWING STANDARDS; SL INDICATES DEFORMED SQUARE MESH D500L TO AS/NZS 4671. ALL STEELWORK TO BE TREATED IN ACCORDANCE WITH CLAUSE 3.4.4.4 "CORROSION PROTECTION" OF THE BUILDING CODE OF AUSTRALIA.

MASS BRICK RETAINING WALL

OPENING

UP TO 1500 75 x 75 x 8.0 EA UP TO 1800 90 x 90 x 8.0 EA UP TO 2200 125 x 75 x 6.0 UA UP TO 2400 125 x 75 x 8.0 UA UP TO 2700 150 x 90 x 8.0 UA UP TO 3000 150 x 90 x 8.0 UA UP TO 3300 T-LINTEL T1 UP TO 3600 T-LINTEL T1 UP TO 4000 T-LINTEL T1 UP TO 4400 T-LINTEL T1 UP TO 5000 T-LINTEL T2

100 x 50 x 4.0 RHS 5 50(150) 5 50(150)

200 x 10 PL

50(150)

50(150)

50(150)

1 REVISION PROJECT

GTU ENG.

ROOF BEAMS AMENDED & FREE STANDING PIER DETAILS ADDED DETAILS

C154312 JOB No.

08/03/13 DATE

200 x 10 PL

T1
250 x 10 PL 5 50(150)

2N 150 x 90 x 8.0 UA LINTELS.

2N 150 x 90 x 8.0 UA LINTELS.

CLIENT

T1 ALTERNATIVE

T2 ALTERNATIVE

LOT 2 of LOT 883 (#245) LAWRENCE ST BEDFORD G H F T BUILDING SERVICES for TURNER

200 x 10 PL

T2

APPROVED Zemla Pty Ltd (ABN 71 349 772 837) ATF the Young Purich and Higham Unit Trust trading as Structerre Consulting Engineers

B.E. M.I.E. (AUST) APPROVED FOR ISSUE

1 ERINDALE ROAD, BALCATTA W.A. 6021 TEL 9205 4500 FAX 9205 4501 EMAIL: residential@structerre.com.au
SCALE ON A3 DESIGNED

BH7

J15

DATE

SHEET N

PROJECT N

1:20

Garry Turner

27/04/12

3 of 6

C139463

SPECIFICATION
1. WIND CLASSIFICATION 2. PHYSICAL CONDITIONS
2.1 2.2 a) METAL DECK ROOF CLADDING TIMBER FRAMED ROOF STRUCTURE, DESIGNED AND CONSTRUCTED STRICTLY IN ACCORDANCE WITH AS1684 - TIMBER FRAMING CODE. b) TIMBER TRUSS ROOF STRUCTURE, DESIGNED AND CONSTRUCTED STRICTLY IN ACCORDANCE WITH AS1720 - TIMBER STRUCTURES CODE. c) STEEL TRUSS ROOF STRUCTURE, DESIGNED AND CONSTRUCTED STRICTLY IN ACCORDANCE WITH AS1538 - COLD FORMED STEEL STRUCTURES CODE. 2.3 ROOF PITCH LESS THAN 35 2.4 MAXIMUM RAFTER SPACING 900mm MAXIMUM TRUSS SPACING 1200mm 2.5 MAXIMUM BATTEN SPACING 1200mm 2.6 REFER TO SECTION 9 OF AS1684 FOR TIE DOWN REQUIREMENTS OF UNDERPURLINS OR TO BUILDER'S DETAIL. 2.7 WALL PLATE MIN 70 x 35mm THICK MGP10 (U.N.O.) WALL PLATE C7510 (STEEL TRUSSED ROOF) 2.8 WALL PLATES SUPPORTING MAXIMUM 3m RLW AS DEFINED IN AS1684. FOR RLW GREATER THAN 3m REFER BACK TO THE ENGINEER. 2.9 ALL TRUSSES SUPPORTING OTHER TRUSSES (GIRDER TRUSSES OR SIMILAR) ARE TO BE TIED DOWN SIMILAR TO ROOF STRUTTING BEAM. MAXIMUM UPLIFT LOAD TO BE 15kN TO BE CONFIRMED BY ROOF TRUSS MANUFACTURER.

