GOPALA KRISHNA
ADE/400KV/APTRANSCO
DOUBLE MAIN BUS & TRANSFER BUS SYSTEM
1. In This Two Main Buses Are Available.
2. They Are Called Bus-1 & Bus-2.
3. One More Bus Is Available. This is Not Main Bus.
4. We Call As Transfer Bus Or Auxiliary Bus Or Temporary Bus.
5. This is Useful only, When any Of the Circuit Breaker (only One) Is Out Of Service Or
Maintenance Or Trouble.
6. If One Of the Circuit Breaker in Trouble, This Is More Useful.
7. If Second Circuit Breaker is also in Trouble, then This Is Not Useful.
8. Most Of The Time, The Auxiliary Bus Is Kept Open.
9. Based On My Experience, Now a Days, this May Be Least Useful.
10. Note: Checking of Every Month, One Day, One Feeder is to be Kept On Transfer Bus and to
Ascertain Healthiness Of Transfer Bus. This is to be Followed Regularly, Then the Transfer
Bus is Available When Emergency Occurs.
11. But, this System is Not Useful For CT Troubles or any other Equipment Troubles.
12. The Tentative Substation Layout Is Shown In Next Slide.
13. This System is adopted When ABCBs, BOCBs, MOCBs Are Available.
14. The ABCBs, BOCBs, MOCBs Requires Regular Maintenance.
15. The reason behind for Adoption of Transfer Bus System is, During The Maintenance of
Circuit Breaker, the Consumer Should Not Suffer.
16. Now A Days SF6 CBs With Trouble Free Mechanisms are Coming and all Substations are
having Redundant or Alternative Source of supply is Available, Still Following This Concept is
Some What Unhappy.
17. The Location of CT is after Line Isolator and towards Line. This is also one more
Disadvantage.
18. For Maintenance Of CT, The Line is to be Taken LC and Remove the Jumpers And to Test.
19. This Type Of One More Unhappy System Is Available i.e. Double Bus With Bypass Isolator.
DOUBLE MAIN BUS & TRANSFER BUS SYSTEM
T/F-1 T/F-2
BUS-1
BUS COUPLER
BUS-2
TRANSFER BUS
COUPLER
BAY3 BAY4 BAY5
BAY1 BAY2 TRANSFER BUS BAY6 BAY7 BAY8
BAY – 1 FEEDER – 1 2 – 1 – 52 CB
BAY – 2 FEEDER – 2 2 – 2 – 52 CB
BAY – 3 TRANSFORMER – 1 2 – 3 – 52 CB
BAY – 4 BUS COUPLER 2 – 4 – 52 CB
BAY – 5 TRANSFORMER – 2 2 – 5 – 52 CB
BAY – 6 TRANSFER BUS 2 – 6 – 52 CB
BAY – 7 FEEDER – 3 2 – 7 – 52 CB
BAY – 8 FEEDER – 4 2 – 8 – 52 CB
DOUBLE MAIN BUS & TRANSFER BUS SYSTEM
STANDARD PRACTICE
1. FOR BUS ISOLATON: EACH BUS HAVING BUS ISOLATOR FOR
EACH BAY.
2. FOR CB ISOLATION: CIRCUIT BREAKER HAVING BOTH SIDES
ISOLATORS.
3. FOR LINE/ICT ISOLATION: LINE / ICT HAVING LINE ISOLATOR.
4. FOR BUS MAINTANENCE: EACH BUS HAVING BUS EARTH
SWITCH.
5. FOR CB MAINTANENCE: EACH ISOLATOR HAVING EARTH
SWITCH TOWARDS CB SIDE.
6. FOR LINE / ICT MAINTANENCE: EACH LINE / ICT HAVING LINE
EARTH SWITCH.
DOUBLE MAIN BUS & TRANSFER BUS SYSTEM
1. In this each Feeder / Transformer / Reactor is having four Isolators.
2. One Isolator for Bus-1, one Isolator for Bus-2, one isolator for Transfer Bus and another
Isolator for Feeder / Transformer / Reactor.
3. In case of Bus Coupler only Bus-1 & Bus-2 Isolators will be available.
4. In case of Transfer Bus Coupler, Bus-1, Bus-2 & Transfer Bus isolators are available.
5. 89 represents Isolator. Bus-1 Isolator represents-A, Bus-2 Isolator represents-B, Transfer
Bus Isolator represents-C, Circuit Isolator represents-L/T/R based on circuit.
