SM6
Modular units
Air insulated switchgear up to 36 kV
Your requirements
Safety
Operating safety through protection against electrical, mechanical and thermal effects of a fault (insulation of each compartment) All operations carried out from the front, door closed Voltage Presence Indicator System located on the front panel Position indicator linked to the devices physical position Protection in the event of internal arcing Interlocking devices Anti-reflex handles
Reliability
Type-tested solution which complies with the IEC62271-200 standard Design by the most accurate three-dimensional computer techniques Manufacturing & Testing according to ISO 9001:2000 quality standard
Simplicity
Easy installation - All cubicles with the same engineering dimensions On-site information retrieval Possibility of remote management Maintenance with power on (LSC2A), very simple Compartmentalization of MV parts (insulated partitions)
Our solutions
Schneider Electric has developed protection, monitoring and control solutions specifically dedicated to Medium Voltage networks for over 40 years. SM6 switchgear has been specifically designed on the basis of that extensive experience. It also incorporates some very new solutions, giving the best in terms of continuity of service and operators safety.
PE57150
A comprehensive solution
SM6 switchgear is fully compatible with PowerMeter metering units. Sepam multi-function protection relays - Protection - Measurements and diagnosis. VIP protection self powered relay for protection. SM6 swithchboards can thus be easily integrated into any monitoring and control system. - Local & remote indication and operation.
SM6, a truly professional solution! More than 1,300,000 cubicles installed world-wide.
SM6
General contents
Presentation
General characteristics
11
49
Connections
83
Installation
91
101
AMTED398078EN
AMTED398078EN
Presentation
Contents
The experience of a world leader The ranges advantages Protecting the environment A full range of services The references of a leader Quality assurance
4 5 6 7 8 9
AMTED398078EN
Presentation
The Schneider Electric experiences extends over forty years in factorybuilt cubicles and over thirty years in SF6 breaking technology for Medium Voltage switchgear. This experience means that today Schneider Electric can propose a complementary range: vacuum type circuit breaker cubicles up to 24 kV and standard or enhanced internal arc withstand cubicles to reinforce the safety of people according to the IEC standard. This gives you the advantage of unique experience, that of a world leader, with over 2,500 000 SF6 Medium Voltage units installed throughout the world. Putting this experience at your service and remaining attentive to your requirements is the spirit of active partnership that we want to develop in offering you the SM6. The modular SM6 is a range of harmonised cubicles equipped with SF6 or vacuum breaking technology switchgear with 30 years life span. These cubicles allow you to produce all your Medium Voltage substation requirements up to 36 kV by superposing their various functions.The result of in-depth analysis of your requirements, both now and in the future, SM6 cubicles mean that you can take advantage of all the features of both a modern and proven technology.
PM103194
1975: innovation Sulphur hexafluoride (SF6) is first used in an MV switch for an MV/LV transformer substation, with the VM6. 1989: experience Over 300,000 VM6 cubicles equipped networks throughout the world. 1991: innovation and experience Cumulated with the second generation of SM6 modular SF6 cubicles. 2013: a leading position With over 1,300,000 SM6 cubicles installed around the world, Schneider Electric consolidates its position as uncontested leader in the Medium Voltage field.
AMTED398078EN
Presentation
Upgradability
SM6, a comprehensive range
bb A comprehensive offer covering your present and future requirements bb A design adapted to the extension of your installations bb A catalogue of functions for all your applications bb A product designed to be in compliance with standards constraints bb Options to anticipate the control and monitoring of your installations.
Compactness
SM6, an optimised range
bb Compact units, with low increment cubicles bb Rationalised space requirement for switchboard installation bb Reduction of civil works costs bb Easy integration in factory-built outdoor substations for which the SM6 is particularly well designed.
Maintenance
SM6, a range with reduced maintenance
bb The active parts (breaking and earthing) are integrated in an SF6-filled, sealed for life unit bb The control mechanisms, are intented to function with reduced maintenance under normal operating conditions bb Enhanced electrical endurance when breaking.
Ease of installation
SM6, a simple range to incorporate
bb Reduced dimensions and weights bb Only one civil works layout bb A solution adapted to cable connection bb Simplified switchboard busbar design.
With the SM6, Schneider Electric proposes solutions for network management; the Sepam and VIP or relay ranges protect installations, providing continuity of electrical supply and reducing downtime.
AMTED398078EN
Presentation
Schneider Electric is committed to a long term environmental approach. As part of this, the SM6 has been designed to be environmentally friendly, notably in terms of the products recycleability. The materials used, both conductors and insulators, are identified in product environmental profile analysis and easily separable. It was performed in conformity with ISO 14040 Environmental management: life cycle assessment - principle and framework. At the end of its life, SM6 can be processed, recycled and its materials recovered in conformity with the draft European regulations on the end-of-life of electronic and electrical products, and in particular withoutany gas being released to the atmosphere nor any polluting fluids being discharged. SM6 is compliant with the RoHS directive. RoHS restricts the use of six hazardous materials in the manufacture of various types of electronic and electrical equipment.
61016N
8% 15% 2% 1%
7.8 % 8% 2% 0.2 %
The environmental management system adopted by Schneider Electric production sites that produce the SM6 have been assessed and judged to be in conformity with requirements in the ISO 14001 standard.
MT55145
01 ISO 140
AMTED398078EN
Presentation
Schneider Electric is capable of offering a full range of services either associated or not with the supply of the SM6 unit. To improve the quality of your electrical power: bb Network study, harmonics study, etc. bb Reactive energy compensation bb Consumption monitoring bb Optimisation of your electrical power supply contracts. To accompany the purchase and installation of your SM6 equipment: bb Adaptation of our equipment to provide a better response to your requirements bb On site assembly, testing and commissioning of your equipment bb Customised financing solutions bb Warranty extension bb Operator training. To accompany your installation throughout its life and upgrading your equipment: bb Upgrading your existing equipment: functional adaptation, control motorisation, renovation of protections units, etc. bb On site work bb Supply of replacement parts bb Maintenance contracts bb End of life recycling. Fore more information on all the services proposed by Schneider Electric, please contact your Schneider Electric Sales Office.
PE57151
61052N
AMTED398078EN
Presentation
PE57234
Asia/Middle East
bb Canal Electrical Distribution Company, Egypt bb General Motors Holden, Australia bb Pasteur Institute, Cambodia bb Tian he City, China bb Sanya Airport, China bb Bank of China, Beijing, Jv Yanta, China bb Plaza Hotel, Jakarta, Indonesia bb Bali Airport, Indonesia bb Wakasa Control Center, Japan bb Otaru Shopping center, Japan bb New City of Muang, Thong Than, Kanjanapas, Thailand bb Danang and Quinhon Airport, Vanad, Vietnam bb British Embassy, Oman bb KBF Palace Riyadh, Saudi Arabia bb Raka Stadium, Saudi Arabia bb Bilkent University, Turkey bb TADCO, BABOIL development, United Arab Emirates bb Melbourne Tunnel City Link, Australia bb Campus KSU Qassim Riyad, Saudi Arabia
Africa
bb ONAFEX, Hilton Hotel, Algeria bb Yaounde University, Cameroon bb Karoua Airport, Cameroon bb Libreville Airport, Gabon bb Ivarto Hospital, CORIF, Madagascar bb Central Bank of Abuja, ADEFEMI, Nigeria bb OCI Dakar, Oger international, CGE, Senegal bb Bamburi cement Ltd, Kenya bb Ivory Electricity Company, Ivory Coast bb Exxon, New Headquarters, Angola
South America/Pacific
bb Lamentin Airport, CCIM, Martinique bb Space Centre, Kourou, Guyana bb Mexico City Underground System, Mexico bb Santiago Underground System, Chile bb Cohiba Hotel, Havana, Cuba bb Iberostar Hotel, Bavaro, Dominican Republic bb Aluminio Argentino Saic SA, Argentina bb Michelin Campo Grande, Rio de Janeiro, Brazil bb TIM Data Center, So Paulo, Brazil bb Light Rio de Janeiro, Brazil bb Hospital Oswaldo Cruz, So Paulo, Brazil
Europe
bb Stade de France, Paris, France bb EDF, France bb Eurotunnel, France bb Nestl company headquarters, France bb TLM Terminal , Folkestone, Great Britain bb Zaventem Airport, Belgium bb Krediebank Computer Centre, Belgium bb Bucarest Pumping station, Romania bb Prague Airport, Czech Republic bb Philipp Morris St Petersburg, Russia bb Kremlin Moscow, Russia bb Madrid airport, Spain bb Dacia Renault, Romania bb Lafarge cement Cirkovic, Czech Republic bb Caterpillar St Petersburg, Russia bb Ikea Kazan, Russia bb Barajas airport, Spain bb Coca-cola Zurich, Switzerland
AMTED398078EN
Presentation
Quality assurance
A major advantage
Schneider Electric has integrated a functional organisation into each of its units. The main mission of this organisation is to check the quality and the compliance with standards. This procedure is: bb Uniform throughout all departments bb Recognised by many customers and approved organisations. But it is above all its strict application that has enabled recognition to be obtained by an independent organisation: The French Quality Assurance Association (FQAA).