4.5 N1
4.5.1 4.5.2

ALL BEAMS (EXCEPT CEILING ONLY BEAMS)


TIMBER BEAMS TO AS 1684. AT LOCATIONS AWAY FROM GABLES\ AND WHERE A ROOF BEAM ALSO SUPPORTS AN INDEPENDANT CEILING FRAME, SUCH AS COUNTER/STRUTTING BEAMS OR HANGER/STRUTTING BEAMS, NO TIE DOWNS WILL BE REQUIRED EXCEPT FOR THOSE ENDS WHICH BEAR ONTO THE EXTERNAL PERIMETER WALLS OF THE BUILDING. TIE DOWN THESE ENDS AS PER NOTE 4.5.3 BELOW. U.N.O. IN AS1684, MIN TIE DOWN TO ALL STEEL AND TIMBER ROOF BEAMS TO EXTERNAL WALL IS 1R10 ROD (OR THREE 30 x 0.8 PGI STRAPS) THREADED AT TOP AND BOLTED TO BEAM ABOVE OR MIN 60mm LONG WELD TO BEAM ABOVE. PROVIDE 90 x 90 BASEPLATE FULLY WELDED TO BASE OF ROD AND EMBED INTO BRICK WALL OR COG ROD MIN 75 INTO WALL AT BASE. ALTERNATIVELY, FULLY WELD TO LINTEL BELOW. FIX LINTEL AT EACH END AS PER THE REQUIREMENT NOTED FOR THE ROOF BEAM. IF CONCRETE SLAB OR BRICK WALL NOT PROVIDED, CONTACT ENGINEER BEFORE PROCEEDING.

PRE-PUNCHED VERTICAL DRIP GROOVES TO PREVENT MOISTURE TRANSFER ACROSS CAVITY. [1c] 50

RAFTER (SHOWN) AND/OR CEILING JOISTS AS APPLICABLE. FIX TO TOP PLATE WITH 2 x 12g TYPE 17 TEKS x 35 LONG MIN.

4.5.3

PRE-PUNCHED TABS TO BE BENT OUT TO EXTEND INTO BED JOINTS.

DETAIL A Z5012 (HEAVILY GALVANISED). BEND OUT AND BUILD TAB PAIRS INTO BED JOINT EVERY SECOND COURSE VERTICALLY STARTING AT THE 0c LEVEL. POSITION WIND POST STIFFENER DIRECTLY ONTO FOOTING OR 2c BELOW FFL (WHICHEVER IS LESS) AND BUILD INTO WALL. NO NEED FOR ANY MECHANICAL FIXING. ENSURE BOND OF BRICKWORK TO FOOTING IS GOOD AND ALL SAND IS REMOVED PRIOR TO PLACING MORTAR. BEND PWP BASE TABS OUT INTO BED JOINTS EACH SIDE. FIX AS PER NOTE 3 WHEN REQUIRED, TO SUIT TIEDOWN LOADS ONLY. ANCHOR NOT REQUIRED FOR UP TO 7kN UPLIFT TIEDOWN LOADS.

4.6
4.6.1 4.6.2 4.6.3 4.6.4 4.6.5

RAFTERS (SEE DETAILS 1 & 2)


FIX RAFTERS TO THE WALL PLATE USING 2N 75 x MIN 2.8 SKEW NAILS AND A MITEK TWIST RAFTER GRIP OR ALTERNATIVELY USE 1N TRIP-L-GRIP CONNECTOR. (EXCEPT AS NOTED IN 4.1.1b) FIX RAFTERS TO CARPORT OR VERANDAH PITCHING BEAMS USING 1N TRIP-L-GRIP CONNECTOR (OR EQUIVALENT). TRIP-L-GRIP CONNECTORS TO BE FIXED WITH MIN 3N 2.8 GALV CONNECTOR NAILS PER TAB. FIX RAFTERS TO INTERNAL BEAMS AND UNDERPURLINS AS PER NOTE 4.6.1 (EXCEPT AS PER NOTE 4.6.5) AT RIDGES AND HIPS, PROVIDE A 30 x 0.8 PGI STRAP x 600mm LONG OVER THE TOP OF THE RAFTER (ACROSS THE JOINT) AND FIX WITH MIN 4N 2.8 GALV. CONNECTOR NAILS EACH SIDE. FIX RAFTERS TO RIDGE AND HIPS VIA 2 N 75 x MIN 2.8 SKEW NAILS.

DETAIL A 1:10
Z50 12 TABS WIRE TIES. REFER TO NOTE 4 FOR DETAILS. 3000 MAX

3. DESIGN CRITERIA
3.1 RELEVANT AUSTRALIAN STANDARDS a) AS 1538 - COLD FORMED STEEL STRUCTURES b) AS1170.2 - LOADING CODE - WIND LOADS c) AS1288 - GLASS IN BUILDINGS d) AS1684 - 'RESIDENTIAL TIMBER FRAMED CONSTRUCTION'. e) AS1720.1 - 'TIMBER STRUCTURES PART 1: DESIGN METHODS'. f) AS 4055 - WIND LOADS FOR HOUSING DESIGN WIND VELOCITY 34 m/s (ULTIMATE LIMIT STATE) DESIGN WIND PRESSURE FOR GLAZING: a) UP TO 1.2m FROM CORNER = 1.04 kPa b) GREATER THAN 1.2m FROM CORNER = 0.69 kPa

4.7
4.7.1

TRUSSES
FIX TRUSSES TO WALL PLATES AS PER MANUFACTURER'S SPECIFICATIONS. TRUSSES MAY EXCEED 3m RLW. IF THIS IS THE CASE, CONTACT STRUCTERRE BEFORE PROCEEDING.