ISOLATORS DESIGNATION
BAY NO CIRCUIT
BUS-1 BUS-2 TR BUS CIRCUIT
BAY – 1 FEEDER – 1 2-1-89A 2-1-89B 2-1-89C 2-1-89L
BAY – 2 FEEDER – 2 2-2-89A 2-2-89B 2-2-89C 2-2-89L
BAY – 3 TRANSFORMER – 1 2-3-89A 2-3-89B 2-3-89C 2-3-89T
BAY – 4 BUS COUPLER 2-4-89A 2-4-89B - -
BAY – 5 TRANSFORMER – 2 2-5-89A 2-5-89B 2-5-89C 2-5-89T
BAY – 6 TRANSFER BUS 2-6-89A 2-6-89B 2-6-89C -
BAY – 7 FEEDER – 3 2-7-89A 2-7-89B 2-7-89C 2-7-89L
BAY – 8 FEEDER – 4 2-8-89A 2-8-89B 2-8-89C 2-8-89L
DOUBLE MAIN BUS & TRANSFER BUS SYSTEM
1. IN THIS EACH FEEDER / TRANSFORMER / REACTOR IS HAVING CT & LA/SA TOWARDS
CIRCUIT.
2. NORMAL APTRANSCO PRACTICE BUS COUPLER HAVING TWO SIDES CT. BUT MOST OF
THE UTILITIES HAVING ONE SIDE CT. BUS COUPLER NOT HAVING LA, CVT & WT/LT.
3. TRANSFER BUS COUPLER HAVING ONE CT. TRANSFER BUS COUPLER NOT HAVING LA,
CVT & WT/LT.
4. IN THIS EACH FEEDER IS HAVING CVT & WT/LT TOWARDS CIRCUIT.
ISOLATORS DESIGNATION
BAY NO CIRCUIT
CT LA/SA CVT WT/LT
BAY – 1 FEEDER – 1 2 – 1CT 2 – 1SA 2 - 1CVT 2 – 1LT
BAY – 2 FEEDER – 2 2 – 2CT 2 – 2SA 2 - 2CVT 2 – 2LT
BAY – 3 TRANSFORMER – 1 2 – 3CT 2 – 3SA - -
2–4
BAY – 4 BUS COUPLER 2 – 4SA - -
A/B CT
BAY – 5 TRANSFORMER – 2 2 – 5CT 2 – 5SA - -
BAY – 6 TRANSFER BUS 2 – 6CT 2 – 6SA - -
BAY – 7 FEEDER – 3 2 – 7CT 2 – 7SA 2 - 8CVT 2 – 8LT
BAY – 8 FEEDER – 4 2 – 8CT 2 – 8SA 2 - 8CVT 2 – 8LT
DOUBLE MAIN BUS & TRANSFER BUS SYSTEM
1. NORMALLY EACH FEEDER / TRANSFORMER / REACTOR IS TO BE CONNECTED TO EITHER
BUS-1 OR BUS-2, NOT BOTH.
2. THE CONCEPT BEHIND IS WHEN EITHER OF THE BUS BAR PROTECTION OPERATES
ATLEAST 50% CIRCUITS WILL BE IN SERVICE.
3. FOR MAINTANENCE POINT OF VIEW IT IS HAPPY THAT ALL CIRCUITS KEPT ON ONE BUS
AND ANOTHER BUS CAN BE TAKEN IN TO MAINTANENCE.
4. NORMALLY BUS-1 OR BUS-2 SELECTION IS TO BE DONE BEFORE CHARGING CIRCUIT.
5. APTRANSCO STANDARD PRACTICE, IN CASE OF DOUBLE CIRCUIT, ONE CIRCUIT ON BUS-
1 AND CIRCUIT -2 ON BUS-2.
6. FOR EXAMPLE VEMAGIRI-1 & 2 FEEDERS ARE AVAILABLE, VEMAGIRI -1CONNECTED ON
BUS-1 AND VEMAGIRI-2 CONNECTED ON BUS-2.
7. IN CASE OF TRANSFORMER ICT-1 CONNECTED ON BUS-1 AND ICT-2 CONNECTED ON
BUS-2.
