Escolar Documentos
Profissional Documentos
Cultura Documentos
Short-circuit power
Introduction
Example 1: 25 kA at an operating voltage of 11 kV
R E
Zcc L
Icc
# The short-circuit power depends directly on the network configuration and the impedance of its components: lines, cables, transformers, motors... through which the short-circuit current passes. # It is the maximum power that the network can provide to an installation during a fault, expressed in MVA or in kA rms for a given operating voltage.
U Isc : : operating voltage (kV) short-circuit current (kA rms.) Ref: following pages
A U B Zs
S sc =
U I sc
The short-circuit power can be assimilated to an apparent power. # The customer generally imposes the value of short-circuit power on us because we rarely have the information required to calculate it. Determination of the short-circuit power requires analysis of the power flows feeding the short-circuit in the worst possible case.
T2
Icc2 Icc3
Example 2: # Feedback via LV Isc5 is only possible if the transformer (T4) is powered by another source. # Three sources are flowing in the switchboard (T1-A-T2) 5 circuit breaker D1 (s/c at A) Isc1 + Isc2 + Isc3 + Isc4 + Isc5 5 circuit breaker D2 (c/c at B) Isc1 + Isc2 + Isc3 + Isc4 + Isc5 5 circuit breaker D3 (c/c at C) Isc1 + Isc2 + Isc3 + Isc4 + Isc5
T3
Icc5
A D1
B D2 10 kV
C D3
D6 MT
D4
D5
D7
Icc4
BT T4 BT MT
Schneider Electric
Gamme
AMTED300014EN_001_01