3.2 3.3

4.8
4.8.1

BATTENS

4. TIE DOWN DETAILS 4.1 4.1.1 WALL PLATES SUPPORTING ROOF


a) TIE DOWN WALL PLATE WITH 30 x 0.8mm PGI STRAPS (OR EQUIVALENT) AT EACH SIDE OF CORNERS AND OPENINGS AND AT 1200mm CRS MAX ELSEWHERE. FIX STRAPS TO WALL PLATE WITH 3 N MIN 2.8mm GALV. CONNECTOR NAILS (USE 2 N 10 x 16 TEKS FOR STEEL TRUSSES). b) IF THE TIE DOWN STRAPS ARE EXTENDED UP AND FIXED TO A BATTEN (SIZE BATTEN AS PER AS1684, MIN SIZE 70 x 35 MGP10) OR FIXED DIRECTLY TO EACH TRUSS/RAFTER, RAFTERS MAY BE FIXED TO THE WALL PLATE VIA 2N 75 x 2.8 SKEW NAILS AND A NON-STRUCTURAL WALL PLATE MAY BE USED (NOT APPLICABLE FOR STEEL TRUSS ROOF STRUCTURES). BUILD STRAPS MIN 75mm INTO BED JOINT MIN 12c DOWN. WHERE OVER OPENINGS, SHOT FASTEN OR WELD STRAPS TO LINTEL OR PROVIDE 300mm R6 LOOP WELDED 25mm EACH END OF ROD TO TOP OF LINTEL. FIX LOOPED STRAP TOGETHER WITH 4 N 10 TEKS (OR ALTERNATIVELY, LOOP STRAP THROUGH LINTEL AND FIX EACH END TO ROOF FRAME AS PER CLAUSE 4.1.1 ABOVE). AT EACH SIDE OF ALL OPENINGS OVER 2.4m WIDE AND LESS THAN 6m WIDE, PROVIDE A FULL WALL HEIGHT STRAP. FOR OPENINGS OVER 6m WIDE, CONTACT STRUCTERRE FOR ALTERNATIVE DETAIL, OR USE TWO 30 x 0.8 PGI STRAPS OR 10 TIE DOWN AS PER ROOF STRUTTING BEAMS. WHERE STRAPS ARE POSITIONED NEXT TO A RAFTER OR TRUSS, IT IS PERMISSIBLE TO FIX TO SIDE OF RAFTER. EXTEND OVER RAFTER AND FIX TO OPPOSITE SIDE WITH 4 N MIN 2.8 CONNECTOR NAILS. (NOT APPLICABLE FOR STEEL TRUSS ROOF STRUCTURES).

FIX TIMBER BATTENS TO RAFTERS OR TIMBER TRUSSES AS PER THE FOLLOWING TABLE: BATTEN LOCATION WITHIN 1.2m OF HIPS, GENERAL ROOF AREA RIDGES & EAVES BATTEN FIXING 1N 14 TYPE 17 x 75 TEK 2N 75 x 3.05 DEFORMED SHANK NAILS OR 1N 14 TYPE 17 x 75 TEK WHERE STEEL BATTENS ARE USED, FIX BATTENS TO TIMBER TRUSSES/RAFTERS USING TWO 2.5 x 57mm LONG NAILS. FIX BATTENS TO STEEL TRUSSES USING 2 N 10 x 16 TEKS.

SECTION B 1:10
50

50

4.8.2 4.8.3

50 FOOTING AND SLAB TO SEPARATE DETAILS.

4.1.2

4.9
4.9.1

ROOF CLADDING
ROOF CLADDING TO BE FIXED TO MANUFACTURERS DETAILS FOR N1 CLASSIFICATION AS PER AS4055.

4.1.3

STRAP OVER RIDGE (NOTE 4.6.5)


FIX AS PER NOTE 4.6.4

Z5012
PERTH WIND POST 1:5
MANUFACTURE FROM G250 1.2 STEEL.

4.1.4

SUPPORT TO WALL DETAIL


PERTH WIND POST - PWP 1:20

4.2
4.2.1 4.2.2 4.2.3

VERANDAH OR CARPORT (PITCHING) BEAMS


FIX BEAMS TO POSTS WITH 2M10 BOLTS. FIX BEAMS TO PIERS/WALL WITH FULL HEIGHT10 ROD (OR THREE 30 x 0.8 PGI STRAPS) BUILT INTO PIER/WALL. MAXIMUM BEAM SPAN TO BE 6m.