8. THE BUS COUPLER BREAKER IS ALWAYS IN SERVICE. THE BUS-1 & 2 ISOLATORS BOTH
ARE CLOSSED POSITION.
9. DURING SERVICE, CHANGE OVER BUS IS NOT A PRACTICE, HOWEVER THIS IS POSSIBLE
WHEN BUS COUPLER IS CLOSSED CONDITION ONLY. PLEASE REFER THE INTERLOCK
CIRCUIT OF ANY FEEDER.
10. DURING SERVICE THE CHANGING OF BUS PROCEDURE IS AS FOLLOWS: IF THE CIRCUIT
IS CONNECTED ON BUS-1, CLOSE BUS-2 ISO AND OPEN BUS-1 ISO. SIMILARLY FOR BUS-2
TO BUS-1 CHANGE OVER. DONOT PRACTICE REGULARLY. THIS IS PURELY FOR
EMERGENCY AND WHEN BOTH ISOLATORS & CB OF BUS COUPLER IS CLOSSED
CONDITION ONLY.
11. THE ISOLATOR SELECTION IS GOING TO BUSBAR PROTECTION. i.e. IF BUS-1 ISO CLOSES
CT IS CONNECTED TO BUSBAR-1 PROTECTION OR BUS-2 ISO CLOSES CT IS CONNECTED
TO BUSBAR-2 PROTECTION.
12. DURING BUS BAR PROTECTION OPERATES, THE BAYS CONNECTED TO THAT BUS AND
BUSCOUPLER CBs ARE OPENED. THIS EXPLAINED IN BUSBAR PROTECTION IN NEXT
SLIDES.
DOUBLE MAIN BUS & TRANSFER BUS SYSTEM
1. NORMALLY TRANSFER BUS COUPLER CB & ISOs ARE ALWAYS IN OPEN CONDITION.
2. WHEN ANY OF THE CB TROUBLE COMES THAT WILL BE TRANSFERED TO AUXILIARY BUS
AND THAT CIRCUIT IS FED FROM AUX BUS.
3. THE OPERATION OF TRANSFER BUS WILL BE EXPLAINED IN NEXT SLIDES.
4. FROM THE SAMPLE LAYOUT WE ARE PRESUMED THAT FEEDER-1, ICT-1 & FEEDER-3 ARE
CONNECTED ON BUS-1 AND FEEDER-2, ICT-2 & FEEDER-4 ARE CONNECTED ON BUS-2.
5. BUS COUPLER CB & ISOLATORS ARE IN SERVICE.
6. DURING THIS CHANGE OVER TO TRANSFER BUS, THE TRIPPING CIRCUITS ARE
TRANSFERRED TO TRANSFER BUS COUPLER CB.
7. DURING THE CIRCUIT IS CONNECTED ON TRANSFER BUS COUPLER, IF FAULT OCCURS
ON CIRCUIT, THE PROTECTIVE RELAYS WILL GIVE TRIP SIGNAL TO CONCERNED CB AND
TRANSFER BUS CB.
8. THIS CAN BE AVOIDED BY USING SOME MORE LOGIC.
9. THE TBC CT ONE CORE IS CONNECTED TO SELECTION OF BUSBAR PROTECTION EITHER
BUS-1 & BUS-2 BASED ON ISOLATOR SELECTION.
10. ANOTHER CORE IS CONNECTED TO BUS-3 BUSBAR PROTECTION.
11. THIS IS EXPLAINED IN BUS BAR PROTECTION PRESENTATION.
12. IN TRANSFER BUS PANEL, AUTO RECLOSURE RELAY IS AVAILABLE. THIS IS USEFUL
WHEN ANY FEEDER IS CONNECTED TO TBC, THEN IT IS USEFUL.
13. IN TRANSFER BUS PANEL, TBC LBB RELAY IS ALSO AVAILABLE.
14. DURING THE OPERATION OF TRANSFERING THE CIRCUIT TO THE TBC, THE COMPLETE
SEQUENCE IS TO BE FOLLOWED. ANY THING WRONG, THEN ALARM WILL COME. THE
OPERATION COMPLETES PERFECTLY THE ALARM WILL DISAPPEAR.
