EXPANSION VESSEL CALCULATION (FOR PRESSURIZATION UNIT)

PROJECT PUMP ARRANGEMENT STATIC HEAD - Ph (IN BAR) PRESSURE MARGIN Ps (0.3 BAR UP TO 90 DEGREE CELCIUS) INITIAL SYSTEM DESIGN PRESSURE( Pi = Ph+Ps IN BAR) FINAL DESIGN PRESSURE (MAXIMUM PERMISSIBLE AT SET Pf IN BAR) VOLUME ACCEPTANCE FACTOR -(VAF)- a TOTAL SYSTEM VOLUME ( Vs) IN LITERS EXPANSION % , e (46 degree C) EXPANDED VOLUME ( Va) SIZE OF EXPANSION VESSEL = EXPANDED VOLUME / VOLUME ACCEPTANCE FACTOR. SAFETY MARGIN (10 %) EXPANSION TANK CAPACITY INCLUDING SAFETY MARGIN HENCE EXPANSION VESSEL SIZE( IN LITERS) a1= EXPANDED VOLUME/EXPANSION VESSEL SISE MAXIMUM FINAL WORKING PRESSURE - Pfw (IN BAR) 7.00 0.30 7.30 8.50 0.13 45,000.00 1.03 463.50 3,669.38 366.94 4,036.31

4,000.00
0.12 8.39

NOTE - THIS CALCULATION IS BASED ON DATA PROVIDED BY CONTRACTOR, CONTRACTOR/CONSULTANT HAS TO VERIFY THIS.