4.3
4.3.1 4.3.2

LINTELS AND COLUMNS AT WINDOW JUNCTION


WELD OR STRAP FASTEN THE LINTEL (TO WHICH THE ROOF TIE DOWN STRAPS ARE FIXED) TO THE COLUMN, USING 2 N 10 x 16 TEKS. PROVIDE 8mm BASE PLATE TO COLUMN AND FIX TO FLOOR SLAB OR TO FOOTING WITH 2M12 MASONRY ANCHORS, OR ALTERNATELY CONTINUE THE STRAP DOWN TO THE FLOOR SLAB AND BOLT TO THE SIDE OF THE SLAB USING 1 M12 BOLT.

FIX AS PER NOTE 4.6.1

RIDGE STRAP MAY BE REMOVED IF MIN 70 x 35 TIE IS LOCATED UNDER RIDGE AND FIXED TO EACH RAFTER VIA 3 N 75 x 2.8 NAILS EACH END.

BEND TABS OUT FROM COLUMN BASE.

PWP BASE TAB OPTION DETAIL 1:20

DETAIL 1

PWP BASE TABS

1:5
1 REVISION PROJECT GTU ENG. ROOF BEAMS AMENDED & FREE STANDING PIER DETAILS ADDED DETAILS C154312 JOB No. 08/03/13 DATE

4.4
4.4.1 4.4.2

INTERNAL BEAMS (RAKING CEILINGS)


TIE DOWN EACH END WITH MIN 0.9m LONG 10 GALV. ROD (OR EQUIVALENT). COG ROD MIN 150mm INTO WALL OR WELD ON 90 SQ x 6mm BASE PLATE AND BUILD IN. TIE DOWN ROD MAY BE LOCATED IN CAVITY OR CHASED MAX 10mm INTO THE WALL.

FIX AS PER NOTE 4.6.1


FIX AS PER NOTE 4.6.2

DETAIL 2

NOTE: THIS DESIGN IS PROTECTED BY COPYRIGHT AND PROVISIONAL PATENT WITH STRUCTERRE HOLDING EXCLUSIVE LICENCE TO DESIGN.
NOTES:
1. MAXIMUM HEIGHT OF WALL TO BE 3.0m TO CEILING LEVEL. 2. IN COASTAL CONDITIONS USE STAINLESS STEEL Z5012 (WITH EITHER STAINLESS STEEL OR PLASTIC WIRE TIES IN ACCORDANCE WITH AS 3700). 3. MAXIMUM 7kN UPLIFT CAPACITY (10kN IF BASEPLATE PROVIDED & FIXED TO SLAB VIA 1M10 MEDIUM DUTY ANCHOR & FIXED TO PWP VIA 2N 10 TEKS). THIS CAPACITY ONLY SUITABLE WHERE PWP IS LOCATED IN A CAVITY WALL A MINIMUM OF 1000mm LONG. 4. PLACE WIRE TIES EACH SIDE OF STIFFENER IN PAIRS AT 4c SPACING VERTICALLY LOCATED IMMEDIATELY ADJACENT.

CLIENT

LOT 2 of LOT 883 (#245) LAWRENCE ST BEDFORD G H F T BUILDING SERVICES for TURNER

APPROVED Zemla Pty Ltd (ABN 71 349 772 837) ATF the Young Purich and Higham Unit Trust trading as Structerre Consulting Engineers

B.E. M.I.E. (AUST) APPROVED FOR ISSUE

NOTE: A 25 x 1.2 STRAP IS EQUIVALENT TO A 30 x 0.8 STRAP.

DISCLAIMER This specification is provided as a guide to good practice as outlined in the specified standards. It will not necessarily provide the optimum solution in all cases. It is assumed that the persons using this specification have sound knowledge of building and understand the general principles involved in constructing roofs to resist wind uplift. If required, Structerre can endorse architectural plans to confirm site specific requests.

1 ERINDALE ROAD, BALCATTA W.A. 6021 TEL 9205 4500 FAX 9205 4501 EMAIL: residential@structerre.com.au
SCALE ON A3 DESIGNED

ROOF TIE DOWN SPECIFICATION


WIND CLASSIFICATION: ROOF CLADDING: N1 METAL

GP205

DATE

SHEET N

PROJECT N

1:20

Garry Turner

27/04/12

4 of 6

C139463

75 x 50 x 8 UA

50

100 x 75 x 8 UA 5 50 (175)
230 - 235

75

50 (150)

210 - 215

TILED OR METAL
OPENING
ROOF CONSTRUCTION TO ARCHITECTURAL REQUIREMENTS
UP TO 1500 UP TO 1800 UP TO 2200 UP TO 2400 UP TO 2700 UP TO 3000 UP TO 3300 UP TO 3600 UP TO 4000 UP TO 4400 UP TO 5000

