Você está na página 1de 32

I -Rectangular Ducts:

DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

- Slip & Drive - Slide-on Flange - Companion Angle

II -Rectangular Ducts Welded

RECTANGULAR DUCTS

I -Rectangular Ducts:
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

- Slip & Drive - Slide-on Flange - Companion Angle

DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

DVAC Is One Of The Premium Workshops For The Duct Fabrication & Fittings. DVAC Has Executed Residential, Governmental, Commercial, Industrial, and Institutional Projects.

Table of Contents
I -Rectangular Ducts:
- Slip & Drive - Slide-on Flange - Companion Angle Page
Fabrication Procedure Bill Of Quantities Model Longitudinal Seams Fittings 4 5 6 7 8 9 10 Splitter Damper Acoustic Liner Installation Plenum Box Slip & Drive Companion Angle Slide-on Flange Suspension Flanges Construction Schedule - SMACNA 1" Construction Schedule - SMACNA 2 Construction Schedule - SMACNA 3 Construction Schedule - SMACNA 4 Construction Schedule - DW/144 500 Pa Construction Schedule - DW/144 1000 Pa Construction Schedule - DW/144 2000 Pa 11 12 13 14 15 16 17 18 19 20 21 22 23 24

II -Rectangular Ducts Welded


Longitudinal Seams and Connection Fittings

25 26 27 28

Tables: - Coating Mass (Weight) - GI Thicknesses - Weight of GI Steel

29

DOHA QATAR PHONE: +974 4500118 +974 4500119 FAX: +974 4500117

I -Rectangular Ducts:
Fabrication Procedure
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

FABRICATION PROCEDURE:
According to The Drawing / Take Off Provided by The Client, DVAC Engineers Start The Operation Production Following The Consequent Steps: a ) Shop Drawings to be Prepared Using CADmep. b ) Accurate B.O.Qs to be Issued Including Accessories And Connectors (Refer to Page 5). c ) An Estimation of The Cost Can be Provided to The Client Upon Issuance of B.O.Q. d ) Fabrication Begins By CAMDuct Linked to CNC Machines Based On CAD-Duct Drawings. e ) All Ductworks Are Fabricated According to SMACNA Or DW 142/144. f ) Each Item to be Numbered On The Drawing Provided, Fabricated Items to be Labeled; Each Label Shows The Project Name, Customer Name, Job Ref., Item Number, Item Description (Straight Duct, Elbow, Tee, VCD, VAV, Silencer, Etc...), Size & Length, Thickness, Weight And Area. g ) QA/QC to be Made For Each Item Before Collection (Delivery).
PB 300X300X3000 S12 S10 S11 350X300 S7 S9 S3 S6 BOD 2450 S8 BOD 2450 S2 S2 S3 S6 S2 S7 S11 S2 S7 S11 S2 S14 S13 BOD 2450

500X300 S8 S5 BOD 2800

S3 S6 BOD 2450

S2

S2

S3 S6

S4

BOD 2450

600X300 R5 S4 BOD 2800 R5

S1

FCU - 42TX-036 R4 500X200 R1 R2 BOD 2800 500X200 R2 BOD 2800 R1 R4

R3

Back to Index

I -Rectangular Ducts:
Bill Of Quantities - Model
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Customer: M/S. (Customer Name) Project : (Project Name)


Job Ref.: Contact Person: Tel: Page: 1/2 Fax:

Bill Of Quantities
DUCTVENTILATIONAIR CONDITIONING Co. (WLL)

Job Date: 17/02/2010 Printing Date: 20/02/2010

MATERIALS: Item No. S3 S11

Description Flex Flex

Qty 4 3

Duct Size (mm) 200 200

Length/Angle 1200 (mm) 600 (mm)

Duct Area

Total Area

Duct Weight

Total Weight

Insulation Area

Insulation

MATERIALS: GALVANIZED x 0.60 Item No. Description R2 S7 S8 S4 S13 S14 S9 S5 Straight Straight (Coil) Straight (Coil) Straight (Coil) Cap End(Alt) Straight (Cut) Drop Cheek Bend Taper

Qty 2 4 2 2 1 1 1 1

Duct Size (mm) 500x200 350x300 500x300 600x300 350x300 350x300 500x300 600x300

Length/Angle 1190 1190 1190 1190 0 560 90 360 (mm) (mm) (mm) (mm) (mm) (mm) (mm)

Duct Area 1.75 1.62 1.99 2.23 0.25 0.79 1.38 1.06

Total Area 3.49 6.48 3.97 4.46 0.25 0.79 1.38 1.06

Duct Weight 8.36 7.78 9.53 10.70 1.20 3.77 6.62 5.07

Total Weight 16.72 31.09 19.06 21.40 1.20 3.77 6.62 5.07

Insulation Area

Insulation

MATERIALS: GALVANIZED x 0.80 Item No. Description R4 R5 R1 Straight Taper Radius Bend

Qty 2 2 2

Duct Size (mm) 500x200 500x200 500x200

Length/Angle 1190 (mm) 260 (mm) 90

Duct Area 1.75 1.00 1.70

Total Area 3.49 2.00 3.39

Duct Weight 11.15 6.40 10.84

Total Weight 22.29 12.80 21.68

Insulation Area

Insulation

MATERIALS: GALVANIZED x 1.00 Item No. Description R3 S1 Breeches Piece Taper

Qty 1 1

Duct Size (mm) 1234x200 1234x219

Length/Angle 200 (mm) 560 (mm)

Duct Area 3.73 1.99

Total Area 3.73 1.99

Duct Weight 29.80 15.90

Total Weight 29.80 15.90

Insulation Area

Insulation

Description: Slot Plenum, Insulation: Item No. Description


S12 Slot Plenum

Qty 1 1

Width (mm) 300

Height (mm) 300

Length (mm) 3000

Total Length (m) 3.00 3.00

Slot Dimension (mm) 150

Neck Slot Collar Length (mm) Diameter 100 200

Collar Qty 3 3

Description: FCU - 42TX-036 Item No. Description S44 FCU - 42TX-036

Qty 1 1

Duct Size (mm) 1234x219

Length (mm) 600 (mm)

Prepared By: Approved By:

Customer Signature:

Customer: M/S. (Customer Name) Project : (Project Name)


Job Ref.: Contact Person: Tel: Page: 2/2 Fax:

Bill Of Quantities
DUCTVENTILATIONAIR CONDITIONING Co. (WLL)

Job Date: 17/02/2010 Printing Date: 20/02/2010

Description: Linear Diffuser Item No. Description S10 Linear Diffuser Description: Rnd Single Blade Damper Item No. Description S2 Rnd Single Blade Damper Description: Supply Plenum Box Item No. Description S6 Supply Plenum Box Description: Canvas Connection Item No. Description R6 Canvas Connection S15 Canvas Connection MATERIALS: GALVANIZED Gauge 0.60 0.80 1.00 Connector Name: S"S&D. SLIP Total Length "S" Cleat (m) 27.97 Connector Name: S&D. SLIP Total Length "S" Cleat (m) 10.26 Connector Name: Wire Mesh Item No R5