The quality system for the design and manufacture of SM6 units has been certified in conformity with the requirements of the ISO 9001: 2000 quality assurance model.
MT55054 MT55055
ISO
900 1
ISO
9002
61002N
During manufacture, each SM6 is subject to systematic routine testing which aims to check the quality and conformity:
The results obtained are written and reported on the test certificate for each device by the quality control department.
61003N
As result of Schneider Electric quality assurance system, SM6 has negligible Mean Down Time (MDT) in comparison to the Mean Up Time (MUT), thus Mean Operating Time Between Failures (MTBF) is as similar as to the MTTF. bb MTTF (cumulative) = 3890 years for SM6-24 bb MTTF (cumulative) = 6259 years for SM6-36.
AMTED398078EN
10
AMTED398078EN
General characteristics
Contents
Field of application Units for switching function Units for protection function Units for metering function Units for other functions Operating conditions Standards Main characteristics Factory-built cubicles description Compartments description Safety of people
By switchgear By operating mechanism safety By internal arc protection
12 14 15 18 19 20 21 22 24 26 28 28 30 31 32 32 33 34 37 39 40 40 43 43 44 45 46 47
AMTED398078EN
11
General characteristics
Field of application
The SM6 is made up of modular units containing fixed, disconnectable or withdrawable metal-enclosed switchgear, using sulphur hexafluoride (SF6) or vacuum: bb Switch-disconnector bb SF1, SFset or Evolis circuit breaker bb Vacuum contactor bb Disconnector. SM6 units are used for the MV section in MV/LV transformer substations in public distribution systems and MV consumer or distribution substations up to 36 kV.
DM2
QM
PM
IM
Substation GAM2 QM
Other standards
IM
MT55146
Outgoing line toward other ring substations Incoming line of the main distribution switchboard
12
AMTED398078EN
General characteristics
Field of application
GBC-B
QM QM IM
IM
GBC-B
DM1-A
Incoming line
ATS
Incoming line
Below is the list of SM6 units used in MV/LV transformer substations and industrial distribution substations: bb IM, IMC, IMB switch bb PM fused switch bb QM, QMC, QMB fuse-switch combination bb CVM contactor and contactor with fuses bb DM1-A, DM1-D, DM1-S single-isolation disconnectable SF6 type circuit breaker bb DMV-A, DMV-D, DMV-S single-isolation vacuum type circuit breaker frontal bb DMVL-A, DMVL-D single-isolation disconnectable vacuum type circuit breaker lateral bb DM1-W, DM1-Z withdrawable single-isolation SF6 type circuit breaker for SM6-24 bb DM2 double-isolation disconnectable SF6 type circuit breaker bb CM, CM2 voltage transformers bb GBC-A, GBC-B current and/or voltage measurements bb NSM-cables for main incoming and standby bb NSM-busbars for main incoming and cables for standby bb GIM intermediate bus unit bb GEM extension unit bb GBM connection unit bb GAM2, GAM incoming cable connection unit bb SM disconnector bb TM MV/LV transformer unit for auxiliaries bb Other units, consult us bb Special function EMB busbar earthing only for SM6-24.
Unit definitions
Standby source
ATS
Incoming line
AMTED398078EN
13
General characteristics
Switching
See in details on page
DE59671 DE59672 DE59673
50
IMB Switch unit with earthing disconnector right or left outgoing line SM6-24: 375 mm SM6-36: 750 mm
51
NSM-cables Cables power supply for main incoming line and standby line SM6-24: 750 mm
NSM-busbars Busbars power supply for main incoming line on right or left and cables for standby line SM6-24: 750 mm
14
AMTED398078EN
General characteristics
Fuse-switch
DE59674 DE59675 DE59676
52
QMB Fuse-switch combination unit right or left outgoing line SM6-24: 375 mm SM6-36: 750 mm
53
SF6 circuit-breaker
DE59678 DE59679
54
DM1-A Single-isolation, disconnectable circuit breaker unit SM6-24: 750 mm SM6-36: 1000 mm
DM1-D Single-isolation, disconnectable circuit breaker unit right or left outgoing line SM6-24: 750 mm SM6-36: 1000 mm
AMTED398078EN
15
General characteristics
SF6 circuit-breaker
See in details on page
DE59681 DE53487 DE53490
55 56
DM1-S Single-isolation, disconnectable circuit breaker unit with autonomous protection SM6-24: 750 mm
DM1-Z Withdrawable single-isolation circuit breaker unit right outgoing line SM6-24: 750 mm
DE59680
55
DM2 Double-isolation, disconnectable circuit breaker unit right or left outgoing line SM6-24: 750 mm SM6-36: 1500 mm
Vacuum circuit-breaker
DE53491 DE53492 DE53493
57
DMV-D Single-isolation circuit breaker unit right outgoing line SM6-24: 625 mm
DMV-S Single-isolation circuit breaker unit with autonomous protection SM6-24: 625 mm
16
AMTED398078EN
General characteristics
Vacuum circuit-breaker
See in details on page
DE53485 DE59694
58
DMVL-D Single-isolation, disconnectable circuit breaker unit right outgoing line SM6-24: 750 mm
59
AMTED398078EN
17
General characteristics
DE59863
60
CM Voltage transformers for mains with earthed neutral system SM6-24: 375 mm SM6-36: 750 mm
DE53496 DE53497
DE59684
CM2 Voltage transformers for mains with insulated neutral system SM6-24: 500 mm SM6-36: 750 mm
61
GBC-A Current and/or voltage measurement unit right or left outgoing line SM6-24: 750 mm SM6-36: 750 mm
GBC-B Current and/or voltage measurement unit SM6-24: 750 mm SM6-36: 750 mm
18
AMTED398078EN
General characteristics
DE59686
DE53498
62
GBM Connection unit right or left outgoing line SM6-24: 375 mm SM6-36: 750 mm
DE59687 DE59688
DE59685
62 63
GAM Incoming cable-connection unit with earthing SM6-24: 500 mm SM6-36: 750 mm
DE53504
DE53498
DE59689
64
DE59690
* For other switchboard extension (Modularc 36, Unifluorc or Fluokit M24), please consult us.
AMTED398078EN
19
General characteristics
Operating conditions
In addition to its technical characteristics, SM6 meets requirements concerning safety of life and property as well as ease of installation, operation and protecting the environment.
PE57152
SM6 units are designed for indoor installations. Their compact dimensions are: bb 375 to 1500 mm width bb 1600 to 2250 mm height bb 840 to 1400 mm depth this makes for easy installation in small rooms or prefabricated substations. Cables are connected via the front. All control functions are centralised on a front plate, thus simplifying operation. The units may be equipped with a number of accessories (relays, toroids, instrument transformers, surge arrester, control and monitoring, etc.).
bb Ambient air temperature: 1) less than or equal to 40C 2) less than or equal to 35C on average over 24 hours 3) greater or equal to 5C. bb Altitude 1) less than or equal to 1000 m 2) above 1000 m, a derating coefficient is applied (please consult us). bb Solar radiation 1) no solar radiation influence is permitted. bb Ambient air pollution 1) no significant pollution by dust, smoke, corrosive and/or flammable gases, vapours or salt. bb Humidity 1) average relative humidity over a 24 hour period, less than or equal to 95% 2) average relative humidity over a 1 month period, less than or equal to 90% 3) average vapor pressure over a 24 hour period, less than or equal to 2.2 kPa 4) average vapor pressure over a 1 month period, less than or equal to 1.8 kPa. For these conditions, condensation may occasionally occur. Condensation can be expected where sudden temperature changes occur in periods of high humidity. To withstand the effects of high humidity and condensation, such as breakdown of insulation, please pay attention on Civil Engineering recommendations for design of the building or housing, by suitable ventilation and installation. Severe operating conditions (please consult us).