LINTEL SPANS
TILED ROOF
EFFECTIVE WIDTH 3600 mm 6600 mm LINTEL BEARING LINTEL BEARING
75 x 75 x 6 EA 75 x 75 x 8 EA 100 x 100 x 6 EA 125 x 75 x 6 UA 125 x 75 x 10 UA 150 x 90 x 8 UA 150 x 90 x 10 UA TYPE 'A' LINTEL TYPE 'A' LINTEL TYPE 'A' LINTEL TYPE 'A' LINTEL 100 100 110 120 135 150 165 180 200 220 250 75 x 75 x 8 EA 100 100 x 75 x 8 UA 120 125 x 75 x 10 UA 150 150 x 90 x 8 UA 165 150 x 90 x 10 UA 180 TYPE 'A' LINTEL 200 TYPE 'A' LINTEL 250 TYPE 'A' LINTEL 280 TYPE 'B' LINTEL 300 TYPE 'B' LINTEL 350 CONSULT ENGINEER

METAL ROOF
EFFECTIVE WIDTH 3600 mm 6600 mm LINTEL BEARING LINTEL BEARING
75 x 75 x 6 EA 75 x 75 x 6 EA 90 x 90 x 6 EA 100 x 75 x 8 UA 100 x 100 x 8 EA 125 x 75 x 8 UA 125 x 75 x 10 UA 150 x 90 x 8 UA 150 x 100 x 10 UA TYPE 'A' LINTEL TYPE 'A' LINTEL 100 100 110 120 135 150 165 180 200 220 250 75 x 75 x 6 EA 90 x 90 x 6 EA 100 x 100 x 8 EA 125 x 75 x 6 UA 125 x 75 x 8 UA 150 x 90 x 8 UA 150 x 100 x 10 UA TYPE 'A' LINTEL TYPE 'A' LINTEL TYPE 'A' LINTEL TYPE 'A' LINTEL 100 120 150 165 180 200 250 280 300 320 350

50 (175)

50 (150)

150 x 90 x 8 UA

150 x 90 x 8 UA

FABRICATED LINTEL TYPE 'A'

FABRICATED LINTEL TYPE 'B'

EAVES SOFFIT SUPPORT AND FASCIA TO BUILDER'S DETAIL.

WALL POSITION FOR SQUARE BULKHEAD, WITH OPENINGS WHERE APPLICABLE

WALL POSITION FOR STANDARD EAVES, WITH OPENINGS WHERE APPLICABLE

WALL PLATE AS PER MANUFACTURERS 3c MAX SPECIFICATION. REINFORCEMENT EFFECTIVE WIDTH 3.6m : SPANS OVER 4400. EFFECTIVE WIDTH 6.6m : SPANS OVER 3000. (SEE NOTE 6 ABOVE). REINFORCEMENT TO BE 2L6 H.D. WIRES, 20 SIDE COVER & CONTINUE 500 PAST EDGE OF OPENING. STEEL ANGLE LINTEL. SEE TABLE BELOW.

NOTE: 90 x 90 x 5.0 OZ LINTEL (450 MPa) IS A SUITABLE ALTERNATIVE TO THE 75 x 75 x 6.0 EA & 75 x 75 x 8.0 EA LINTELS.

75 x 50 x 8 UA

50

100 x 75 x 8 UA 5 50 (175)
230 - 235

75

50 (150)

SQUARE BULKHEAD / EAVES LINTEL DETAIL


TILED ROOF
EFFECTIVE WIDTH 3600 mm 6600 mm LINTEL BEARING LINTEL BEARING

210 - 215

TILED OR METAL

METAL ROOF
EFFECTIVE WIDTH 3600 mm 6600 mm LINTEL BEARING LINTEL BEARING
100 120 150 165 180 200 250 280 300 320 350

50 (175)

50 (150)