Qty 1 1 Qty 7 7 Qty 4 4 Qty 1 1 2

Duct Size (mm) 3000x150

Length (mm) 25 (mm)

Duct Size (mm) 200

Length (mm) 200 (mm)

Duct Size (mm) 450x450

Length (mm) 100 (mm)

Duct Size (mm) 1234x200 1234x219

Length (m) 2.87 2.91 5.78 Total Area (sq m) 21.85 8.87 5.72 36.43 Total Weight (kg) 104.88 56.76 45.69 207.32 Qty C Cleat L.1220mm 11

Total Length C Cleat (m) 12.39

Qty "S" Cleat L.1220mm 23

Total Length C Cleat (m) 8.55

Qty "S" Cleat L.1220mm 9

Qty C Cleat L.1220mm 8

Depth (m) 0.20

Width (m) 0.50

Qty 2 2

Area 0.20 0.20

Prepared By: Approved By:

Customer Signature:

Back to Index

I -Rectangular Ducts:
Longitudinal Seams
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

- Slip & Drive - Slide-on Flange - Companion Angle

As per: - SMACNA (2nd Edition-1995) See Pages 1.17/1.67/1.74 - SMACNA (3rd Edition-2005) See Pages 2.10/2.113 - DW/144 See Page 20

DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Straight Ducts are Beaded or Crossbroken


- Duct Sides that are 260mm and over, shall be Crossbroken or Beaded.

Grooved Corner Seam


- Galvanized Up to 20 Gage - Stainless Steel Up to 22 Gage

152.5 305

305

305
152.5

Beading

Pittsburgh Lock Seam


- Galvanized 16 Gage Maximum - Stainless Steel 20 Gage Maximum

Grooved Seam
- Galvanized 16 Gage Maximum - Stainless Steel 20 Gage Maximum

* Materials Used for Ductworks :


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation. - Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L. - Aluminum Metal : (Optional) Complying with ASTM B209, Alloy 3003, Temper H14.

* Can Be Supplied with Acoustic Lining or Double Wall


6 Back to Index

I -Rectangular Ducts:
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

- Slip & Drive - Slide-on Flange - Companion Angle

As per: - SMACNA (2nd Edition-1995) See Pages 2.3/2.9/A.42/A.43 - SMACNA (3rd Edition-2005) See Pages 4.3/4.9/4.12/4.13 - DW/144 See Pages 55/57

DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Straight
Standard Length 1220mm While Using Slip & Drive Length Will be 1190mm

Taper

22.5 Max.

OW

W1 x D1 WxD

OD

W2 x D2

L1

L1

A
Radius Bend
Width - mm 400 - 800 801 - 1600 1601 - 2000 Splitters 1 2 3
A Splitter Position B C

B
Medium Radius Bend (as illustrated)
Can be Applied to any Angle
W/3 W/4 W/8 W/2 W/3 W/2

Splitters not Required in Bend Angles Less Than 45

Long Radius Bend


Similar but Radius = Width Can be Applied to any Angle

B A

WxD

Minimum Throat Radius = 100mm DVAC Standard Throat Radius = 150mm

D
Master Bend

WxD

Throat Radius = Width

Drop Cheek Bend


Can be Applied to any Angle

Outer R W2 x D2

OD

W2 x D2

Inner R

W1 x D1

W1 x D1

E
* Materials Used for Ductworks :

F
- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation. - Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L. - Aluminum Metal : (Optional) Complying with ASTM B209, Alloy 3003, Temper H14.

* Can Be Supplied with Acoustic Lining or Double Wall


7 Back to Index

I -Rectangular Ducts:
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

- Slip & Drive - Slide-on Flange - Companion Angle

As per: - SMACNA (2nd Edition-1995) See Pages 2.8/2.9 - SMACNA (3rd Edition-2005) See Pages 4.8/4.9 - DW/144 See Pages 55/58

DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Shoe Branch
WxD

Width (W) mm Up to 200 ,, ,, 300 400 600

Dim. (A) mm 75 100 125 150 200

Straight + 2 Branches
W2 x D2

,,

Over 600

Clinch Lock (Optional) Duct Sealant 25mm

Straight Tap (DVAC Standard) Duct Sealant Fixing by Rivets or Self-Tapping Screws 25mm

W1 x D1

L1

G
Radius 2-Way Offset
Minimum Throat Radius = 150mm

H
Straight + Branch

W3 x D3

W2 x D2

W1 x D1

OW

OD

W2 x D2

W1 x D1

I
Mitered Offset

L1

J
Radius Offset
Minimum Throat Radius = 150mm

L1

30 Max. WxD

OW

W1 x D

OW

E1 E2 W2 L1

K
* Materials Used for Ductworks :

L1

- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation. - Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L. - Aluminum Metal : (Optional) Complying with ASTM B209, Alloy 3003, Temper H14.

* Can Be Supplied with Acoustic Lining or Double Wall


8 Back to Index

I -Rectangular Ducts:
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

- Slip & Drive - Slide-on Flange - Companion Angle

As per: - SMACNA (2nd Edition-1995) See Pages 2.8/2.9/3.18 - SMACNA (3rd Edition-2005) See Pages 3.36/4.8/4.9 - DW/144 See Pages 55/58

DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Angled Offset

Trousers Piece
W2 x D2 O W3 x D2

15 Max.

OW
WxD

OD

OW

W1 x D1 L1

M
Square to Round
22.5 Max.

N
Collar (Dovetail)
VCD Optional
75mm

OW

Sealant
WxD

OD

Crimped Beaded Duct


L1

O
Drop Cheek Breeches Piece

P
3-Way Tee
Splitter Damper Optional
W3

W2 x D2

OD2

OD3

W3 x D3 W2

W4

R2 R1 W1 x D1 R2 R1 W1 x D

Q
* Materials Used for Ductworks :

R
- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation. - Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L. - Aluminum Metal : (Optional) Complying with ASTM B209, Alloy 3003, Temper H14.

* Can Be Supplied with Acoustic Lining or Double Wall


9 Back to Index

I -Rectangular Ducts:
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

- Slip & Drive - Slide-on Flange - Companion Angle

As per: - SMACNA (2nd Edition-1995) See Page 2.7 - SMACNA (3rd Edition-2005) See Page 4.7 - DW/144 See Pages 52/55

DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Breeches Piece
Splitter Damper Optional

Radius Tee

W2

W3

W2

W3

R1 W1 x D

R2

R1 W1 x D

R2

S
Side Branch
Splitter Damper Optional
W2

T
2-Way Breeches
W2 x D2

OD2
W3

OD3

W3 x D3

R W1 x D W1 x D1

U
Flexible Connection

V
Plenum Box
Side or Top Connection

WxD

WxD

W
* Materials Used for Ductworks :

X
- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation. - Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L. - Aluminum Metal : (Optional) Complying with ASTM B209, Alloy 3003, Temper H14.