20
AMTED398078EN
General characteristics
Standards
SM6 units meet all the following standards and specifications: b IEC standards b UTE standards for SM6-24 b EDF specifications for SM6-24.
bb IEC standards 62271-200 High-voltage switchgear and controlgear - Part 200: A.C. metalenclosed switchgear and controlgear for rated voltage above 1 kV and up to and including 52 kV. High-voltage switchgear and controlgear - Part 1: Common specifications. High voltage switches - Part 1: switches for rated voltages above 1 kV and less or equal to 52 kV. High-voltage switchgear and controlgear - Part 105: High voltage alternating current switch-fuse combinations. Electrical relays. High-voltage switchgear and controlgear - Part 100: High-voltage alternating current circuit breakers. High-voltage switchgear and controlgear - Part 102: High-voltage alternating current disconnectors and earthing switches. Instrument transformers - Part 1: Current transformers. Instrument transformers - Part 2: Voltage transformers. Instrument transformers - Part 8: Low Power Current Transducers. High-voltage prefabricated switchgear and controlgear assemblies Voltage presence indicating systems. High-voltage switchgear and controlgear - Part 304: Design classes for indoor enclosed switchgear and controlgear for rated voltages above 1 kV up to and including 52 kV to be used in severe climatic conditions. Consumer substation installed inside a building and fed by a second category voltage public distribution system. High voltage electrical installations requirements. High voltage switches for rated voltage above 1 kV and less than 52 kV.
62271-1 62271-103 62271-105 60255 62271-100 62271-102 61869-2 61869-3 60044-8 62271-206 62271-304
NFC 64.160. Alternating current disconnectors and earthing switches EDF specifications for 24 kV HN 64-S-41 HN 64-S-43 A.C. metal-enclosed swichgear and controlgear for rated voltages above 1 kV and up to and including 24 kV. Electrical independent-operating mechanism for switch 24 kV - 400 A.
AMTED398078EN
21
General characteristics
Main characteristics
PE57150
The hereunder values are for working temperatures from -5C up to +40C and for a setting up at an altitude below 1000 m.
Electrical characteristics
Rated voltage Ur Ud Ud Up Up kV 50/60 Hz, 1 min (kV rms) 50/60 Hz, 1 min (kV rms) 1.2/50 s (kV peak) 1.2/50 s (kV peak) A A Ir Ik/tk (1) A kA/1 s 25 20 (2) 16 12.5 Making capacity (50 Hz) Ima kA 62.5 50 40 31.25 7.2 20 23 60 70 16 31.5 400 - 630 -1250 630 - 1250 630 - 1250 630 - 1250 400 - 630 - 1250 630 630 630 400 - 630 630 - 800 (3) 630 - 800 (3) 25 25 6.3 25 25 20 DM1-S DM1-Z DM2 Vacuum circuit breaker range DMV-A, DMV-D, DMV-S DMVL-A DMVL-D NA: Non Available (1) 3 phases (2) In 20 kA/3 s, consult us (3) In 800 A, consult us. (4) NA for SM6-36 kA kA kA 25 20 25 630-1250 630 630 NA NA NA kA kA 25 25 20 25 630-1250 630-1250 630 1250 630 630 1250 NA NA NA NA 1250 20 630 630 NA 20 20 NA 630-1250 50 630-1250 1250 12 28 32 75 85 17.5 38 45 95 110 24 50 60 125 145 36 70 80 170 195
Insulation level
Insulation Isolation Insulation Isolation
Breaking capacity
Transformer off load Cables off load Rated current Short-time withstand current
22
AMTED398078EN
General characteristics
Main characteristics
PE57150
Endurance
Units
Units IM, IMC, IMB, PM, QM (5), QMC (5), QMB (5), NSM-cables, NSM-busbars CVM Disconnector Mechanical endurance IEC 62271-103 1000 operations class M1 IEC 62271-102 1000 operations IEC 60470 250000 breaks at Ir Electrical endurance IEC 62271-103 100 breaks at Ir, p.f. = 0.7, class E3
Vacuum contactor IEC 60470 2500000 operations 250000 with mechanical latching SF6 circuit breaker range DM1-A, DM1-D, DM1-W, DM1-Z, DM1-S, DM2 Disconnector IEC 62271-102 1000 operations
IEC 62271-100 30 breaks at 12.5 kA for SM6-24 25 breaks at 25 kA for SM6-24 40 breaks at 16 kA for SM6-36 15 breaks at 25 kA for SM6-36 10000 breaks at Ir, p.f. = 0.7, class E2 O - 0.3s - CO - 15s - CO O - 0.3s - CO - 3mn O - 3mn - CO - 3mn - CO IEC 62271-103 100 breaks at Ir, p.f. = 0.7, class E3 IEC 62271-100 100 breaks at 25kA for SM6-24 10000 breaks at Ir, p.f. = 0.7, class E2
Operating sequence Vacuum circuit breaker range DMV-A, DMV-D, DMV-S Switch Evolis circuit breaker DMVL-A DMVL-D Disconnector Evolis circuit breaker IEC 62271-103 1000 operations class M1 IEC 62271-100 10000 operations class M2 IEC 62271-102 1000 operations IEC 62271-100 10000 operations class M2
IEC 62271-100 100 breaks at 16kA for SM6-24 100 breaks at 25kA for SM6-24 10000 breaks at Ir, p.f. = 0.7, class E2
(5) As per recommendation IEC 62271-105, three breakings at p.f. = 0.2 800 A under 36 kV; 1400 A under 24 kV; 1730 A under 12 kV; 2600 A under 5.5 kV.
Internal arc withstand (in accordance with IEC 62271-200): bb SM6-24: vv 12.5 kA 1s, IAC: A-FLR & IAC: A-FL vv 16 kA 1s, IAC: A-FLR & IAC: A-FL vv 20 kA 1s, IAC: A-FLR & IAC: A-FL bb SM6-36: vv 16 kA 1s, IAC: A-FL. Protection index: bb Classes: PI (insulating partition) bb Loss of service continuity classes: LSC2A (LSC1 for metering functions) bb Units in switchboard: IP3X bb Between compartments: IP2X for SM6-24, IP2XC for SM6-36 bb Cubicle: IK08 for SM6-24, IK07 for SM6-36. Electro-magnetic compatibility: bb Relays: 4 kV withstand capacity, as per recommendation IEC 60801.4 bb Compartments: vv electrical field: -- 40 dB attenuation at 100 MHz -- 20 dB attenuation at 200 MHz vv magnetic field: 20 dB attenuation below 30 MHz. Temperatures: The cubicles must be stored and installed in a dry area free from dust and with limited temperature variations. bb For stocking: from 40C to +70C bb For working: from 5C to +40C bb Other temperatures, consult us.
AMTED398078EN
23
General characteristics
DE58646
2 busbars: all in the same horizontal plane, thus enabling later switchboard 3 connection: accessible through front, connection to the lower switch-disconnector and earthing switch terminals (IM cubicles) or the lower fuse-holders (PM and QM cubicles). This compartment is also equipped with an earthing switch downstream from the MV fuses for the protection units. 4 operating mechanism: contains the elements used to operate the switchdisconnector and earthing switch and actuate the corresponding indications (positive break).
5 low voltage: installation of a terminal block (if motor option installed), LV fuses
and compact relay devices. If more space is required, an additional enclosure may be added on top of the cubicle. Options: please, refer to the chapter Characteristics of the functional units.
DE58647
2 busbars: all in the same horizontal plane, thus enabling later switchboard 3 connection and switchgear: accessible through front, connection to the downstream
terminals of the circuit breaker. Two circuit breaker offers are possible: bb SF1: combined with an electronic relay and standard sensors (with or without an auxiliary power supply bb SFset: autonomous set equipped with an electronic protection system and special sensors (requiring no auxiliary power supply). the circuit breaker and the earthing switch and actuate the corresponding indications. boxes. If more space is required, an additional enclosure may be added on top of the cubicle. Options: please, refer to the chapter Characteristics of the functional units.
4 operating mechanism: contains the elements used to operate the disconnector(s), 5 low voltage: installation of compact relay devices (Statimax) and test terminal
24
AMTED398078EN
General characteristics
DE58648
2 1
1 switchgear: load break switch and earthing switch(es), in enclosure filled with 5 4
SF6 and satisfying and one vacuum circuit breaker, sealed pressure system requirements. extensions and connection to existing equipment.
2 busbars: all in the same horizontal plane, thus enabling later switchboard 3 connection and switchgear: accessible through front, connection to the
downstream terminals of the circuit breaker. bb Evolis: device associated with an electronic relay and standard sensors (with or without auxiliary source).
4 operating mechanism: contains the elements used to operate the disconnector(s), the circuit breaker and the earthing switch and actuate the corresponding indications. 5 low voltage: installation of compact relay devices (VIP) and test terminal boxes.
Options: please, refer to the chapter Characteristics of the functional units.
DE58649
If more space is required, an additional enclosure may be added on top of the cubicle.