15. NORMAL CONVENTIONAL SYSTEM WE ARE PROVIDING TTS SWITCH. THIS IS TRIP
TRANSFER SWITCH. IN NORMAL MODE TRIPING IS DONE FOR PARTICULAR CIRCUIT
BREAKER, IF IT IS TRANSFER MODE THE TRIP CIRCUIT IS PARALLED AND EXTENDED TO
TBC CIRCUIT BREAKER BAY.
16. IN AUTOMATION SYSTEM, THE LATCH RELAY MAY PROVIDE, FOR THIS OPERATION AND
THAT CAN BE OPERATED FROM BCU/ REMOTE.
DOUBLE MAIN BUS & TRANSFER BUS SYSTEM
CHANGING OVER OPERATION OF FEEDER-1 TO TBC CIRCUIT & TO NORMAL
NORMALLY FEEDER-1 IS CONNECTED BUS-1 & Feeder Protections are to be kept on Line CVT
THE SEQUENCE OF OPERATION STARTS AS FOLLOWS:
1. PUT ALL PROTECTIONS ON LINE CVT.
2. CLOSE TBC BAY BUS-1 ISOLATOR.
3. CLOSE TBC BAY BUS-3 ISOLATOR.
4. CLOSE FEEDER-1, BAY-3 ISOLATOR.
5. SO THE TBC CB BOTH SIDES HAVING VOLTAGE.
6. PUT TTS IN TRANSFER MODE OF FEEDER-1 PANEL.
7. CLOSE THE TBC CB.
8. THEN, THE FEEDER-1 IS PARALLED WITH TBC CB AND FEEDING TWO PARALLEL PATHS.
9. PATH1:FEEDER-1 CIRCUIT : FEEDER-1 BUS-1 ISO, FEEDER-1 CB, FEEDER-1 LINE ISO TO
FEEDER-1.
10. PATH2:TBC CIRCUIT : TBC BUS-1 ISO, TBC CB, TBC BUS-3 ISO AND FEEDER-1 BUS-3 ISO
TO FEEDER-1.
11. THEN OPEN FEEDER-1 CB.
12. NOW THE FEEDER-1 IS FEEDING FROM TBC CB.
13. OPEN THE FEEDER ISOLATORS i.e. BUS-1 ISO, LINE ISO. NOT BUS-3 ISO.
14. AFTER MAINTANENCE WORK IS OVER, THE REVERSE PROCEDURE MAY BE FOLLOWED.
TAKING TO NORMAL SYSTEM.
1. CLOSE FEEDER-1 BUS-1 ISOLATOR.
2. CLOSE FEEDER-1 LINE ISOLATOR.
3. PUT TTS IN NORMAL MODE.
4. CLOSE FEEDER-1 CIRCUIT BREAKER.
5. OPEN TBC CB.
6. OPEN TBC BAY BUS-1 ISOLATOR.
7. OPEN TBC BAY BUS-3 ISOLATOR.
8. OPEN FEEDER-1 BUS-3 ISOLATOR.
DOUBLE MAIN BUS & TRANSFER BUS SYSTEM
CHANGING OVER OPERATION OF ICT-2 TO TBC CIRCUIT & TO NORMAL
NORMALLY ICT-2 IS CONNECTED BUS-2.
THE SEQUENCE OF OPERATION STARTS AS FOLLOWS:
1. CLOSE TBC BAY BUS-2 ISOLATOR.
2. CLOSE TBC BAY BUS-3 ISOLATOR.
3. CLOSE ICT-2 BAY-3 ISOLATOR.
4. SO THE TBC CB BOTH SIDES HAVING VOLTAGE.
5. PUT TTS IN TRANSFER MODE IN ICT-2 PANEL.
6. CLOSE THE TBC CB.
7. THEN, THE ICT-2 IS PARALLED WITH TBC AND FEEDING TWO PARALLEL PATHS.
8. PATH1:ICT-2 CIRCUIT : ICT-2 BUS-2 ISO, ICT-2 CB, ICT-2 TRANSFORMER ISO TO ICT-2.
9. PATH2:TBC CIRCUIT : TBC BUS-2 ISO, TBC CB, TBC BUS-3 ISO AND ICT-2 BUS-3 ISO TO
ICT-2.