* Can Be Supplied with Acoustic Lining or Double Wall


10 Back to Index

I -Rectangular Ducts:
Splitter Damper
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

- Slip & Drive - Slide-on Flange - Companion Angle

DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Splitter Damper

Piano Hinge Blade

Control Rod

Splitter Damper Length (A x 1.5)

Aerofoil Blade Splitter Damper (DVAC Standard)


Piano Hinge Blade

W2 x D2

OD2

OD3

W3 x D3

Single Blade Splitter Damper


Piano Hinge Blade

B W1 x D1

* Materials Used for Ductworks :


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation. - Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L. - Aluminum Metal : (Optional) Complying with ASTM B209, Alloy 3003, Temper H14.

* Can Be Supplied with Acoustic Lining or Double Wall


11 Back to Index

I -Rectangular Ducts:
Duct Acoustic Liner
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

- Slip & Drive - Slide-on Flange - Companion Angle

As per: - SMACNA (2nd Edition-1995) See Pages 2.24/2.28 - SMACNA (3rd Edition-2005) See Pages 7.13/7.17

DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Acoustic Liner Installation Insulation Guard (DVAC Standard)


24 Gage Liner 24 Gage

Liner

Insulation Guard (Channel)


Rivets

Duct

Duct

Tog-L-Loc or Rivets

Liner

Insulation Guard (Zee)


Rivets

24 Gage

Duct

Liner Welding Pin

B A E B E C B A Insulation Guard Fixing byTog-L-Loc or Rivets Welding Pin "A" Pin Row May be Omitted when Metal Nosing is Used. Then E Starts from the Nosing. Dimensions Velocity * A 0 - 2500 FPM (0 - 12.7 MPS) 2501 - 6000 FPM (12.7 - 30.5 MPS) 3" (76.2) 3" (76.2) B 12" (305) 12" (305) C 4" (102) 4" (102) D 6" (152) 6" (152) E 18" (457) 18" (457) All Transverse Edges to be Coated with Adhesive, Except when Nosing is present. D

D Alternate Folded Corner

Liner Adhered to the Duct with 90% Min. Area Coverage of Adhesive.

* Materials Used for Acoustic Liner :


- Insulation

: KIMMCO Clean Liner 15mm, 48 kg/m3, is Faced with a Black, Strong, Durable, Dimensionally Stable Woven Glass Fabric. - Adhesive : Foster 80-10 - Duct Sealant : Foster 32-17

* Optional : - Acoustic Liner as per Client Request


12 Back to Index

I -Rectangular Ducts:
Plenum Box
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
As per: - SMACNA (2nd Edition-1995) See Page 2.20 - SMACNA (3rd Edition-2005) See Page 10.1

DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Plenum Box
* Plenum Box : Fabricated of 22 Gage Galvanized Steel * Acoustic Liner : KIMMCO Clean Liner 15mm, 48 kg/m3, is Faced with a Black, Strong, Durable, Dimensionally Stable Woven Glass Fabric. * Optional :- Volume Control Damper. - Inside Insulation Covered with Galvanized Perforated Sheet Insuring Full Protection. - Acoustic Liner as per Client Request.
Hanging Bracket

L + 50mm Plenum Box Acoustic Liner C

B Liner Welding Pin A

76mm W

Plenum Box H

O2 D

Tog-L-Loc or Rivets

Standard 76mm

Crimped O1 Beaded Plenum Box Insulation Guard Tog-L-Loc or Rivets

End Cap

* Liner Adhered to the Plenum Box with 100% Area Coverage of Adhesive. * Welding Pins Fixation from Center to Center: 300mm.

* Materials Used for Ductworks :


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation. - Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L. - Aluminum Metal : (Optional) Complying with ASTM B209, Alloy 3003, Temper H14.

13

Back to Index

I -Rectangular Ducts:
DVAC Accessories
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
As per: - SMACNA (2nd Edition-1995) See Pages 1.14/1.61 - SMACNA (3rd Edition-2005) See Pages 2.6/2.7/2.8 - DW/142 See Pages 28/31

DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Slip & Drive


Standing S

Duct

Hemmed S Slip (DVAC Standard)

Standing S (Optional)

Standing S 28.6 (DVAC Standard)

Standing S 41.3 (Optional)

Standing S 54 (Optional)

C1 / T-6

C2 / T-10

C2 / T-10

T-13
5 5

C3 / C4 / T-14
5

54 41.3 15 28.6

27 Thickness 0.6mm

27 Thickness 0.6mm

35 Thickness 0.6 to 1.0mm

35 Thickness 0.7 to 1.2mm

35 Thickness 1.0mm

Drive Slip

Backup Angle for Drive Slip

C1 / T-1

T-3

DVACStandard

Optional

75

28.5 Thickness 0.6 to 1.0mm

28.5 Thickness 0.8 to 1.2mm

28.5

* Materials Used for Duct Accessories :


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation. - Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L. - Aluminum Metal : (Optional) Complying with ASTM B209, Alloy 3003, Temper H14. * NOTE : Standard Length of Hemmed S, Standing S & Drive Slip is 1220mm.
14 Back to Index

I -Rectangular Ducts:
DVAC Accessories
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
As per: - SMACNA (2nd Edition-1995) See Pages 1.14/1.61 - SMACNA (3rd Edition-2005) See Pages 2.6/2.7/2.8 - DW/142 See Pages 28/31

DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Companion Angles J3 / J4 / J5 / J6 / T-22

Duct

Fixing by Rivets or Screws

Companion Angle

Gasket

Dimensions 25 x 3 30 x 4 40 x 4

Rating J3 J4 J5

- Duct Ends Turn up 10mm. - Fixing Bolts at Each Corner Intermediately Centers at 300mm.