2 busbars: all in the same horizontal plane, thus enabling later switchboard 3 connection and switchgear: accessible through front, connection to the
downstream terminals of the circuit breaker. bb Evolis: device associated with an electronic relay and standard sensors (with or without auxiliary source).
4 operating mechanism: contains the elements used to operate the disconnector(s), the circuit breaker and the earthing switch and actuate the corresponding indications. 5 low voltage: installation of compact relay devices (VIP) and test terminal boxes.
Options: please, refer to the chapter Characteristics of the functional units. If more space is required, an additional enclosure may be added on top of the cubicle.
Contactor cubicles
DE58650
2 1
2 busbars: all in the same horizontal plane, thus enabling later switchboard 5 4 3 connection and switchgear: accessible through front.
This compartment is also equipped with an earthing switch downstream. The contactor may be equipped with fuses. 2 types may be used: bb Vacuum with magnetic holding bb Vacuum with mechanical latching. the disconnector(s), the contactor and the earthing switch and actuate the corresponding indications. With basic equipment, an additional enclosure is added on top of the cubicle. Options: please, refer to the chapter Characteristics of the functional units.
5 low voltage: installation of compact relay devices and test terminal boxes. 4
AMTED398078EN
25
General characteristics
Compartments description
DE53507
61007N
Busbar compartment
The three insulated busbars are parallel-mounted. Connection is made to the upper pads of the enclosure using a field distributor with integrated captive screws. Ratings 400 (for SM6-24 only) - 630 - 1250 A.
DE53508
61006N
Switch compartment
This compartment is separated from the busbar compartment and the connection compartment by the enclosure surrounding the switch, the disconnector and the earthing switch.
DE57172
See in fonctional units characteristics chapter for each unit allowable section. The earthing switch must be closed before the cubicle may be accessed. The reduced depth of the cubicle makes for easy connection of all phases. A stud incorporated in the field distributor makes it possible to position and secure the cable-end lug with a single hand.
DE53510
26
AMTED398078EN
General characteristics
Compartments description
DE57173
PE57230
Operating-mechanism cover
These covers contain the various operating functions for the: bb switch and earthing switch bb disconnector(s) bb circuit breaker bb contactor and the voltage presence indicator. The operating-mechanism cover may be accessed with the cables and busbars energised and without isolating the substation. It also enables easy installation of padlocks, locks and standard LV accessories (auxiliary contacts, trip units, motors, etc.).
PE57153
450 mm
C B A
A - LV cover h = 2250 mm
PE58270
AB
1500 mm 1615 mm
AMTED398078EN
27
General characteristics
Safety of people
By switchgear
61010N
Switch-disconnector for 24 kV
PE57226
Switch-disconnector for 36 kV
Closed position
Open position
Earth position
bb Insensitivity to the environment vv parts are designed in order to obtain optimum electrical field distribution. vv the metallic structure of cubicles is designed to withstand and aggressive environment and to make it impossible to access any energised part when in operation.
28
AMTED398078EN
General characteristics
Safety of people
By switchgear
61012N
61058N
Contacts closed
Precompression
Arcing period
Contacts open
PE50798
bb Vacuum tightness Vacuum contactor comprises three separate poles fixed on a structure supporting the control mechanism. Each pole encloses all of the active parts in an insulating enclosure under vacuum and its vacuum tightness is checked in the factory.
AMTED398078EN
29
General characteristics
Safety of people
PE57230
bb Switchgear status indicator: Fitted directly to the drive shaft, these give a definite indication of the contacts position. (appendix A of standard IEC 62271-102). bb Operating lever: This is designed with an anti-reflex device that stops any attempt to re-open the device immediately after closing the switch or the earthing disconnector. bb Locking device: Between one and three padlocks enable the following to be locked: v access to the switching shaft of the switch or the circuit breaker, v access to the switching shaft of the earthing disconnector, v operating of the opening release push-button.
Mechanical and electrical controls are side by side on the front fascia, on a panel including the schematic diagram indicating the devices status (closed, open, earthed): bb Closed: the drive shaft is operated via a quick acting mechanism, independent of the operator. No energy is stored in the switch, apart from when switching operations are taking place. For combined switch fuses, the opening mechanism is armed at the same time as the contacts are closed. bb Opening: the switch is opened using the same quick acting mechanism, operated in the opposite direction. For circuit breakers and the combined switch fuses, opening is controlled by: vv a push-button, vv a fault. bb Earthing: a specific control shaft enables the opening or closing of the earthing contacts. Access to this shaft is blocked by a cover that can be slid back if the switch is open but which remains locked in place if it is closed.
PE57231
The position of main contacts is clearly visible from the front of the cubicle through the window.
PE57166
Despite SM6 switch is sealed pressure system and has open and close capacity on rated current at 0 bar relative pressure SF6, to insure you about the internal pressure, we propose on request before sale or on site by after-sales either a pressure switch or an analog manometer on the switch. These devices are both fitted without any alteration on the switch, they are temperature compensated and compatible with visibility of main contacts if requested.
PE56366
VPIS complies with 62271-206 standard allowing to indicate the voltage presence on each phase with LEDs. Designed for harsh environments so that to guarantee high reliability in MV/LV susbstations worldwide. Exits in Voltage Output version to provide voltage presence information to VD23 voltage presence relay.
30
AMTED398078EN
General characteristics
Safety of people
Standard IEC 62271-200 appendix A indicates a method for testing switchgear in metal enclosures under internal arc conditions. The aim of this test is to show that an operator situated in front of a switchboard would be protected against the effects of an internal fault.
To enhance the safety of people, it is desirable to provide as high a degree of protection as possible by evacuating the effects of internal arc using: bb Evacuation systems which direct gases towards the top or the bottom of the switchboard enabling over pressure to be limited in the case of an internal fault in the compartments bb Channelling and evacuating hot gases towards an external area, which is not hazardous for the operator bb Materials which are non-inflammable in the cubicles bb Reinforced panels.
Consequently:
The SM6 is designed to offer a good level of safety bb Control of the architecture: vv compartment type enclosure. bb Technological control: vv electrotechnical: modelling of electrical fields, vv mechanical: parts produced using CAD systems. bb Use of reliable components: vv choice of materials, vv earthing switch with closing capacity. bb Devices for total operating safety: vv voltage presence indicator on the front face, vv natural reliable interlocking, vv locking using keys or padlocks.
DE59732
Example of installation of an SM6 switchboard installed against the wall downwards exhaust 12.5 kA 1s and 16 kA 1s, IAC: A-FL: 3-sides internal arc protection
DE59734
Example of installation of an SM6-24 switchboard installed in the middle of a room downwards exhaust 16 kA 1s, IAC: A-FLR: 4-sides internal arc protection
SM6 proposes several options to install a standard internal arc withstand switchboard
DE57174
bb 3-sides internal arc protection IAC: A-FL, 12,5 kA 1s, 16 kA 1s and 20 kA 1s for SM6-24 and 16 kA 1s for SM6-36. SM6 switchboard positioned against the wall, access to the rear of the cubicles is impossible, internal arc protection on three sides is sufficient. bb 4-sides internal arc protection IAC: A-FLR, 12,5 kA 1s, 16 kA 1s and 20 kA 1s for SM6-24. For SM6 switchboards installed in the middle of a room, 4-sides internal arc protection is necessary in order to protect an operator moving around the switchboard. bb Choice of exhaust: (Installation requirements manual to be considered) vv downwards exhaust Civil engineering with an adequate volume is necessary. vv upwards exhaust for SM6-24 A ceiling height greater or equal than 2150 mm is necessary, duct at the right or left side of the cubicle (not supplied).
Example of installation of an SM6-24 switchboard installed in the middle of a room upwards exhaust 16 kA 1s and 20 kA 1s, IAC: A-FLR: 4-sides internal arc protection
AMTED398078EN
31
General characteristics
Easergy T200 S is a simplified MV substation control unit for secondary distribution networks enabling remote control of one or two MV substation switches. T200 S, a version of the T200 unit, is integrated in the SM6 cubicle LV control cabinet. It is limited to control 2 switches. It is intended for remote control applications for source transfer switching and back up generator set switching in NSM cubicle. Easergy T200 S a multifunctional plug and play interface which integrates all functions required for remote monitoring and control of MV substations: bb Acquisition of various data types: switch position, fault detectors, current values, etc. bb Transmission of opening and closing orders to the switches bb Exchange with the control center. Particularly used during network incidents, Easergy T200 S has proven its reliability and availability to be able to operate the switchgear at all times. It is easy to implement and operate.
Easergy T200 S is installed in the low voltage control cabinet of NSM cubicles for remote control of one or two switches. Easergy notably enables source transfer switching between two switches. It has a simple panel for local operation to manage electrical controls (local/remote switch) and to display switchgear status information. It integrates a fault current detector (overcurrent and zero sequence current) with detection thresholds configurable channel by channel (threshold and fault duration).