10. THEN OPEN ICT-2 CB.
11. NOW THE ICT-2 IS FEEDING FROM TBC CB.
12. OPEN THE ICT-2 ISOLATORS i.e. BUS-2 ISO, TRANSFORMER ISO. NOT BUS-3 ISO.
13. AFTER MAINTANENCE WORK IS OVER, THE REVERSE PROCEDURE MAY BE FOLLOWED.
TAKING TO NORMAL SYSTEM.
1. CLOSE ICT-2 BUS-2 ISOLATOR.
2. CLOSE ICT-2 TRANSFORMER ISOLATOR.
3. PUT TTS IN NORMAL MODE.
4. CLOSE ICT-2 CIRCUIT BREAKER.
5. OPEN TBC CB.
6. OPEN TBC BAY BUS-2 ISOLATOR.
7. OPEN TBC BAY BUS-3 ISOLATOR.
8. OPEN ICT-2 BUS-3 ISOLATOR.
DOUBLE MAIN BUS & TRANSFER BUS SYSTEM
THIS CONTAINS
1. INDIVIDUAL BAYS LIKE FEEDER/LINE, TRANSFORMER, REACTOR.
2. BUS COUPLER BAY.
3. TRANSFER BUS COUPLER BAY.
THIS CONTAINS
1. ENTIRE SUBSTATION CONTAINS 1. EACH FEEDER/LINE BAY CONTAINS
A. BUSBAR PROTECTION PANEL A. LINE CONTROL PANEL
B. COMMON ANNUNCIATION/CONTROL B. CB RELAY PANEL
PANEL C. LINE PROTECTION PANEL
2. BUS COUPLER BAY CONTAINS D. LINE REACTOR PROTECTION PANEL
A. BUS COUPLER CONTROL PANEL 2. EACH TRANSFORMER/ICT BAY
B. BUS COUPLER RELAY & PROTECTION CONTAINS
PANEL A. ICT HV CONTROL PANEL
3. BUS SECTIONALISER BAY CONTAINS B. HV CB RELAY PANEL
A. BUS COUPLER CONTROL PANEL C. ICT PROTECTION PANEL.
B. BUS COUPLER RELAY & PROTECTION D. LV CB RELAY PANEL.
PANEL E. ICT LV CONTROL PANEL
4. TRANSFER BUS COUPLER BAY 3. EACH BUS REACTOR BAY CONTAINS
CONTAINS
A. REACTOR CONTROL PANEL
A. TRANSFER BUS COUPLER CONTROL
PANEL B. CB RELAY PANEL
B. TRANSFER BUS COUPLER RELAY & C. REACTOR PROTECTION PANEL.
PROTECTION PANEL
BUSBAR PROTECTION PANEL
DISTRIBUTED ARCHITECTURE CENTRALISED ARCHITECTURE
S.NO DESCRIPTION QTY
2 RBB 2 RBB
3 Zone Numerical Bus Bar Protection
Relay for Double Bus and Transfer Bus
1 1 No
System of Either Distributed Architecture
or Centralised Architecture with test plug.
BCU1 BCU2 Incase of Distributed Architecture Bay/ BCU1 BCU2
2 Peripheral units are at respective CB set
Relay Panels.
Numerical Breaker Failure Relay.
BCU3 (BFR/CBF/LBB/ Stuck Breaker BCU3
3 --
Protection)
Inbuilt function of Bus Bar Protection
BUSBAR Selector Switch Bus IN / OUT for each BUSBAR-1
CENTRAL UNIT 4 3 No RELAY
Bus
DC
AE CMR
Bus
AE CMR
89BB1
89BB2
AE CMR
Bus
AE CMR
89BB1
89BB2
Bar -1
respective CB Relay Panels. Aux DC
relays -2
Auxiliary Relays to Close Bus Isolators of
8 3 No
Particular Bus from BCU.