150 x 90 x 8 UA

150 x 90 x 8 UA

OPENING

UP TO 1500 75 x 75 x 6 EA 100 75 x 75 x 8 EA 100 75 x 75 x 6 EA 100 75 x 75 x 6 EA UP TO 1800 75 x 75 x 8 EA 100 100 x 75 x 8 UA 120 75 x 75 x 6 EA 100 90 x 90 x 6 EA UP TO 2200 100 x 100 x 6 EA 110 125 x 75 x 10 UA 150 90 x 90 x 6 EA 110 100 x 100 x 8 EA UP TO 2400 125 x 75 x 6 UA 120 150 x 90 x 8 UA 165 100 x 75 x 8 UA 120 125 x 75 x 6 UA UP TO 2700 125 x 75 x 10 UA 135 150 x 90 x 10 UA 180 100 x 100 x 8 EA 135 125 x 75 x 8 UA UP TO 3000 150 x 90 x 8 UA 150 TYPE 'A' LINTEL 200 125 x 75 x 8 UA 150 150 x 90 x 8 UA UP TO 3300 150 x 90 x 10 UA 165 TYPE 'A' LINTEL 250 125 x 75 x 10 UA 165 150 x 100 x 10 UA UP TO 3600 TYPE 'A' LINTEL 180 TYPE 'A' LINTEL 280 150 x 90 x 8 UA 180 TYPE 'A' LINTEL UP TO 4000 TYPE 'A' LINTEL 200 TYPE 'B' LINTEL 300 150 x 100 x 10 UA 200 TYPE 'A' LINTEL UP TO 4400 TYPE 'A' LINTEL 220 TYPE 'B' LINTEL 350 TYPE 'A' LINTEL 220 TYPE 'A' LINTEL UP TO 5000 TYPE 'A' LINTEL 250 CONSULT ENGINEER TYPE 'A' LINTEL 250 TYPE 'A' LINTEL NOTE: 90 x 90 x 5.0 OZ LINTEL (450 MPa) IS A SUITABLE ALTERNATIVE TO THE 75 x 75 x 6.0 EA & 75 x 75 x 8.0 EA LINTELS.

FABRICATED LINTEL TYPE 'A'

FABRICATED LINTEL TYPE 'B'

NOTES:
1. THIS DETAIL IS TO PROVIDE LINTEL SIZES ONLY. 2. REFER TO BUILDER'S SPECIFICATIONS FOR ROOF & CEILING MEMBER SIZES AND SPACINGS. 3. REFER TO TRUSS MANUFACTURER'S SPECIFICATIONS FOR DETAILS OF ROOF TRUSS SIZES AND SPACINGS. 4. LINTELS ARE DESIGNED TO SUPPORT 3c OF BRICKWORK & UP TO 3.6m OR 6.6m OF TILED OR METAL ROOF & A CEILING. 5. DO NOT SUPPORT ROOF STRUTTING BEAMS, GIRDER TRUSSES OR OTHER SIMILAR POINT LOADS OVER THE LINTEL. LINTELS DESIGNED TO SUPPORT RAFTERS AND COMMON ROOF TRUSSES. 6. REINFORCEMENT TO BRICKWORK OVER LINTELS TO BE THE MINIMUM SPECIFIED IN THE FOOTING DETAIL, OR 2 L6 H.D. WIRES, 20 SIDE COVER & CONTINUE 500 PAST EDGE OF OPENING FOR SPANS > 4400mm WITH 3600mm EFFECTIVE WIDTH, AND FOR SPANS > 3000mm WITH 6000mm EFFECTIVE WIDTH. 7. REINFORCEMENT SHALL BE IN ACCORDANCE WITH THE FOLLOWING STANDARDS; L INDICATES PLAIN OR DEFORMED WIRE R500L OR D500L TO AS/NZS 4671. ALL STEELWORK TO BE TREATED IN ACCORDANCE WITH CLAUSE 3.4.4.4 "CORROSION PROTECTION" OF THE BUILDING CODE OF AUSTRALIA. 8. A BRICK COURSE, AS REFERRED TO IN THIS DOCUMENT IS STANDARD 86mm HIGH. 9. IT IS PERMISSIBLE TO ADJUST THE SPAN BY ROUNDING TO THE NEAREST BRICK LENGTH, SUBJECT TO IT BEING NO MORE THAN 20mm. 10. ALL WORK TO CONFORM TO THE PROVISIONS OF THE BUILDING CODE OF AUSTRALIA. 11. ALL STEELWORK TO CONFORM TO AS 4100. 12. ALL STEELWORK TO BE MINIMUM GRADE 300 (MPa) IN ACCORDANCE WITH AS/NZS 3679.1.