Control command
PE15078
Integrated in the low voltage control cabinet of an MV-equipped cubicle, it is ready to connect to the data transmission system. Easergy T200 S has been subject to severe tests on its resistance to MV electrical constraints. A back-up power supply guarantees several hours continuity of service for the electronic devices, motorization and MV switchgear. Current transformers are of split core type for easier installation.
Easergy T200 S supplies the following standard protocols: bb Modbus serial and IP bb DPN3 serial and IP bb IEC 870-5-101/104. Data transmission system standards are: RS232, RS485, PSTN, FSK, FFSK, GSM/GPRS. Other systems are available on request, the radio frequency emitter/receiver is not supplied.
32
AMTED398078EN
General characteristics
PE56311
Easergy T200 I is a plug and play or multifunction interface that integrates all the functional units necessary for remote supervision and control of the SM6: bb Acquisition of the different types of information: switch position, fault detectors, current values... bb Transmission of switch open/close orders bb Exchanges with the control center. Required particularly during outages in the network, Easergy T200 I is of proven reliability and availability, being able to ensure switchgear operation at any moment. It is simple to set up and to operate.
bb Easergy T200 I is designed to be connected directly to the MV switchgear, without requiring a special converter. bb It has a simple front plate for local operation, which allows management of electrical rating mechanisms (local/remote switch) and display of information concerning switchgear status. bb It has an integrated MV network fault current detection system (overcurrent and zero sequence) with detection set points that can be configured channel by channel (current value and fault current duration). bb Easergy T200 I has undergone severe MV electrical stress withstand tests. bb It is a backed up power supply which guarantees continuity of service for several hours in case of loss of the auxiliary source, and supplies power to the Easergy T200 I and the MV switchgear motor mechanisms. bb Ready to plug vv Easergy T200 I is delivered with a kit that makes it easy to connect the motor mechanisms and collect measurements. vv the connectors are polarized to avoid any errors during installation or maintenance interventions. vv current measurement acquisition sensors are of the split type, to facilitate their installation. vv works with 24 Vdc and 48 Vdc motor units.
Polarized connectors
Easergy T200 I supplies the following standard protocols: bb Modbus serial and IP bb DPN3 serial and IP bb IEC 870-5-101/104. Data transmission system standards are: RS232, RS485, PSTN, FSK, FFSK, GSM/GPRS. Other systems are available on request, the radio frequency emitter/receiver is not supplied.
PE57787
VD23 provides accurate information of presence or absence of voltage. Associated with VPIS-Voltage Output, VD23 is typically used in critical power and safety applications.
VD23
Various combinations of voltage detection are possible: bb 3 Ph-N and residual voltage: V1 + V2 + V3 + V0 bb 3 Ph-N or Ph-Ph voltage: V1 + V2 + V3 or U12 + U13 + U23 bb 1 Ph-N or Ph-Ph or residual voltage: V1, V2, V3, U12, U13, U23, V0. VD23 can display the MV network voltage (in % of service voltage), activate the relay output R1 to monitor a loss of voltage on 1 phase at least and active the relay output R2 to monitor a presence of voltage on 1 phase at least. bb Auxilary power supply: from 24 to 48 Vdc bb Assembly: compact DIN format, mounted in the same place as fault passage indicator (format DIN, integrated in switchgear), terminal connexion fitted with VPIS-Voltage Output bb Compatible with all neutral earthing systems.
AMTED398078EN
33
General characteristics
DE40552EN
Voltage drop
b Switches can be controlled manually in the following circumstances: v automation system switched off v switch in local mode.
Sectionaliser (SEC)
Time b Configurable parameters: v Number of faults: from 1 to 4 v Execution time: from 20 s to 4 mins configurable in 5 s steps v Automation system valid/invalid.
DE59320EN
The sectionaliser automation system opens the switch after a predefined number of faults (1 to 4) during the voltage dip in the reclosing cycle of the top circuit breaker. b The automation system counts the number of times a fault current followed by a voltage loss is detected. It sends an open order if: v the switch is closed v the fault has disappeared v the MV supply is absent. b The automation system is reset at the end of the execution time delay.
Vn O Vn O C O C O
SW2 voltage
SW1 voltage
T1
TR
SW1 T1 TR
TR
The automatic transfer system performs automatic control and management of sources in the MV secondary distribution network. Two possible versions for ATS: Network ATS version: control of two MV network channels. The network ATS automatic transfer system requires use of the VD23 relay for detection of voltage presence/absence. Generator ATS version: control of one network channel and one generating set channel (not available on T200 E). Note: ATS automatic transfer system is available only on channels 1 and 2 of each CONTROL module. Generator ATS automatic transfer system is available only on the first CONTROL module (channels 1 to 4).
SW1
TR
SW2
SW2
Network ATS - Semi-Auto Mode (without paralleling upon automatic return) TR: switch response time Vn O C O C O T1 TR SW1 T2 TR SW1 voltage
Operating modes
TR
The operating mode is selected from the T200 Web server. Mode SW1VSW2 or SW2VSW1 (or SWVSWG if Generator ATS): Automatic transfer system executes only one changeover from the priority channel to the backup channel. Automatic transfer system then remains on that channel. Semi-Auto mode SW1XVSW2 (or SWXVSWG if Generator ATS): In the event of a voltage loss on the active channel, automatic transfer system switches to the other channel after a time delay T1. Automatic transfer system executes no return, except in case of voltage loss on the new active channel. Auto SW1 or Auto SW2 mode (or Auto SW if Generator ATS): After a changeover, return to the priority channel occurs if the MV voltage on that channel is restored. The channel that has priority can be defined according to the state of a dedicated digital input.
Tg2
TR
SW2
Network ATS - Auto Mode SW1 (with paralleling upon automatic return) TR: switch response time
DE59321EN
Vn 0 1 0 Vg 0 C O C O C O
Changeover sequences:
TR
SW
Network ATS: in the event of voltage loss on the normal channel, changeover involves opening the normal channel after time delay T1 and then closing the backup channel. Note: in Auto mode, the sequence of return to the normal channel depends on configuration of the Paralleling upon auto return option (see below). Generator ATS: in the event of voltage loss on the network channel, changeover involves sending the order for opening the network channel and at the same time the Generator start-up order, after time delay T1. The remainder of the changeover sequence depends on the management of Generator channel closing (configurable option): bb Case of Generator channel closing after start-up order: After the Generator start-up order, the closing order is given to the Generator channel, without waiting until the Generator is actually started. bb Case of Generator closing after Generator power on: The Generator channel closing order is sent only when Generator voltage is detected.
TR TR
T2 TR T2 TR
SWG SWG
Generator ATS - Auto SW mode (Without paralleling upon Auto return) TR: Switch response time Tg1: Generator starting time (maximum 60 s) Tg2: Generator stopping time Case : Generator channel closing after Generator power on (configurable option) Case : Generator channel closing after Generator start-up command (configurable option)
34
AMTED398078EN
DE56654
General characteristics
Configurable parameters: bb Automatic transfer system ON/OFF bb Operating mode: Semi-Auto, Auto SW1, Auto SW2, SW1 > SW2, SW2 > SW1 bb T1: 0 ms to 2 min. in increments of 100 ms bb T2: 0 s to 30 min. in increments of 5 s bb Disabling/enabling transfer upon fault detection: bb Choice of voltage presence detection: DI4 or VD23 bb Channel connected to generator: SW1 or SW2 bb Type of automatic transfer system: Network ATS or Generator ATS bb Manual control enabled/disabled if ATS in operation bb Paralleling enabled/disabled in auto and/or manual mode bb Choice of type of changeover to Generator: immediately or after detection of Generator power on
A software-configurable option allows the automatic transfer system to disable or enable paralleling of the channels upon automatic return to the main channel (in Auto mode). Enabling of paralleling must be confirmed by the activation of a dedicated digital input. Paralleling disabled: Auto return to the priority channel involves opening the backup channel and, when it is open, closing the priority channel. Paralleling enabled: Auto return to the priority channel involves first closing the priority channel and, when it is closed, opening the backup channel.
Changeover conditions
Priority channel Genset voltage presence Parallel connection input Genset forcing The DIs can be assigned for ATS automation (configurable options)
DI 1 DI 2 DI 3 DI 4 DI 5 DI 6
1 2 3 4 5 6 7 8 9 10 11 12
Changeover takes place if the following conditions are met: bb Automatic transfer system in operation bb SW1 open and SW2 closed or SW1 closed and SW2 open bb Absence of fault current on the two channels (only if locking by fault detection option activated) bb Transfer locking absent bb Earthing switch absent on the two channels bb MV voltage absent on the active channel bb MV voltage present on the other channel. Return to the main channel for the Auto modes occurs if: bb The priority channel is open bb The MV voltage on the priority channel is present during time delay T2.
