TransformerCoreGrounds

ByPhilipJHopkinson,PE

1. TheissueisgassingandPartialDischarge 2. DielectricBreakdowninwindingsnotthe problem 3. GassingandPDworstat34.5kV 4. Gassingnotanissueat5kV 5. Gassingat15kVanannoyanceonly 6. GassingcomingfromCore 7. Solutionviagroundingorshielding

10/28/2012

TransformerCoreGrounds
ByPhilipJHopkinson,PE

GroundLead

ViOuterCore L

ViInnerCore

ViInnerCore

ViOuterCore

C5

C2

C1C3 C4C1

C1C4

C4C1

C1C4

C3C1

C2 C3C5

C5 LV HV L

C5

C5

C5

GroundedClamp

10/28/2012

TransformerCoreGrounds
ByPhilipJHopkinson,PE

HV
C2

ViOuterCoreLoopInsideSurface 804 Volts LVStartisGrounded 0 Volts


C1

LGVolts 19919
C3

CoreGround 0 Volts

CaseI,CoreGroundConnectedtoFrame VoltagedropinOuterCorestacks= 804 Volts

1.Outsidecoregroundsat34.5kVresultinhighcorevolts 2.Insidecoregroundseliminatestaticchargesanddropcorevolts to volt/turnlevels


10/28/2012 3

TransformerCoreGrounds
ByPhilipJHopkinson,PE

0.030"thickstatic shield 0.020"thickpaper OutsideCoreLeg

CoreGround

GroundedElectrostaticShield

1.Outsidecoregroundsat34.5kVresultinhighcorevolts 2.Insidecoregroundseliminatestaticchargesanddropcorevolts to volt/turnlevels 3.Coreshieldsequallyeffective

10/28/2012

TransformerCoreGrounds
ByPhilipJHopkinson,PE

WithOutsideCoreGroundandnocoreshield: 1.Hydrogenat15kVtypically100300ppm 2.Hydrogenat34.5kVtypically3,00010,000 ppm 3.Hydrogenaccompaniedbysmallamountsof a. Ethane b. Ethylene c. Methane


10/28/2012 5

TransformerCoreGrounds
ByPhilipJHopkinson,PE

WithOutsideCoreGroundandnocoreshield: 1. Partialdischargebestdetector 2. PDshouldbeconductedperClassIItransformers a. Startat50%ofratedvolts b. Goto100%ofratedvoltsandrecord c. Goto110%ofratedvoltsandrecord d. Goto150%ofratedvoltsandholdfor1hour e. Dropbackto110%ofratedvoltsandholdforat least10minutesandrecord. f. Dropbackto100%ofratedvoltsandrecord. g. Dropbackuntilpdextinguishesbelow100pc 3.Transformerfailsifextinguishlessthan110%of ratedvolts
10/28/2012 6