NOTES:
1. THIS DETAIL IS TO PROVIDE LINTEL SIZES ONLY. 2. REFER TO BUILDER'S SPECIFICATIONS FOR ROOF & CEILING MEMBER SIZES AND SPACINGS. 3. REFER TO TRUSS MANUFACTURER'S SPECIFICATIONS FOR DETAILS OF ROOF TRUSS SIZES AND SPACINGS. 4. LINTELS ARE DESIGNED TO SUPPORT 3c OF BRICKWORK & UP TO 3.6m OR 6.6m OF TILED OR METAL ROOF & A CEILING. 5. DO NOT SUPPORT ROOF STRUTTING BEAMS OR OTHER POINT LOADS OVER THE LINTEL. 6. MINIMUM REINFORCEMENT TO BRICKWORK OVER LINTELS TO BE AS PER THE SPECIFIED FOOTING DETAIL OR AS PER THE NOTE SHOWN ON THE DETAIL. 7. REINFORCEMENT SHALL BE IN ACCORDANCE WITH THE FOLLOWING STANDARDS; L INDICATES PLAIN OR DEFORMED WIRE R500L OR D500L TO AS/NZS 4671. ALL STEELWORK TO BE TREATED IN ACCORDANCE WITH CLAUSE 3.4.4.4 "CORROSION PROTECTION" OF THE BUILDING CODE OF AUSTRALIA. 8. A BRICK COURSE, AS REFERRED TO IN THIS DOCUMENT IS STANDARD 86mm HIGH. 9. IT IS PERMISSIBLE TO ADJUST THE SPAN BY ROUNDING TO THE NEAREST BRICK LENGTH, SUBJECT TO IT BEING NO MORE THAN 20mm. 10. WHERE LINTEL BEARS ON PERPENDICULAR BRICKWORK, BEARING IS TO BE ACROSS THE FULL WIDTH OF THE BRICK (90mm MIN). 11. ALL WORK TO CONFORM TO THE PROVISIONS OF THE BUILDING CODE OF AUSTRALIA. 12. ALL STEELWORK TO CONFORM TO AS 4100. 13. ALL STEELWORK TO BE MINIMUM GRADE 300 (MPa) IN ACCORDANCE WITH AS/NZS 3679.1.

1 REVISION PROJECT

GTU ENG.

ROOF BEAMS AMENDED & FREE STANDING PIER DETAILS ADDED DETAILS

C154312 JOB No.

08/03/13 DATE

CLIENT

LOT 2 of LOT 883 (#245) LAWRENCE ST BEDFORD G H F T BUILDING SERVICES for TURNER

APPROVED Zemla Pty Ltd (ABN 71 349 772 837) ATF the Young Purich and Higham Unit Trust trading as Structerre Consulting Engineers

B.E. M.I.E. (AUST) APPROVED FOR ISSUE

1 ERINDALE ROAD, BALCATTA W.A. 6021 TEL 9205 4500 FAX 9205 4501 EMAIL: residential@structerre.com.au
SCALE ON A3 DESIGNED

BH4

BH5

DATE

SHEET N

PROJECT N

1:20

Garry Turner

27/04/12

5 of 6

C139463

990 190 190 4L10 GALV ROD IN PIER, COG 150 INTO FOOTING. (OR USE 850 x 150 L10 STARTER). CAST INTO PERPEND OR CAVITY. CONTINUE TO WITHIN 100mm OF TOP OF PIER. 190 190

590 METER BOX TO BUILDER'S DETAIL. 4L10 GALV ROD IN PIER, COG 150 INTO FOOTING. (OR USE 850 x 150 L10 STARTER). CAST INTO PERPEND OR CAVITY. CONTINUE TO WITHIN 100mm OF TOP OF PIER. 100

590 100

990

PIER PLAN
METER BOX TO BUILDER'S DETAIL. 2000 MAX

PIER PLAN
2000 MAX 4L10 GALV ROD IN PIER, COG 150 INTO FOOTING. (OR USE 850 x 150 L10 STARTER). CAST INTO PERPEND OR CAVITY. CONTINUE TO WITHIN 100mm OF TOP OF PIER. REFER TO PIER PLAN FOR PIER DIMENSIONS.

REFER TO PIER PLAN FOR PIER DIMENSIONS. 4L10 GALV ROD IN PIER, COG 150 INTO FOOTING. (OR USE 850 x 150 L10 STARTER). CAST INTO PERPEND OR CAVITY. CONTINUE TO WITHIN 100mm OF TOP OF PIER.