DE59175
DE56806
Relays are installed in factory in the T200 enclosure to provide interfacing with the generating set (Generator ATS version only). Connection should be performed as follows (see diagram opposite): bb Voltage: contact closed if Generator started, to be wired on the two available terminals (do not wire if detection of power on is performed by a relay VD23) bb Start-up: Generator start-up order, to be wired on terminals C and B bb Stop: Generator stoppage order, to be wired on terminals D and B.
Voltage presence on a channel managing the Generator can be executed by two processes: bb Either by a dedicated Voltage digital input bb Or by voltage relay VD23 (via cubicle cable).
Terminal block T200
C D C D
For routine test or reduced pricing requirements, it is possible to perform override setting of operation on the generator manually, remotely (from the supervisor) or locally (activation by a dedicated digital input). When the override setting is terminated, the automatic transfer system places itself back in the initial mode, i.e. in the mode that was active before the override setting (ON or OFF). During override setting, the automatic transfer system is set to ON for channels 1 and 2.
A dedicated digital input allows changeover to be locked if a problem occurs on one of the devices related to the changeover. This input is generally connected to the downstream circuit breaker. Local and remote controls are no longer possible in this case.
G
DE59173
bb Upon transfer to the Generator, if the latter doesnt start, the automatic transfer system waits for a period of 60 s at most before stopping changeover, then: vv in SW > SWG mode: the automatic transfer system is locked and must be reset (on the Control panel) to restart the device. vv in SW <> SWG mode or in Auto mode: the automatic transfer system remains operational. If voltage returns to the network channel, the automatic transfer system requests return to the network channel. bb When the automatic transfer system is configured with auto return on the network channel, Generator stoppage is requested 6 s after the changeover sequence is completed.
1 2 3 4 +5 6
Lock connection (J1 terminal block on the 4-ways interface or J9 on the 2-ways interface) AMTED398078EN
35
General characteristics
DE56655
SW1
SW3
SW2
The BTA (Bus Tie Automatism) is an automation system for switching sources between two incoming lines (SW1 and SW2) and a busbar coupling switch (SW3). It must be used in conjunction with VD23 type voltage presence detectors and the fault current detection function on the busbar incoming lines.
Operating mode
Normal position
SW1
SW3
SW2
Two operating modes can be configured: b Standard mode: If the voltage is lost on one busbar, the automation system opens the incoming line (SW1 or SW2) and closes the coupling switch SW3. Coupling is conditional upon the absence of a fault current on the main source. b Interlock on loss of voltage after switching mode: After execution of the automation system in standard mode, the voltage presence is checked for a configurable period. If the voltage is lost during this period, the coupling switch SW3 is opened and the automation system interlocked.
Coupling sequence
Active coupling
SW1 V2
V1 O C O C O
SW2
T1
SW1 T3 SW3 T2
Configurable parameters: b Operating mode: Standard/locking upon voltage loss b Automatic return: SW1/SW2 b Automation system: on/off b Delay before switching T1: 100 ms to 60 s in 100 ms steps b Delay before return T2: 5 s to 300 s in 1s steps b Interlock delay on voltage loss T3: 100 ms to 3 s in 100 ms steps b Motorisation type: command time b Manual control: enabled/disabled in local and remote modes if automation system in operation b Paralleling: enabled/disabled in auto and (or) manual modes b Transfer locking upon fault detection.
b Coupling takes place if the following conditions are met: v the automation system is switched on v the switches on incoming channels SW1 and SW2 are closed v the earthing switches SW1, SW2 and SW3 are open v there is no voltage on an incoming line SW1 or SW2 v there is no fault current detection on SW1 and SW2 v there is no transfer interlock v voltage is present on the other incoming line. b The coupling sequence in standard mode is as follows: v opening of the de-energised incoming line switch after a delay T1 v closing of the coupling switch SW3. b The coupling sequence in Interlock on loss of voltage after coupling mode i s completed as follows: v monitoring of the voltage stability for a delay T3 v opening of the coupling switch SW3 if this condition is not met v locking of BTA automation system. b The system returns to standard mode after coupling if: v the return to SW1 or SW2 option is activated v voltage on the channel has been normal for a delay T2 v the automation system is activated v the automation system is not locked v there is no coupling interlock.
DE59322EN
Coupling interlock
A dedicated digital input allows changeover to be locked if a problem occurs on one of the devices related to the changeover. This input is generally connected to the downstream circuit breaker. Local and remote controls are no longer possible in this case. Locking the automation system The BTA automation system is locked if one of the following conditions is met during the coupling process: b Failure of a command to open or close a switch b Indication that an earthing switch has closed b Appearance of a fault current b Switch power supply fault b Appearance of the coupling interlock b Manual or remote ON/OFF command from the automation system.
A software-configurable option allows the automation system to disable or enable paralleling of the channels upon automatic return to the main channel (in Auto mode). Enabling of paralleling must be confirmed by the activation of a dedicated digital input. If paralleling is disabled: Auto return to the normal channel involves opening the coupling channel (SW3) and, when it is open, closing the normal channel. If paralleling is enabled: Auto return to the normal channel involves first closing the normal channel and, when it is closed, opening the coupling channel (SW3).
36
AMTED398078EN
General characteristics
Flair 21D, 22D, 23DM is a family of DIN format fault passage indicators. They are small in size, self-powered and adapt automatically to the network. These devices use cutting-edge technology to detect earth faults on underground MV networks with isolated, resistor-earthed or directly earthed neutral and overcurrents on all networks. b Self-powered, the fault current passage detection and indication system operates continuously b Adjustment-free, they are immediately operational (numerous manual adjustments are however possible) b Compact, their DIN format easily fits in MV cubicles b Smart, they offer an ammeter/digital maximeter function b Comprehensive, the Flair 23DM version incorporates a highly sophisticated voltage presence/absence relay function with RJ45 Modbus communication.
The Flair range increases your power availability by providing indicators suitable for fault locating and MV network load management. b Indication of phase-phase and phase-earth faults b Display of settings b Indication of the faulty phase b Display of the load current including peak demand and frequency b Fault passage indication and voltage detection combination (Flair 23DM) b RJ45 communication (Flair 23DM only). These fault passage indicators are reliable and easy to use. b Automatic setting on the site b Fault indication with LED or outdoor lamp b 15-year battery life for Flair 22D b More accurate fault detection if Flair 22D or 23DM is connected to voltage presence indication system (VPIS) voltage output b Can be factory-mounted in Premset cubicles or added on the site b Easy on-site addition without removing MV cables using split-type current sensor.
PE57783
The detector checks the 3 phases for current variations (di/dt). A time delay of 70 s is applied for fault confi rmation by the upstream protective device. b Automatic mode for adjustment-free calibration of detection thresholds b Manual mode for special override settings: Flair 21D: 6 detection thresholds from 40 to 160 A, via microswitches Flair 22D and Flair 23DM (configurable via the front panel keypad): - Type A from 20 to 200 A, in 10 A increments - Type B from 5 to 30 A in 5 A increments and 30 to 200 A in 10 A. b Inrush function: prevents unnecessary detection in the event of load switch-on. Incorporates a 3 s time delay for fault fi ltering at network power up. The Inrush function can be disabled via confi guration on Flair 22D and 23DM.
PE57784
Indication reset
b Automatic reset upon load current recovery (configurable time delay on Flair 22D and Flair 23DM) b Manual reset via front panel button b Reset via external Reset input b Reset by time delay: fixed (4 hr) for Flair 21D and adjustable using front panel keypad (2 hr to 16 hr) for Flair 22D and Flair 23DM.
AMTED398078EN
37
General characteristics
Sensors The Flair 21D, 22D, 23DM range uses an integrated detection system composed of indicators and dedicated CTs. Integrated sensors are normally placed around the bushings. Split CTs can be placed around cables for retrofit purposes.
DE58715
Test Reset
Display principle
b The load current is displayed continuously b When a fault is detected, the faulty phase is indicated b Use the buttons on the front panel to scroll through settings and measurements.
Selection table
Flair
Flair 21D
Power supply Self-powered Dual-powered Overcurrent Earth-fault Display (4 digit LCD) Ammeter Maximeter SCADA interface (relay) External lamp External reset Extended setting (keypad) Communication 2-voltage output relays Serial communication port b
Flair 22D
b b (1) b b b b b b b b
Flair 23DM
b b b b b b b b b b b b
L1 L2 L3
Esc
I max.