50 x 5 J6 Fixing Bolts 25 x 3 30 x 4 40 x 4 50 x 5 6mm 8mm 8mm 10mm

* Materials Used for Duct Accessories :


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation. - Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L. - Aluminum Metal : (Optional) Complying with ASTM B209, Alloy 3003, Temper H14. * NOTE : Companion Angle & Reinforcement are Made of Primer Painted Black Steel Angle.
15 Back to Index

I -Rectangular Ducts:
VENTO Accessories
(BELGIUM)

DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)


DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Slide-on Flange

Duct

Lance-N-Locor Rivets

Flange

Gasket

Drive Slip
SR

Clamp with Screw

Flange System 20

8.5 CM Thickness 0.7mm 20

E20

18

H20

SR40 8x20

25 Thickness 0.6mm

73

Thickness 1.0mm

Thickness 3.0mm

Thickness 0.7mm

Thickness 2.5mm

Flange System 40
10 A40 37 H40 8.5

Flange System 30
E30 27 H30

40 30

36 Thickness 0.9mm Thickness 1.0mm

140

27 Thickness 0.7mm

105

Thickness 3.0mm

Thickness 0.8mm

Thickness 3.0mm

* Materials Used for Duct Accessories :


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation. - Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L. - Aluminum Metal : (Optional) Complying with ASTM B209, Alloy 3003, Temper H14. * NOTE : DVAC Standard Use For Flange System : - 20: Thickness 0.7mm
- 30: Thickness 0.8mm - 40: Thickness 1.0mm 16 Back to Index

I -Rectangular Ducts:
VENTO Accessories
(BELGIUM)

DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)


DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

VENTO Suspension Flanges Type: U


L

14 14 14 1.5 1.5 30 20 30 30 35 2 50

Code U203 U206

Length 3m 6m

Code U353 U356

Length 3m 6m

Code U503 U503

Length 3m 6m

Type: UP
L

10.5

24

50
14 14 14 2 50

1.5
1.5 30 20 30

35 30

Code UP203 UP206

Length 3m 6m

Code UP353 UP356

Length 3m 6m

Code UP503 UP506

Length 3m 6m

* Materials Used for Duct Accessories :


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation.

17

Back to Index

I -Rectangular Ducts:
Ductwork Construction Schedule - Tables 1A / 1B / 1C - 1"
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
As per: - SMACNA (3rd Edition-2005 Table 2-2) See Page 2.16

DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117


OPTION -1-

1"

Transverse Connections

Table 1A : 1" W.G. Static Positive or Negative (as per SMACNA Third Edition - 2005 Table 2-2)
Gage Straight Seam Fittings
Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Not Required Not Required Not Required Not Required Not Required Not Required Not Required Not Required Angle 50x50x5mm @ 600mm Gage 24 Gage 24

75

Duct Dimension (mm)


0 - 400 401 - 750 751 - 900 901 - 1200 1201 - 1500 1501 - 1800 1801 - 2100 2101 - 2700 2701 - 3000

Intermediate Reinforcement

T-1 Drive Slip

T-3 Drive Slip with Backup Angle

T-6 Hemmed S Slip


Gage 24

T-10 Standing S H. 28.6mm

T-13 Standing S H. 41.3mm

T-14 Standing S H. 54mm

T-22 Companion Angles

Slide-on Flange

26 26 26 24 24 22 20 18 18

Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Pittsburgh Lock Pittsburgh Lock

Gage 22 Gage 22 + 25X25X3 Angle Gage 20 Flange 20 Thickness 0.7mm Flange 30 Thickness 0.8mm Flange 30 Thickness 0.8mm Flange 40 Thickness 1.0mm Flange 40 Thickness 1.0mm Flange 40 Thickness 1.0mm

1"

OPTION -2-

Transverse Connections

Table 1B : 1" W.G. Static Positive or Negative (as per SMACNA Third Edition - 2005 Table 2-2)
Gage Straight Seam Fittings
Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Not Required Not Required Not Required Not Required Not Required Not Required Not Required Not Required Angle 50x50x5mm @ 600mm Gage 24 Gage 24

75

Duct Dimension (mm)


0 - 400 401 - 750 751 - 900 901 - 1200 1201 - 1500 1501 - 1800 1801 - 2100 2101 - 2700 2701 - 3000

Intermediate Reinforcement

T-1 Drive Slip

T-3 Drive Slip with Backup Angle

T-6 Hemmed S Slip


Gage 24

T-10 Standing S H. 28.6mm

T-13 Standing S H. 41.3mm

T-14 Standing S H. 54mm

T-22 Companion Angles

Slide-on Flange

26 26 26 24 24 22 20 18 18

Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Pittsburgh Lock Pittsburgh Lock

Gage 22 Gage 22 + 25X25X3 Angle Gage 20 25x25x3mm 25x25x3mm 40x40x4mm 50x50x5mm 50x50x5mm 50x50x5mm

1"

AS PER PROJECT SPECS.

Transverse Connections

Table 1C : 1" W.G. Static Positive or Negative (as per SMACNA Third Edition - 2005 Table 2-2)
Gage Straight Seam Fittings
Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock

75

Duct Dimension (mm)


0 - 400 401 - 750 751 - 900 901 - 1200 1201 - 1500 1501 - 1800 1801 - 2100 2101 - 2700 2701 - 3000

Intermediate Reinforcement

T-1 Drive Slip

T-3 Drive Slip with Backup Angle

T-6 Hemmed S Slip

T-10 Standing S H. 28.6mm

T-13 Standing S H. 41.3mm

T-14 Standing S H. 54mm

T-22 Companion Angles

Slide-on Flange

Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Pittsburgh Lock Pittsburgh Lock

* Materials Used for Transverse Connections :


- Galvanized Steel:(Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation. - Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L. * NOTE : 1 - Transverse Connectors are Based on 1200mm Spacing.
2 - Standard Straight Duct Length 1220mm. 3 - Companion Angle & Reinforcement are Made of Primer Painted Black Steel Angle. 18 Back to Index

I -Rectangular Ducts:
Ductwork Construction Schedule - Tables 2A / 2B / 2C - 2"
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
As per: - SMACNA (3rd Edition-2005 Table 2-3) See Page 2.18

DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117


OPTION -1-

2"

Transverse Connections

Table 2A : 2" W.G. Static Positive or Negative (as per SMACNA Third Edition - 2005 Table 2-3)
Gage Straight Seam Fittings
Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Not Required Not Required Not Required Not Required Not Required Not Required Not Required Angle 50x50x5mm @ 600mm Angle 50x50x5mm @ 600mm Gage 24 Gage 24

75

Duct Dimension (mm)


0 - 300 301 - 550 551 - 700 701 - 900 901 - 1200 1201 - 1500 1501 - 2100 2101 - 2700 2701 - 3000

Intermediate Reinforcement

T-1 Drive Slip

T-3 Drive Slip with Backup Angle

T-6 Hemmed S Slip


Gage 24

T-10 Standing S H. 28.6mm

T-13 Standing S H. 41.3mm

T-14 Standing S H. 54mm

T-22 Companion Angles

Slide-on Flange

26 26 26 24 22 20 20 18 18

Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Pittsburgh Lock Pittsburgh Lock

Gage 22 Gage 22 + 25X25X3 Angle Gage 20 Flange 20 Thickness 0.7mm Flange 30 Thickness 0.8mm Flange 30 Thickness 0.8mm Flange 40 Thickness 1.0mm Flange 40 Thickness 1.0mm Flange 40 Thickness 1.0mm

2"

OPTION -2-

Transverse Connections

Table 2B : 2" W.G. Static Positive or Negative (as per SMACNA Third Edition - 2005 Table 2-3)
Gage Straight Seam Fittings
Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Not Required Not Required Not Required Not Required Not Required Not Required Not Required Angle 50x50x5mm @ 600mm Angle 50x50x5mm @ 600mm Gage 24 Gage 24

75

Duct Dimension (mm)


0 - 300 301 - 550 551 - 700 701 - 900 901 - 1200 1201 - 1500 1501 - 2100 2101 - 2700 2701 - 3000

Intermediate Reinforcement

T-1 Drive Slip

T-3 Drive Slip with Backup Angle

T-6 Hemmed S Slip


Gage 24

T-10 Standing S H. 28.6mm

T-13 Standing S H. 41.3mm

T-14 Standing S H. 54mm

T-22 Companion Angles

Slide-on Flange

26 26 26 24 22 20 20 18 18

Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Pittsburgh Lock Pittsburgh Lock

Gage 22 Gage 22 + 25X25X3 Angle Gage 20 25x25x3mm 25x25x3mm 40x40x4mm 50x50x5mm 50x50x5mm 50x50x5mm

2"

AS PER PROJECT SPECS.