300

300 MIN

300

300 MIN

NOTES:
1. REMOVE ALL TOPSOIL, VEGETATION AND DELETERIOUS FILL MATERIAL FROM THE BUILDING AREA. 2. SAND FILL TO BE CLEAN WELL DRAINED, WITH MAX FINES (PARTICLES UP TO 0.07mm) CONTENT OF 5%. SAND TO BE COMPACTED TO A MIN 6 BLOWS/300mm FOR 750mm OR DEPTH OF PAD. 3. A MIN OF 150mm OF SAND REQUIRED UNDER FOOTINGS FOR CLASS A & S SITES. MIN 450 SAND REQUIRED UNDER FOOTING FOR CLASS M SITES. 4. BRICK PIER DESIGNED TO SUPPORT MAX 10m2 FOR METAL ROOF AND 15m2 FOR TILE ROOF. 5. ROOF AND SURFACE WATER TO BE TAKEN AWAY FROM FOUNDATION AREA TO SITE DRAIN. (DRAIN TO LOCAL AUTHORITY STORM WATER SYSTEM WHERE APPROPRIATE). 6. EXCAVATIONS FOR PLUMBING NOT TO UNDERMINE FOOTINGS. IF UNDERMINING IS LIKELY TO OCCUR, CONTACT THE ENGINEER. 7. CONCRETE TO CONFORM WITH AS 3600. 8. BLENDED CEMENT TO CONFORM WITH AS 3972. 9. ALL CONCRETE TO BE N20/20/80. 10. CURE CONCRETE FOR 7 DAYS MINIMUM. 11. THE DETAIL ONLY PROVIDES LIMITED LATERAL STABILITY. IF THE OVERALL ROOF STRUCTURE DOES NOT PROVIDE LATERAL STABILITY TO THE STRUCTURE, CONTACT THE ENGINEER FOR ADVICE. 12. ALL MASONRY SHALL COMPLY WITH AS 3700. ENSURE ALL PERPENDS ARE FULLY MORTARED. SPECIFICALLY, PERPENDS CONTAINING REINFORCING RODS. 13. REINFORCEMENT SHALL BE IN ACCORDANCE WITH THE FOLLOWING STANDARDS; R INDICATES PLAIN REINFORCING BAR R250N TO AS/NZS 4671. ALL STEELWORK TO BE TREATED IN ACCORDANCE WITH CLAUSE 3.4.4.4 "CORROSION PROTECTION" OF THE BUILDING CODE OF AUSTRALIA.

1090 (x 690)

FREE-STANDING GATE PIER

NOTES:
1. REMOVE ALL TOPSOIL, VEGETATION AND DELETERIOUS FILL MATERIAL FROM THE BUILDING AREA. 2. SAND FILL TO BE CLEAN WELL DRAINED, WITH MAX FINES (PARTICLES UP TO 0.07mm) CONTENT OF 5%. SAND TO BE COMPACTED TO A MIN 6 BLOWS/300mm FOR 750mm OR DEPTH OF PAD. 3. A MIN OF 150mm OF SAND REQUIRED UNDER FOOTINGS FOR CLASS A & S SITES. MIN 450 SAND REQUIRED UNDER FOOTING FOR CLASS M SITES. 4. BRICK PIER DESIGNED TO SUPPORT MAX 10m2 FOR METAL ROOF AND 15m2 FOR TILE ROOF. 5. ROOF AND SURFACE WATER TO BE TAKEN AWAY FROM FOUNDATION AREA TO SITE DRAIN. (DRAIN TO LOCAL AUTHORITY STORM WATER SYSTEM WHERE APPROPRIATE). 6. EXCAVATIONS FOR PLUMBING NOT TO UNDERMINE FOOTINGS. IF UNDERMINING IS LIKELY TO OCCUR, CONTACT THE ENGINEER. 7. CONCRETE TO CONFORM WITH AS 3600. 8. BLENDED CEMENT TO CONFORM WITH AS 3972. 9. ALL CONCRETE TO BE N20/20/80. 10. CURE CONCRETE FOR 7 DAYS MINIMUM. 11. THE DETAIL ONLY PROVIDES LIMITED LATERAL STABILITY. IF THE OVERALL ROOF STRUCTURE DOES NOT PROVIDE LATERAL STABILITY TO THE STRUCTURE, CONTACT THE ENGINEER FOR ADVICE. 12. ALL MASONRY SHALL COMPLY WITH AS 3700. ENSURE ALL PERPENDS ARE FULLY MORTARED. SPECIFICALLY, PERPENDS CONTAINING REINFORCING RODS. 13. REINFORCEMENT SHALL BE IN ACCORDANCE WITH THE FOLLOWING STANDARDS; R INDICATES PLAIN REINFORCING BAR R250N TO AS/NZS 4671. ALL STEELWORK TO BE TREATED IN ACCORDANCE WITH CLAUSE 3.4.4.4 "CORROSION PROTECTION" OF THE BUILDING CODE OF AUSTRALIA.

1090 (x 690)

FREE-STANDING GATE PIER WITH METER BOX

1 REVISION PROJECT

GTU ENG.

ROOF BEAMS AMENDED & FREE STANDING PIER DETAILS ADDED DETAILS

C154312 JOB No.

08/03/13 DATE

CLIENT

LOT 2 of LOT 883 (#245) LAWRENCE ST BEDFORD G H F T BUILDING SERVICES for TURNER

APPROVED Zemla Pty Ltd (ABN 71 349 772 837) ATF the Young Purich and Higham Unit Trust trading as Structerre Consulting Engineers

B.E. M.I.E. (AUST) APPROVED FOR ISSUE

Y3
SPECIAL A

Y3
SPECIAL B

1 ERINDALE ROAD, BALCATTA W.A. 6021 TEL 9205 4500 FAX 9205 4501 EMAIL: residential@structerre.com.au
SCALE ON A3 DESIGNED

DATE

SHEET N

PROJECT N

1:20

Garry Turner

27/04/12

6 of 6