Detection
Connection diagrams
DM1000048
L3 L2 L1
Description
Detector with autonomous power supply
Fault passage indicator with single power supply (self-powered) External indicator lamp output powered by battery (BVP) Fault passage indicator with dual power supply Flair 22D Detector with autonomous power supply and lithium battery External indicator lamp output powered by the Flair (BVE) VPIS-VO option Zero sequence CT option (type B setup) Interface with VPIS-VO possible to confirm the fault by voltage absence Fault passage indicator with dual power supply and voltage presence/absence Flair 23DM Detector with 24-48 Vdc external and autonomous power supply External indicator lamp output powered by the Flair (BVE) FLAIR 22D Reset Indication L3 L2 L1 SCADA Reset VPIS-VO option + (1) Zero sequence CT option (type B or C setup) Voltage presence and absence detector (same as for VD23) Interface with VPIS-VO needed for the voltage presence
FLAIR 21D
Reset Indication L3 L2 L1
Standard applications
Flair 21D Flair 22D Flair 23DM Maintenance-free, adjustment-free fault detector Fault detector for networks with very low load current (< 2 A) with possibility of manual adjustments Adapted to Feeder Automation. Forwarding of current measurement, fault passage indication and voltage outage information to the SCADA via a serial communication port. Combination fault passage indicator and voltage detector, ideal for use with an Automatic Transfer System
38
AMTED398078EN
General characteristics
Ammeter
b At the leading edge of technology, Amp 21D is suitable for Medium Voltage network load management. b Self-powered, it ensures a permanent display of currents. b Compact and in DIN format, it fits naturally into MV cubicles. b Cost efficient, it uses the CT optimised for Fault Passage Indicator. b Performant, it displays phase current and maximum of current.
Functions
bb Display of 3 phase current: I1 , I2 , I3. Range: 3 A to 630 A bb Display of 3 phase current maximeter: I1 , I2 , I3. Range: 3 to 630 A.
Display principle
bb Load curents are permanently displayed vv continuous scrolling of L1, then L2, then L3. bb Maximeter vv access to maximeter display by pressing a dedicated push button vv continuous scrolling of M1, then M2, then M3 vv reset of all maximeter by pressing a combination of two push buttons.
Connections, assembly
Small size enclosure bb DIN format: 93 x 45 mm bb Secured, extraction-proff mounting bb Terminal connections. Current sensors bb Split core CT for mounting on MV cables.
PE57786
Technical data
Application Frequency Load current Measurement Range Amp 21D Reset of maximeter Power supply Self power Battery Auxiliary supply Display L1 L2 L3 Sensors Phase CTs Miscellaneous Test
PE57233
Minimum current Phase current Accuracy (I < 630 A) Manual from device From the current sensors
50 Hz and 60 Hz 3A 3 to 630 A (resolution 1 A) (2% + 2 digit) Yes I load 3 A No No 4 digits LCD Yes (resolution 1 A) Yes 3 split core CT Yes
DE58404
The SM6 can integrate ammeter Amp 21D on all incoming cubicles and the fuse-switch cubicles
AMTED398078EN
39
General characteristics
The Sepam range of protection and metering is designed for the operation of machines and electrical distribution networks of industrial installations and utility substations for all levels of voltage. It consists of complete, simple and reliable solutions, suited to following five families: Sepam series 10, 20, 40, 60 and 80. A range adapted at your application
bb Protection of substation (incoming, outgoing line and busbars). bb Protection of transformers. bb Protection of motors, and generators.
Series 10
Series 20
Simplicity
Easy to install bb Light, compact base unit. bb Optional modules fitted on a DIN rail, connected using prefabricated cords. bb User friendly and powerful PC parameter and protection setting software to utilize all of Sepams possibilities. User-friendly bb Intuitive User Machine Interface, with direct data access. bb Local operating data in the users language.
Protections
b b b b b
Disconnection by rate of change of frequency
Breaker failure
Applications
Characteristics
4 7
0 to 10 4 to 8 0 to 8
0 to 10 4 to 8 0 to 8
3I + Io
3I + Io 3V + Vo
b
1 1 to 2 1 to 2
b b
b b
Other
Backup battery Front memory cartridge with settings (1) LPCT: low-power current transformer complying with standard IEC 60044-8. (2) Control matrix for simple assignment of information from the protection, control and monitoring functions. (3) Logipam ladder language (PC programming environment) to make full use of Sepam series 80 functions. (4) Standard lithium battery 1/2 AA format, 3.6 V, front face exchangeable. Lithium battery (4)
40
AMTED398078EN
General characteristics
Series 40
Series 60
Protections
b b b
b b b
Directional earth fault
b b b
Directional earth fault and phase overcurrent
b b b
b b b
Directional earth fault
b b b
Directional earth fault and phase overcurrent
Applications
S40 T40
S41, S43
S42 T42
M41 G40
Characteristics
0 to 10 4 to 8 0 to 16 3 I + Io 3V, 2U + Vo
b
1 to 2
b
1 to 2
b b b
b b b
Other
Backup battery Front memory cartridge with settings 48 hours Lithium battery (4)
(1) LPCT: low-power current transformer complying with standard IEC 60044-8. (2) Control matrix for simple assignment of information from the protection, control and monitoring functions. (3) Logipam ladder language (PC programming environment) to make full use of Sepam series 80 functions. (4) Standard lithium battery 1/2 AA format, 3.6 V, front face exchangeable.
AMTED398078EN
41
General characteristics
Series 80
Protections
b b b
b b b
Directional earth fault
b b b
Directional earth fault and phase overcurrent
b b b
Disconnection by rate of change of frequency
b b b
b b b
b b b
Voltage and frequency protection for 2 sets of busbars
b b b
Capacitor-bank unbalance
Applications
S80 B80
Characteristics
0 to 42 5 to 23 0 to 16 3I + 2 x Io 3V + Vo
0 to 42 5 to 23 0 to 16 2 x 3I + 2 x Io 3V + Vo
0 to 42 5 to 23 0 to 16 3I + Io 2 x 3V + 2 x Vo
0 to 42 5 to 23 0 to 16 2 x 3I + 2 x Io 3V + Vo
b
2 to 4
b
2 to 4
b
2 to 4
b
2 to 4
b b b b
Lithium battery (4)
b b b b
Lithium battery (4)
b b b b
Lithium battery (4)
b b b b
Lithium battery (4)
Other
Backup battery Front memory cartridge with settings
(1) LPCT: low-power current transformer complying with standard IEC 60044-8. (2) Control matrix for simple assignment of information from the protection, control and monitoring functions. (3) Logipam ladder language (PC programming environment) to make full use of Sepam series 80 functions. (4) Standard lithium battery 1/2 AA format, 3.6 V, front face exchangeable.
42
AMTED398078EN
General characteristics
PE57159
VIP 35
PE57160
VIP 300 LL
AMTED398078EN
43
General characteristics
Sepam series 10
44
AMTED398078EN
General characteristics
Code
Protection units
series 20 b b series 40 b b b b b b b b b b b b series 60 b b b b b b b b b b b b series 80 b b b b b b b b b b b b VIP 35 b (2) b (3) 300 b (1) b (1)
b b b b b b
(1) DT, EI, SI, VI and RI trip curves. (2) Inverse curve suited to transformer protection. (3) DT trip curve.
Current sensor for VIP 35 and VIP 300LL and Sepam series 10 for SM6-24
Type Dimensions (mm) External Internal Thickness (without fastening) 143.5 81 37.5 Weight (kg) Ratio of Class of precision transformation VIP 35 VIP 300LL Sepam 10
CRa
2.18
1/200
CRb CRc
143.5 143.5
81 81
37.5 37.5
1.26 2
2% from 10 A to 100 A On load 5.7 (cal. x 1) 1% from 100 A to 1600 A 1% from 10 A to 10 kA On load 0.67 (cal. x 4) 1% from 10 A to 11 kA On load 5.7 (cal. x 1) 1 % from 10 A to 25 kA On load 0.67 (cal. x 4) S1-S2: On load 0.6 5% from 10 A to 80 A 2.5 % from 80 A to 600 A S1-S3: 2% from 20 A to 2200 A
b b b
b b
DE58402
AMTED398078EN
45
General characteristics
Standard applications
PE88012
TLP130, TLP190, CLP2 sensors for Sepam series 20, 40, 60, 80 protection units
LPCT sensors are voltage-output current sensors (Low Power Current Transformer) compliant with the IEC 60044-8 standard. These sensors are designed to measure rated current between 5 A and 630 A, with a ratio of 100 A / 22.5 mV. Sepam series 20, 40, 60 and 80 protection units are at the heart of the LPCT protection chain. Sepam series 20, 40, 60 and 80 performs the following functions: bb acquisition of phase currents measured by the LPCT sensors bb utilization of measurements by the protection functions bb tripping of the breaking device in case of fault detection.