Transverse Connections

Table 2C : 2" W.G. Static Positive or Negative (as per SMACNA Third Edition - 2005 Table 2-3)
Gage Straight Seam Fittings
Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock

75

Duct Dimension (mm)


0 - 300 301 - 550 551 - 700 701 - 900 901 - 1200 1201 - 1500 1501 - 2100 2101 - 2700 2701 - 3000

Intermediate Reinforcement

T-1 Drive Slip

T-3 Drive Slip with Backup Angle

T-6 Hemmed S Slip

T-10 Standing S H. 28.6mm

T-13 Standing S H. 41.3mm

T-14 Standing S H. 54mm

T-22 Companion Angles

Slide-on Flange

Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Pittsburgh Lock Pittsburgh Lock

* Materials Used for Transverse Connections :


- Galvanized Steel:(Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation. - Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L. * NOTE : 1 - Transverse Connectors are Based on 1200mm Spacing.
2 - Standard Straight Duct Length 1220mm. 3 - Companion Angle & Reinforcement are Made of Primer Painted Black Steel Angle. 19 Back to Index

I -Rectangular Ducts:
Ductwork Construction Schedule - Tables 3A / 3B / 3C - 3"
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
As per: - SMACNA (3rd Edition-2005 Table 2-4) See Page 2.20

DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117


OPTION -1-

3"

Transverse Connections

Table 3A : 3" W.G. Static Positive or Negative (as per SMACNA Third Edition - 2005 Table 2-4)
Gage Straight Seam Fittings
Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Not Required Not Required Not Required Not Required Not Required Not Required Angle 50x50x5mm @ 600mm Angle 50x50x5mm @ 600mm Angle 50x50x5mm @ 600mm Gage 24 Gage 24

75

Duct Dimension (mm)


0 - 300 301- 450 451 - 750 751 - 1000 1001 - 1200 1201 - 1500 1501 - 1800 1801 - 2400 2401 - 3000

Intermediate Reinforcement

T-1 Drive Slip

T-3 Drive Slip with Backup Angle

T-6 Hemmed S Slip

T-10 Standing S H. 28.6mm


Gage 24 Gage 22

T-13 Standing S H. 41.3mm

T-14 Standing S H. 54mm

T-22 Companion Angles

Slide-on Flange

26 26 24 22 20 18 18 18 18

Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock

Flange 20 Thickness 0.7mm Flange 30 Thickness 0.8mm Flange 30 Thickness 0.8mm Flange 40 Thickness 1.0mm Flange 40 Thickness 1.0mm Flange 40 Thickness 1.0mm 50x50x5mm

3"

OPTION -2-

Transverse Connections

Table 3B : 3" W.G. Static Positive or Negative (as per SMACNA Third Edition - 2005 Table 2-4)
Gage Straight Seam Fittings
Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Not Required Not Required Not Required Not Required Not Required Not Required Angle 50x50x5mm @ 600mm Angle 50x50x5mm @ 600mm Angle 50x50x5mm @ 600mm Gage 24 Gage 24

75

Duct Dimension (mm)


0 - 300 301- 450 451 - 750 751 - 1000 1001 - 1200 1201 - 1500 1501 - 1800 1801 - 2400 2401 - 3000

Intermediate Reinforcement

T-1 Drive Slip

T-3 Drive Slip with Backup Angle

T-6 Hemmed S Slip

T-10 Standing S H. 28.6mm


Gage 24 Gage 22

T-13 Standing S H. 41.3mm

T-14 Standing S H. 54mm

T-22 Companion Angles

Slide-on Flange

26 26 24 22 20 18 18 18 18

Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock

25x25x3mm 30x30x3mm 40x40x4mm 50x50x5mm 50x50x5mm 50x50x5mm 50x50x5mm

3"

AS PER PROJECT SPECS.

Transverse Connections

Table 3C : 3" W.G. Static Positive or Negative (as per SMACNA Third Edition - 2005 Table 2-4)
Gage Straight Seam Fittings
Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock

75

Duct Dimension (mm)


0 - 300 301- 450 451 - 750 751 - 1000 1001 - 1200 1201 - 1500 1501 - 1800 1801 - 2400 2401 - 3000

Intermediate Reinforcement

T-1 Drive Slip

T-3 Drive Slip with Backup Angle

T-6 Hemmed S Slip

T-10 Standing S H. 28.6mm

T-13 Standing S H. 41.3mm

T-14 Standing S H. 54mm

T-22 Companion Angles

Slide-on Flange

Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock

* Materials Used for Transverse Connections :


- Galvanized Steel:(Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation. - Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L. * NOTE : 1 - Transverse Connectors are Based on 1200mm Spacing.
2 - Standard Straight Duct Length 1220mm. 3 - Companion Angle & Reinforcement are Made of Primer Painted Black Steel Angle. 20 Back to Index

I -Rectangular Ducts:
Ductwork Construction Schedule - Tables 4A / 4B / 4C - 4"
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
As per: - SMACNA (3rd Edition-2005 Table 2-5) See Page 2.22

DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117


OPTION -1-

4"

Transverse Connections

Table 4A : 4" W.G. Static Positive or Negative (as per SMACNA Third Edition - 2005 Table 2-5)
Gage Straight Seam Fittings
Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Not Required Not Required Not Required Not Required Not Required Not Required Angle 50x50x5mm @ 600mm Angle 50x50x5mm @ 600mm Angle 50x50x5mm @ 600mm Gage 24 Gage 24

75

Duct Dimension (mm)


0 - 250 251- 400 401 - 650 651 - 900 901 - 1000 1001 - 1500 1501 - 2100 2101 - 2400 2401 - 3000

Intermediate Reinforcement

T-1 Drive Slip

T-3 Drive Slip with Backup Angle

T-6 Hemmed S Slip

T-10 Standing S H. 28.6mm


Gage 24 Gage 22

T-13 Standing S H. 41.3mm

T-14 Standing S H. 54mm

T-22 Companion Angles

Slide-on Flange

26 26 24 22 20 18 18 18 18

Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock

Flange 20 Thickness 0.7mm Flange 30 Thickness 0.8mm Flange 30 Thickness 0.8mm Flange 40 Thickness 1.0mm Flange 40 Thickness 1.0mm 50x50x5mm 50x50x5mm

