Heat Loss in the Pipe WONO Temperature of surrounding water (C) Temperature of air after blower (C) Lower

air temperature (C) Length of pipe (m) Mass airflow = 1.699 x air density (kg/m3) x SCFM Specific Heat of Air (0.25 kcal/kg C) Heat flow rate through a pipe wall per meter of pipe length (kcal/m . H . C) ID of pipe (m) OD of pipe (m) Heat transfer coefficient between outside surface of pipe and surrounding medium (kcal/m2 . H . C) lambda Thermal conductivity of pipe material carbon steel = 45 kcal/m *h* C stainless steel = 22 kcal/m*h*C PVC = 0.14 kcal/m*h*C Conversion Units di Pipe diameter ID 8.477 0.215316 m do Pipe diameter OD 8.625 0.219075 m To Water temp 25 C T1 Inlet temp 108 C T2 Outlet temp 60 C Pressure inside pipe 686.5 mBarG Standard air flow 1230 SCFM Actual air flow inside pipe 953.3464 ACFM V Air Velocity 12.35183 m/s General Equation -Lxk T2 - To = T1-To e mxc To T1 T2 L m c k di do alpha-s 60-25 108-25 = e - L * _ 24.59971 2510.859 * .25 24.59971 *-L/ e 24.59971 *-L/ 22.03388 m 627.7147

0.421687 =

-0.86349 = L = Calculation of k k= 1/

627.7147 72.28947 ft + 1/3.14*do*alpha s LN do/di + 0.000284 0.017308

1/3.14*di*alpha a 1/2*3.14*lambda * = 0.040242 0.007238 * k= 24.5997095 kcal/m * h * C Calculation of alpha-a alpha a = w^.75/di^.25 * 3.8 alpha a = V^.75/ 0.215316 ^.25 36.7547 kcal/m2 . H . C Calculation of alpha-s alpha s = delta 2900 t^.233/do^.3 w1^.85 (1+0.14 tm)

+ +

*3.8

5127.624 kcal/m2. H. C Calculation of air mass m=1.699x1.2015xSCFM =

2510.859 kg/h