9 Bus Earth Switches Contact Multiplier 2 No
Transfer Bus Coupler Isolators Contact
10 2 No
multiplication
BUS COUPLER PANEL
CONVENTIONAL PANEL AUTOMATION PANEL
2RBC S.NO DESCRIPTION QTY 2RBC
TRIP COIL Flag relays two element type for TRIP COIL
CB 1&2 3 Set CB 1&2
TROUBLES HEALTHY
Circuit Breaker Troubles TROUBLES HEALTHY
& ALARMS LEDS & ALARMS LEDS
4 Trip Coil Supervision Relays. 6 No
DC-1
DC-1
DC-2
DC-2
TRIP COIL Flag relays two element type for TRIP COIL
CB 1&2 3 Set CB 1&2
TROUBLES HEALTHY
Circuit Breaker Troubles TROUBLES HEALTHY
& ALARMS LEDS & ALARMS LEDS
4 Trip Coil Supervision Relays. 6 No
DC-1
DC-1
DC-2
DC-2
DC-1
DC-1
DC-2
DC-2
86 R1,Y1,B1
5 Trip Coil Supervision Relays. 6 No 86 R1,Y1,B1
GR-B R2,Y2,B2 DC-1 & DC-2 Supply Monitoring GR-B R2,Y2,B2
CB 6 2 No Closing
96 Multiply /Supervision relays for Gr-A & Gr-B 96 Aux
50Z Relay 50Z relays
High Speed Single Phase Trip Relays CB PB
7 12 No
with self resetting & Flag indication.
3-Ph High Speed Master Trip Relays
with Electrical Reset through BCU for
8 3 No
86Gr-A, 86Gr-B & 96BB/50Z including
Supervision.
Auxiliary Relays to Close Circuit Breaker
9 Set
& Isolators of Particular Bay from BCU.
Emergency Circuit Breaker TNC Switch
10 1 No
or Push Button for CB Open & Close.
LINE CB RELAY PANEL
CONVENTIONAL PANEL AUTOMATION PANEL
2RLA S.NO DESCRIPTION QTY 2RLA
DC-1
186
FOR 21L1 DC-1 & DC-2 Supply Monitoring /Supervision
6 2 No 86 R1,Y1,B1
1-PH TRIP relays for Gr-A & Gr-B GR-A R2,Y2,B2
86 GR -B RELAYS -6
3-Ph High Speed Master Trip Relays with 286
DC-2
FOR 21L2
7 Electrical Reset through BCU for 86Gr-A, 3 No 86 R1,Y1,B1
D/T CH-1 D/T CH-2 86Gr-B & 96BB/50Z including Supervision. GR-B R2,Y2,B2
RECEIVE RECEIVE
RELAYS RELAYS CB, ISO
High Speed Single Phase Trip Relays with 96 CLSOING
8 self resetting & Flag indication.
12 No
50Z AUX RLYS CB PB
UNDER BREAKER
VOLTAGE MULTIPLICA High Speed Auxiliary trip relays with flags D/T CH-1 D/T CH-2
RELAY TION RELAY RECEIVE RECEIVE
9 and self resetting for Direct Trip-1 & 2 2 No RELAYS RELAYS
Receive.
Auxiliary Relays to Close Circuit Breaker &
10 Isolators of Particular Bay from BCU.
SET
DC-1
DC-1 & DC-2 Supply Monitoring
5 2 No 86
/Supervision relays for Gr-A & Gr-B
GR-A
96 3-Ph High Speed Master Trip Relays
DC-2
50Z
with Electrical Reset through BCU for 86
6 3 No GR-B
INTER INTER 86Gr-A, 86Gr-B & 96BB/50Z including
TRIP TRIP Supervision. CB, ISO
RELAYS RELAYS 96 CLSOING
BREAKER High Speed Inter trip relays and self 50Z AUX RLYS CB PB
7 4 No
MULTIPLICA resetting INTER TRIP
TION RELAY RELAYS
Auxiliary Relays to Close Circuit Breaker
8 SET
& Isolators of Particular Bay from BCU.
Emergency Circuit Breaker TNC Switch
9 1 No
or Push Button for CB Open & Close.
Under Voltage Relay for Line Isolator
10 Set
Earth Switch Interlock circuit.
3-Ph Energy Meter for Both Export &
Import with Test Terminal Block with
11 1 No
RS232/485 with Modbus/ DNP 3.0
Protocol
REACTOR CB RELAY PANEL
CONVENTIONAL
CONVENTIONAL PANEL
PANEL AUTOMATION PANEL
S.NO DESCRIPTION QTY 2RBRA
2RBRA
Bay Control Units for Bus Reactor Main
CB Bay Equipment Control, Operation,
1 1 No
Monitoring, Synchronisation & Interlocks
with Mimic.
50 Z BAY1 BCU
(LBB / BFR) Numerical Breaker Failure Relay.