4"

OPTION -2-

Transverse Connections

Table 4B : 4" W.G. Static Positive or Negative (as per SMACNA Third Edition - 2005 Table 2-5)
Gage Straight Seam Fittings
Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Not Required Not Required Not Required Not Required Not Required Not Required Angle 50x50x5mm @ 600mm Angle 50x50x5mm @ 600mm Angle 50x50x5mm @ 600mm Gage 24 Gage 24

75

Duct Dimension (mm)


0 - 250 251- 400 401 - 650 651 - 900 901 - 1000 1001 - 1500 1501 - 2100 2101 - 2400 2401 - 3000

Intermediate Reinforcement

T-1 Drive Slip

T-3 Drive Slip with Backup Angle

T-6 Hemmed S Slip

T-10 Standing S H. 28.6mm


Gage 24 Gage 22

T-13 Standing S H. 41.3mm

T-14 Standing S H. 54mm

T-22 Companion Angles

Slide-on Flange

26 26 24 22 20 18 18 18 18

Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock

25x25x3mm 30x30x3mm 40x40x4mm 50x50x5mm 50x50x5mm 50x50x5mm 50x50x5mm

4"

AS PER PROJECT SPECS.

Transverse Connections

Table 4C : 4" W.G. Static Positive or Negative (as per SMACNA Third Edition - 2005 Table 2-5)
Gage Straight Seam Fittings
Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock

75

Duct Dimension (mm)


0 - 250 251- 400 401 - 650 651 - 900 901 - 1000 1001 - 1500 1501 - 2100 2101 - 2400 2401 - 3000

Intermediate Reinforcement

T-1 Drive Slip

T-3 Drive Slip with Backup Angle

T-6 Hemmed S Slip

T-10 Standing S H. 28.6mm

T-13 Standing S H. 41.3mm

T-14 Standing S H. 54mm

T-22 Companion Angles

Slide-on Flange

Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock

* Materials Used for Transverse Connections :


- Galvanized Steel:(Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation. - Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L. * NOTE : 1 - Transverse Connectors are Based on 1200mm Spacing.
2 - Standard Straight Duct Length 1220mm. 3 - Companion Angle & Reinforcement are Made of Primer Painted Black Steel Angle. 21 Back to Index

I -Rectangular Ducts:
Ductwork Construction Schedule - Tables 5A / 5B / 5C - 500 Pa
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
As per: - DW/142 See Page 18 - DW/144 See Page 18

DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

500 Pa
Duct Dimension (mm)

OPTION -1Table 5A : LOW PRESSURE 500 Pa Positive as per DW/142-144 Table 2)

Transverse Connections

Thick. (mm)
Straight

Seam Fittings
Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock

Intermediate Reinforcement
Not Required Not Required Not Required Not Required Angle 30x30x3mm @ 600mm Angle 40x40x4mm @ 600mm Angle 50x50x5mm @ 600mm Angle 50x50x5mm @ 600mm

C1 Drive Slip

C1 Drive Slip

C1 Hemmed S Slip
0.6mm 0.6mm

C2 Standing S H. 28.6mm

C3 Standing S H. 28.6mm

C4 Standing S H. 41.3mm

Companion Angles

Slide-on Flange

0 - 400

0.6 0.8 0.8 1.0 1.0 1.0 1.0 1.2

Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Pittsburgh Lock

0.6mm 0.6mm 0.8mm

401 - 600
601 - 1000 1001 - 1250

0.8mm Flange 30 Thickness 0.8mm Flange 30 Thickness 0.8mm Flange 40 Thickness 1.0mm Flange 40 Thickness 1.0mm Flange 40 Thickness 1.0mm

1251 - 1600 1601 - 2000 2001 - 2500 2501 - 3000

500 Pa
Duct Dimension (mm)

OPTION -2Table 5B : LOW PRESSURE 500 Pa Positive as per DW/142-144 Table 2)

Transverse Connections

Thick.
Straight

Seam Fittings
Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock

Intermediate Reinforcement
Not Required Not Required Not Required Not Required Angle 30x30x3mm @ 600mm Angle 40x40x4mm @ 600mm Angle 50x50x5mm @ 600mm Angle 50x50x5mm @ 600mm

C1 Drive Slip

C1 Drive Slip

C1 Hemmed S Slip
0.6mm 0.6mm

C2 Standing S H. 28.6mm

C3 Standing S H. 28.6mm

C4 Standing S H. 41.3mm

Companion Angles

Slide-on Flange

0 - 400

0.6 0.8 0.8 1.0 1.0 1.0 1.0 1.2

Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Pittsburgh Lock

0.6mm 0.6mm 0.8mm

401 - 600
601 - 1000 1001 - 1250

0.8mm 25x25x3mm 30x30x3mm 40x40x4mm 40x40x4mm 40x40x4mm

1251 - 1600 1601 - 2000 2001 - 2500 2501 - 3000

500 Pa
Duct Dimension (mm)

AS PER PROJECT SPECS.


Table 5C : LOW PRESSURE 500 Pa Positive as per DW/142-144 Table 2)

Transverse Connections

Thick.
Straight

Seam Fittings
Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock

Intermediate Reinforcement

C1 Drive Slip

C1 Drive Slip

C1 Hemmed S Slip

C2 Standing S H. 28.6mm

C3 Standing S H. 28.6mm

C4 Standing S H. 41.3mm

Companion Angles

Slide-on Flange

0 - 400

Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Pittsburgh Lock

401 - 600
601 - 1000 1001 - 1250

1251 - 1600 1601 - 2000 2001 - 2500 2501 - 3000

* Materials Used for Transverse Connections :


- Galvanized Steel:(Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation. - Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L. * NOTE : 1 - Transverse Connectors are Based on 1200mm Spacing.
2 - Standard Straight Duct Length 1220mm. 3 - Companion Angle & Reinforcement are Made of Primer Painted Black Steel Angle. 22 Back to Index

I -Rectangular Ducts:
Ductwork Construction Schedule - Tables 6A / 6B / 6C - 1000 Pa
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
As per: - DW/142 See Page 19 - DW/144 See Page 19

DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

1000 Pa
Duct Dimension (mm)

OPTION -1-

Transverse Connections

Table 6A : MEDIUM PRESSURE 1000 Pa Positive as per DW/142-144 Table 3)


Thick.
Straight
0 - 400
0.6 0.8 0.8 0.8 1.0 1.0 1.2
Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Pittsburgh Lock

Seam Fittings
Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock

Intermediate Reinforcement
Not Required Not Required Not Required Not Required Angle 40x40x4mm @ 600mm Angle 50x50x5mm @ 600mm Angle 60x60x5mm @ 600mm

C1 Drive Slip

C1 Drive Slip

C1 Hemmed S Slip
0.6mm

C2 Standing S H. 28.6mm

C3 Standing S H. 28.6mm

C4 Standing S H. 41.3mm

Companion Angles

Slide-on Flange

0.6mm 0.6mm

401 - 600
601 - 800 801 - 1000

0.8mm Flange 20 Thickness 0.7mm Flange 30 Thickness 0.8mm Flange 40 Thickness 1.0mm Flange 40 Thickness 1.0mm 50x50x5mm

1001 - 1600 1601 - 2500 2501 - 3000

1000 Pa
Duct Dimension (mm)

OPTION -2-

Transverse Connections

Table 6B : MEDIUM PRESSURE 1000 Pa Positive as per DW/142-144 Table 3)


Thick.
Straight
0 - 400
0.6 0.8 0.8 0.8 1.0 1.0 1.2
Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Pittsburgh Lock

Seam Fittings
Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock

Intermediate Reinforcement
Not Required Not Required Not Required Not Required Angle 40x40x4mm @ 600mm Angle 50x50x5mm @ 600mm Angle 60x60x5mm @ 600mm

C1 Drive Slip

C1 Drive Slip

C1 Hemmed S Slip
0.6mm

C2 Standing S H. 28.6mm

C3 Standing S H. 28.6mm

C4 Standing S H. 41.3mm

Companion Angles

Slide-on Flange

0.6mm 0.6mm

401 - 600
601 - 800 801 - 1000

0.8mm 25x25x3mm 30x30x3mm 30x30x3mm 40x40x4mm 50x50x5mm

1001 - 1600 1601 - 2500 2501 - 3000

1000 Pa AS PER PROJECT SPECS.


Table 6C : MEDIUM PRESSURE 1000 Pa Positive as per DW/142-144 Table 3)
Duct Dimension (mm)

Transverse Connections

Thick.
Straight

Seam Fittings
Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock

Intermediate Reinforcement

C1 Drive Slip

C1 Drive Slip

C1 Hemmed S Slip

C2 Standing S H. 28.6mm

C3 Standing S H. 28.6mm

C4 Standing S H. 41.3mm

Companion Angles

Slide-on Flange

0 - 400

Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Pittsburgh Lock

401 - 600
601 - 800 801 - 1000

1001 - 1600 1601 - 2500 2501 - 3000

* Materials Used for Transverse Connections :


- Galvanized Steel:(Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation. - Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L. * NOTE : 1 - Transverse Connectors are Based on 1200mm Spacing.
2 - Standard Straight Duct Length 1220mm. 3 - Companion Angle & Reinforcement are Made of Primer Painted Black Steel Angle. 23 Back to Index

I -Rectangular Ducts:
Ductwork Construction Schedule - Tables 7A / 7B / 7C - 2000 Pa
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
As per: - DW/144 See Page 19

DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

2000 Pa
Duct Dimension (mm)

OPTION -1-

Transverse Connections

Table 7A : HIGH PRESSURE 2000 Pa Positive (as per DW/142-144 Table 4)


Thick.
Straight
0 - 600
0.8 0.8 0.8 1.0 1.0 1.2 1.2
Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Pittsburgh Lock Pittsburgh Lock

Seam Fittings
Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock

Intermediate Reinforcement
Not Required Not Required Angle 30x30x3mm @ 600mm Angle 40x40x4mm @ 600mm Angle 50x50x5mm @ 600mm Angle 50x50x5mm @ 600mm Angle 60x60x5mm @ 600mm

C1 Drive Slip

C1 Drive Slip

C1 Hemmed S Slip

C2 Standing S H. 28.6mm

C3 Standing S H. 28.6mm

C4 Standing S H. 41.3mm

Companion Angles

Slide-on Flange
Flange 20 Thickness 0.7mm Flange 30 Thickness 0.8mm Flange 30 Thickness 0.8mm Flange 40 Thickness 1.0mm Flange 40 Thickness 1.0mm Flange 40 Thickness 1.0mm

601 - 800
801 - 1000 1001 - 1250

1251 - 1600 1601 - 2000 2001 - 2500

50x50x5mm

2000 Pa
Duct Dimension (mm)

OPTION -2-

Transverse Connections

Table 7B : HIGH PRESSURE 2000 Pa Positive (as per DW/142-144 Table 4)


Thick.
Straight
0 - 600
0.8 0.8 0.8 1.0 1.0 1.2 1.2
Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Pittsburgh Lock Pittsburgh Lock

Seam Fittings
Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock

Intermediate Reinforcement
Not Required Not Required Angle 30x30x3mm @ 600mm Angle 40x40x4mm @ 600mm Angle 50x50x5mm @ 600mm Angle 50x50x5mm @ 600mm Angle 60x60x5mm @ 600mm

C1 Drive Slip

C1 Drive Slip

C1 Hemmed S Slip

C2 Standing S H. 28.6mm

C3 Standing S H. 28.6mm

C4 Standing S H. 41.3mm

Companion Angles
25x25x3mm 25x25x3mm 25x25x3mm 30x30x3mm 40x40x4mm 40x40x4mm 50x50x5mm

Slide-on Flange

601 - 800
801 - 1000 1001 - 1250

1251 - 1600 1601 - 2000 2001 - 2500

2000 Pa AS PER PROJECT SPECS.


Table 7C : HIGH PRESSURE 2000 Pa Positive (as per DW/142-144 Table 4)
Duct Dimension (mm)

Transverse Connections

Thick.
Straight

Seam Fittings
Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock Pittsburgh Lock

Intermediate Reinforcement

C1 Drive Slip

C1 Drive Slip

C1 Hemmed S Slip

C2 Standing S H. 28.6mm

C3 Standing S H. 28.6mm

C4 Standing S H. 41.3mm

Companion Angles

Slide-on Flange

0 - 600

Grooved Corner Grooved Corner Grooved Corner Grooved Corner Grooved Corner Pittsburgh Lock Pittsburgh Lock

601 - 800
801 - 1000 1001 - 1250

1251 - 1600 1601 - 2000 2001 - 2500

* Materials Used for Transverse Connections :


- Galvanized Steel:(Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation. - Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L. * NOTE : 1 - Transverse Connectors are Based on 1200mm Spacing.
2 - Standard Straight Duct Length 1220mm. 3 - Companion Angle & Reinforcement are Made of Primer Painted Black Steel Angle. 24 Back to Index

II -Rectangular Ducts Welded


Longitudinal Seams & Connections
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Straight Ducts And Fittings With Flange Steel Angles

Flange Steel Angle Semi-continuous Welding

Duct Full Welded Seam

Continuous Welded

Flanged Cross Joint


Gasket or Sealant Semi-continuous Welding Duct

Continuous Welded

Flange Steel Angles Flange Steel Angle


Dimensions 25x25x3mm 30x30x3mm 40x40x4mm 50x50x5mm 60x60x6mm Bolts Diam. 8mm 8mm 8mm 10mm 12mm

- Fixing Bolts at Each Corner Intermediately Centered at 150mm.