2 (BFR/CBF/LBB/ Stuck Breaker 1 No
CB TROUBLE ALARAM Protection) (Part of Bus Bar Protection)
AND TRIP RELAYS
Flag relays two element type for Circuit LBB/ BU
50Z
3 Breaker Troubles for Alarms/ Event Set
TSR DC TSR
TC-1 I & II TC-1I Logger / Disturbance Recorder. TRIP COIL
CB 1&2
TROUBLES HEALTHY
4 Trip Coil Supervision Relays. 6 No & ALARMS LEDS
86 GR -A 86 GR -B
DC-1
DC-1 & DC-2 Supply Monitoring
5 2 No 86
/Supervision relays for Gr-A & Gr-B GR-A
96
3-Ph High Speed Master Trip Relays
DC-2
50Z
with Electrical Reset through BCU for 86
6 3 No GR-B
86Gr-A, 86Gr-B & 96BB/50Z including
Supervision. CB, ISO
96 CLSOING
BREAKER Auxiliary Relays to Close Circuit Breaker 50Z AUX RLYS CB PB
MULTIPLICA 7 SET
& Isolators of Particular Bay from BCU.
TION RELAY
Emergency Circuit Breaker TNC Switch
8 1 No
or Push Button for CB Open & Close.
Under Voltage Relay for Line Isolator
9 Set
Earth Switch Interlock circuit.
CONVENTIONAL CONTROL PANELS
(THESE ARE REPLACED BY BCU’s IN AUTOMATION)
LINE + REACTOR PROTECTION PANEL
2RLB 2RLRC
LINE PROTECTION PANEL
S.NO DESCRIPTION QTY
75A 75A,B
75B 1 MAIN-1(21L1): Line Distance Protection 1 No
21L1 2 MAIN-2(21L2): Line Distance Protection 1 No 87R
a) Protection Function:
For each group of protection, separate DC sources
are recommended.
Example: Group-1: 21L1, 87T1, 67HV, 87R, 87BB1
Group-2: 21L2, 87T2, 67LV, 21R, 87BB2
b) CB Functions
Trip coil 1 & 2 shall be fed from separate sources.
Closing coil can be from either of these two sources.
c) Isolator / Earth switch
These associated with any one circuit shall be fed
from one of the two DC sources.
In the case of One and half (1 & ½) CB arrangement,
the Isolator / Earth switch associated with the tie CB
can be fed from either source 1 or 2.
CBIP Guidelines on Protection
GR-A & GR-B TRIPPINGS
It is recommended that:
(i) Separate cables are used for AC & DC circuit.
(ii) Separate cables are used for DC 1 & DC 2 circuits.
(iii) For different cores of CT & CVT separate cables
shall be used.
GROUP-A & GROUP-B TRIPPINGS
LINE TRANSFORMER REACTOR
PROTECTION PROTECTION PROTECTION
GROUP-A GROUP-A GROUP-A
MAIN-1 PROTECTION (21L1) T/F DIFFERENTIAL RELAY (87T1) REACTOR DIFFERENTIAL RELAY (87R)
M1 BUILT IN FUNCTIONS T/F B/U IMP RELAY (21T) REACTOR BACKUP RELAY (21 R)
TEED-1 PROTECTION (87 TEED-1) T/F HV BACKUP RELAY (67HV) OIL TEMP HIGH TRIP
OVER VOLTAGE STAGE-1 PROT (59-1) T/F HV OVERFLUX RELAY (99HV) PRESURE RELIEF TRIP
DIRECT TRIP CHANNEL-1 RECEIVED TERITIARY DELTA WNDG NDR PROT
OIL TEMP HIGH TRIP GROUP-B
GROUP-B PRESURE RELIEF TRIP REACTOR REF RELAY (64R)
MAIN-2 PROTCTION (21L2) GROUP-B BUCHHOLZ TRIP
M2 BUILT IN FUNCTIONS T/F HIGH Z DIFF RELAY (87T2) WINDING TEMP HIGH TRIP
TEED-2 PROTECTION (87 TEED-2) T/F NEUTRAL CURRENT RLY (51 NCT) LOW/ HIGH OIL LEVEL TRIP
OVER VOLTAGE STAGE-2 PROT (59-2) T/F LV BACKUP RELAY (67LV) FIRE PROTECTION TRIP
LBB/BFR RELAY (50Z) T/F LV OVERFLUX RELAY (99 LV)
DIRECT TRIP CHANNEL-2 RECEIVED OVER LOAD PROT (ALARM ONLY)
BUCHHOLZ TRIP
OLTC BUCHHOLZ TRIP
WINDING TEMP HIGH TRIP
LOW/ HIGH OIL LEVEL TRIP
PRINCIPLE OF Gr-A & Gr-B SEPERATION
BUS BAR PROT
CABLE
CABLE 96 BB
ABB Network Partner AG COM581
CT CABLE
SELCTION SELCTION
MAIN-1 86 Gr-A
CABLE PROT
CABLE
PT
BUS-2
ISOLATOR
BUS-2
SELCTION
PT
TRIP TRIP
COIL-1 COIL-2
LINE
CABLE
CABLE
CVT
DC -1/2
DC SOURCE-1 SELCTION
CABLE
DC SOURCE-2
CABLE
LINE PROTECTIONS TRANSFORMER PROTECTIONS
21L1 21L2 87T1 87T2
CIRCUIT BREAKER ABB Network Partner AG COM581
RELYS OF TRANSFER
BUS COUPLER C
E
NORMAL
TRANSFER
A A A
B B B
AUTO RECLSOING FUNCTION
AUTO RECLOSING CIRCUITS:
Arrangement of Relays
When Line is Transferred to Transfer Bus, Auto Reclosing Facility for This CB can be
extended in Two Ways
* CB Oriented
1. Individual Auto reclosure and Synchro-check relay for each CB . Hence co-
operation between CB’s and Synchro-check relay etc., is straight forward.
2. Interconnection between Line relays and reclosure relays complicated.
* LINE Oriented
1. Interconnection between Line relays and reclosure relays Simpler.
2. Connections to CB Oriented equipments complicated.
Note: CB Oriented Arrangement is preferred.
MAIN-1 PROTECTION CARRIER INTER TRIPPING
NSD 50
G4AC V9LC 1
G4AC V9LC 6 LINE 21L1
IN OUT
CR
CARRIER RECEIVE
G4AC V9LC 5 -VE
CS
G4AC V9LC 2 CARRIER SEND
G4AA V9LB 5
ABB
PANEL-1
+VE -VE
NSD 50
G4AC V9LC 10
G4AC V9LC 13
THIS IS BACKUP FOR PERMISSIVE/ PROTECTION TRIP
G4AC V9LC 14 AND CONNECTED IN ANOTHER PANEL
G4AC V9LC 9
ABB
PANEL-2
MAIN-2 PROTECTION CARRIER INTER TRIPPING
NSD 50
G4AC V9LC 1
G4AC V9LC 6 LINE 21L2
IN OUT
CR
CARRIER RECEIVE
G4AC V9LC 5 -VE
CS
G4AC V9LC 2 CARRIER SEND
G4AA V9LB 5
ABB
PANEL-2
+VE -VE
NSD 50
G4AC V9LC 10
G4AC V9LC 13
THIS IS BACKUP FOR PERMISSIVE/ PROTECTION TRIP
G4AC V9LC 14 AND CONNECTED IN ANOTHER PANEL
G4AC V9LC 9
ABB
PANEL-1
DIRECT TRANSFER TRIP – Gr-A
96 BUSBAR PROT PANEL
PANEL-1
87 BUSBAR TRIP
ABB
M_CB CONTROL PANEL
N T T NC
NSD 50
DC +VE
FROM PANEL
MAIN CB
BREAKER BACK-UP
NO
RETRIP
TRIP
YES WAIT FOR BACK-UP/
INITIATE FAULT AND
BFR Adjacent
CLEARENCE BREAKERS
52 52 52 52 52 52
CU CU
copper
copper
fiber
BUS-2
UU
UU
UU
UU
AUX BUS
UU
UU
UU
UU
BUS-2
UU
UU
UU
UU
AUX BUS
UU
UU
UU
UU
89C
89A
89B
89A
89B
89C
89C
89C
89A
89B
89A
89B
89A
89B
BUS-2
UU
UU
UU
UU
AUX BUS
UU
UU
UU
UU
89C
89A
89B
89A
89B
89C
89C
89C
89A
89B
89A
89B
89A
89B