* Materials Used for Ductworks & Connections :


- Carbon-Steel : Complying withASTM A 366/A 366M, Cold-rolled. - Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L. * NOTES: Kitchen Ventilation Systems : - Access Doors for Cleaning Must be Provided at Distance not Exceeding 3 Metres. As per: - DW 172 Page 36 - DW 144 Page 84
- Fire dampers must not be Used. - Internal Thermal or Acoustic Lining Should not be Used, and Turning Vanes Should be Avoided Wherever Possible. 25 Back to Index

II -Rectangular Ducts Welded


DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
As per: - SMACNA (2nd Edition-1995) See Pages 2.3/2.9/A.42/A.43 - DW/144 See Pages 55/57

DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Straight
Standard Length 1220mm

Taper

22.5 Max.

OW

W1 x D1 WxD

OD

W2 x D2

L1

A
Radius Bend

B
Master Bend

L1

Outer R

OD

W2 x D2

Inner R

WxD

C
Drop Cheek Bend
Can be Applied to any Angle

Minimum Throat Radius = 100mm DVACStandard Throat Radius = 150mm

W1 x D1

D
Trousers Piece
W2 x D2 O W3 x D2

W2 x D2

OD
R OW

W1 x D1

W1 x D1

E
* Materials Used for Ductworks & Connections :

F
- Carbon-Steel : Complying withASTM A 366/A 366M, Cold-rolled. - Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L. * NOTES: Kitchen Ventilation Systems : - Access Doors for Cleaning Must be Provided at Distance not Exceeding 3 Metres.

As per: - DW 172 Page 36 - DW 144 Page 84

- Fire dampers must not be Used. - Internal Thermal or Acoustic Lining Should not be Used, and Turning Vanes Should be Avoided Wherever Possible. 26 Back to Index

II -Rectangular Ducts Welded


DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
As per: - SMACNA (2nd Edition-1995) See Pages 2.8/2.9 - DW/144 See Pages 55/58

DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Angled Offset

Straight + 2 Branches
Width (W) mm Dim. (A) mm Up to 200 ,, 300 400 600 75 100 125 150 200

W2 x D2

15 Max.

,,

OW
WxD

,,

Over 600

W1 x D1

L1

A L1

G
Radius 2-Way Offset

H
Straight + Branch
Width (W) mm Dim. (A) mm Up to 200 ,, 300 400 600 75 100 125 150 200

W3 x D3

W2 x D2

W1 x D1

OW

,, ,,

Over 600

OD

W2 x D2

W1 x D1

I
Mitered Offset

L1

J
Radius Offset
Minimum Throat Radius = 100mm

L1

30 Max. WxD

OW

W1 x D

OW

E1 E2

W2 L1

K
* Materials Used for Ductworks & Connections :

L1

- Carbon-Steel : Complying withASTM A 366/A 366M, Cold-rolled. - Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L. * NOTES: Kitchen Ventilation Systems : - Access Doors for Cleaning Must be Provided at Distance not Exceeding 3 Metres. As per: - DW 172 Page 36 - DW 144 Page 84
- Fire dampers must not be Used. - Internal Thermal or Acoustic Lining Should not be Used, and Turning Vanes Should be Avoided Wherever Possible. 27 Back to Index

II -Rectangular Ducts Welded


DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
As per: - SMACNA (2nd Edition-1995) See Page 2.7 - DW/144 See Pages 52/55

DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Breeches Piece

3-Way Tee
W3

W2

W3 W2

W4

R1

R2 R1 W1 x D W1 x D

R2

M
Side Branch
W2

N
2-Way Breeches
W2 x D2

OD2
W3

OD3

W3 x D3

W1 x D

W1 x D1

O
Drop Cheek Breeches Piece

P
Access Door
Duct

Access Door
W2 x D2

OD2

OD3

W3 x D3

R1

R2

Bolt

W1 x D1

Q
* Materials Used for Ductworks & Connections :

Ensure that Cleaning Doors are not on the Underside of the Ductwork.

- Carbon-Steel : Complying withASTM A 366/A 366M, Cold-rolled. - Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L. * NOTES: Kitchen Ventilation Systems : - Access Doors for Cleaning Must be Provided at Distance not Exceeding 3 Metres. As per: - DW 172 Page 36 - DW 144 Page 84
- Fire dampers must not be Used. - Internal Thermal or Acoustic Lining Should not be Used, and Turning Vanes Should be Avoided Wherever Possible. 28 Back to Index

Rectangular Ducts
Tables: - Coating Mass (Weight) - Galvanized Thicknesses - Weight of Galvanized Steel

DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

As per: - DW/144 See Pages 93/97/98

DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

(Extract from BS.EN10142: 1991) Coating mass (Weight)


Minimum coating mass (including both sides)

Coating Designation
Triple spot test Single spot test

Suggested Applications (Provided by British Steel PLC)

g/m Zinc coatings (Z) Z100 Z200 Z275 Z350 Z450 Z600 Zinc-Iron alloy coatings (ZF) ZF100 Zf180

g/m

100 200 275 350 450 600

85 170 235 300 385 510

Light - for use where corrosion conditions are not severe and/or where forming operations preclude heavier coating. Standard Heavy Duty - for longer life relative to standard and light coatings

100 180

85 150

Iron-zinc alloys- alloyed coating of iron and zinc for easy painting and particularly resistance welding.

Note 1. The mass of zinc is not always equally distributed on both surfaces of the sheet. However, it can normally be expected that not less than 40% of the specified minimum coating mass, as determined by the single spot test, will be found on each surface.

Galvanized Thicknesses
Galvanized Steel *
Standard Thickness inch .0197 .0236 .0276 .0315 .0354 .0394 .0472 .0630 .0787 .0984 mm 0.5 0.6 0.7 0.8 0.9 1.0 1.2 1.6 2.0 2.5 Birmingham Gage BG 26 24 22 20 18 16 14 12 inch .0196 .0248 .0312 .0392 .0495 .0625 .0785 .0991

Weight of Galvanized Steel


Thickness mm 0.5 0.6 0.7 0.8 0.9 1.0 1.2 1.6 2.0 2.5 Weight per Square meter Kg 3.9213 4.7056 5.4898 6.2741 7.0584 7.8426 9.4111 12.5481 15.6852 19.6064

29

Back to Index

Remarks:

DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117


30 Back to Index

DVAC - DUCT VENTILATION AIR CONDITIONING Co. (W.L.L)


- Main Branch and Head Office
Industrial Area - Street 47 - Gate 6 Tel: +974 44500118 - 44500119 - Fax: +974 44500117

- 2nd Branch
Industrial Area - Street 46 - Gate 53 Tel: +974 44514381 - 44514188 - Fax: +974 44514052 Doha - State Of Qatar - P.O.Box: 55619 E-mail: info@dvac-duct.com - Web: www.dvac-duct.com

Back to Index