Sepam series 20
Advantages
Demanding applications
PE88011
Sepam series 40
DE58405EN
bb Consistent protection chain with the same sensor measures phase currents from 5 A to 630 A bb Simple to install and implement: vv installation of LPCT sensors -- TLP130 and TLP190 are installed around MV cable -- CLP2 is installed on the MV circuit vv LPCT connected directly to Sepam series 20, 40, 60 and 80 vv accessories available to test the LPCT protection chain by secondary current injection. bb LPCTs range of use LPCT measuring and protection function guaranteeing the accuracy up to the short-time current. Following the range of use of LPCT: vv from 5 A up to 1250 A respecting the error limits imposed by the accuracy class 0,5 vv from 1250 A up to 50 kA respecting the error limits imposed by the accuracy class 5P.
Ratio error
Custom applications
PE88010
5.00 4.75 4.50 4.25 4.00 3.75 3.50 3.25 3.00 2.75 2.50 2.25 2.00 1.75 1.50 1.25 1.00 0.75 0.50 0.25
A
5 20 100 1000 1250 2000 3000 31500 40000 50000
bb Optimized integration of functions: vv measurement of phase rated currents as of 25 A that is set by micro-switch vv monitoring of LPCT sensor by Sepam series 20, 40, 60 and 80 (detection of phase loss).
MT11325
Connections
1 LPCT sensor, equipped with a shielded cable fitted with an RJ45 connector to be connected directly to the card 3 2 Sepam series 20, 40, 60 and 80 protection unit 3 Card interface that adapts the voltage delivered by the LPCT sensors, with microswitch setting of rated current. vv CCA671 card for series 60 and 80 vv CCA670 card for series 20 and 40.
46
AMTED398078EN
General characteristics
Backup solution for MV switchgear power needs in the event of micro outages and power interruptions. bb Easy maintenance with only one battery bb Remote battery monitoring bb High level of insulation to protect the electronic devices in harsh MV environments bb End-of-life alarm possible via Modbus communication bb Compliant with standards IEC 60 255-5 (10 kV level).
A battery ensures uninterrupted operation of the whole substation in the event of loss of the main supply. The backup power supply unit: bb Includes a regulated and temperature-compensated charger bb Stops the battery before deep discharge bb Carries out a battery check every 12 hours bb Measures battery ageing bb Forwards monitoring information via a Modbus communication port and output relays.
PM100592
PS100 benefits
Only one battery
Traditional backup power supplies require a set of 2 or 4 batteries to produce 24 V or 48 V, with complicated replacement and adjustment of the battery pack. The PS100 needs only one battery, simplifying replacement.
PS100
The battery is a standard sealed lead-acid 12 V battery with a 10-year service. It can be purchased easily, anywhere in the world.
The PS100 is designed to ride through power network interruptions of up to 48 hours. It is associated with a battery selected to meet the required backup time. The PS100 protects and optimises the battery with state-of-the-art monitoring. A Modbus communication port forwards monitoring data to allow optimised maintenance operations. Perfect integration with the Easergy range to control and monitor your distribution network.
The PS100 stops supplying power and reserves an additional energy backup to restart the installation after an extended power interruption. The additional energy backup can be enabled with a local pushbutton to provide energy for restarting the protection relays and operating the MV switchgear.
The PS100 includes 10 kV insulation, electronic protection against overvoltage and overloads, and automatic restart after a fault.
Main features
bb DIN rail mounting for easy integration in any LV cabinet or MV/LV substation bb 2 power supply outputs: vv 12 Vdc - 18 W continuous - 100 W 20 s (for modem, radio, RTU, etc.) vv 48 Vdc or 24 Vdc - 300 W /1 minute (for switchgear operating mechanism motors) and 90 W / continuous for protection relays, electronic devices, etc. bb RJ45 Modbus communication port bb 2 output relays (AC supply ON, Battery ON) bb Diagnosis with LEDs bb 1 sealed lead-acid 12 V battery with a 10-year service life (from 7 Ah to 40 Ah) bb Power supply paralleling available with a 2nd PS100 bb -40C to +70C operating temperature.
Range
48 Vdc power supply and battery charger 24 Vdc power supply and battery charger 24 Ah long life battery 38 Ah long life battery.
AMTED398078EN
47
48
AMTED398078EN
Contents
50 50 52 60 62 65 68 70 72 73 75 76 77 79
Operating mechanisms Auxiliaries Current transformers for SM6-24 Current transformers for SM6-36 Voltage transformers for SM6-24 Voltage transformers for SM6-36 Motors protection units Protection of transformers Interlocks
AMTED398078EN
49
IM Switch unit
DE59700 DE53518
Electrical characteristics
DE59710
kA 25 20 16 12.5
Ik/1s
DE59711
kA 62.5 50
Ima
Ir = 630 A
Ir = 630 A 40
Ur kV
31.25 7.2
Ur kV
Basic equipment:
bb switch and earthing switch bb three-phase busbars bb CIT operating mechanism bb voltage presence indicator bb 150 W heating element for SM6-36 bb connection pads for dry-type cables bb one to three CTs for SM6-24 bb three CTs for SM6-36 bb three-phase bottom busbars for outgoing lines (right or left)
Versions:
bb CI2 operating mechanism bb CI1 operating mechanism bb in 800 A version for SM6-24, consult us bb CI1 operating mechanism for SM6-36 bb CI1 operating mechanism
Optional accessories:
bb motor for operating mechanism bb auxiliary contacts bb key-type interlocks bb release units (coil) bb operation counter bb 1250 A three-phase upper busbars
bb 630 A three-phase upper busbars for severe operating conditions for SM6-24 bb visibility of main contacts bb pressure indicator device bb enlarged low-voltage control cabinet for SM6-24 bb 50 W heating element for SM6-24 bb 630 A cable connection by the top (no internal arc withstand if selected)
bb fault indicators bb Connection pads for two dry-type single-core cables for 36 kV bb digital ammeter bb surge arresters (for SM6-36 and for SM6-24 in 500 mm width cubicle) bb 630 A busbars earthing switch cabinet for SM6-24 (not available for internal arc IEC62271-200)
50
AMTED398078EN
Switching
NSM-cables Cables power supply for main incoming line (N) and standby line (S)
DE53559 DE58401
NSM-busbars Cables power supply for main incoming line on left (N) and busbars for standby line (S) on right
DE53561
NSM-busbars Busbars power supply for main incoming line on left (N) and cables for standby line (S) on right
Electrical characteristics
DE59212
kA 25 20 16 12.5
Ik/1s
DE59218
kA 62.5 50
Ima
Ir = 630 A
Ir = 630 A 40
Ur kV
31.25 7.2
Ur kV
Basic equipment:
bb switches and earthing switches bb three-phase busbars bb connection pads for dry-type cables bb voltage presence indicator bb mechanical interlocking bb motorised operating mechanism CI2 with open/close coils bb additional enclosure bb automatic-control equipment (T200 S)
Optional accessories:
bb auxiliary contacts bb key-type interlocks bb 50 W heating element bb control and monitoring bb visibility of main contacts bb pressure indicator device bb 1250 A three-phase upper busbars bb 630 A three-phase upper busbars for severe operating conditions
AMTED398078EN
51
Electrical characteristics
DE59712 DE59713
kA 25 20 16 12.5
Ik/1s
kA 25 20
Isc
Ir = 200 A
Ir = 63 A
16 12.5 7.2
Ir = 200 A
Ir = 63 A
Ur 7.2 12 17.5 24 36 kV
Ur 12 17.5 24 36 kV
Basic equipment:
bb switch and earthing switch bb three-phase busbars bb CI1 operating mechanism bb voltage presence indicator bb equipment for three DIN striker fuses bb mechanical indication system for blown fuses bb 150 W heating element for SM6-36 bb three-phase bottom busbars for outgoing lines (right or left) bb one to three CTs for SM6-24 bb three CTs for SM6-36
bb connection pads for dry-type cables bb downstream earthing switch 2 kA rms making capacity
Version:
bb equipment for three UTE striker fuses for SM6-24 bb CI2 operating mechanism bb CI2 operating mechanism for SM6-36
Optional accessories:
bb motor for operating mechanism bb auxiliary contacts bb key-type interlocks bb auxiliary contact for blown fuses bb DIN striker fuses bb release units (coil) bb digital ammeter bb 1250 A three-phase upper busbars bb 630 A cable connection by the top (no internal arc withstand if selected) bb visibility of main contacts bb pressure indicator device bb 630 A three-phase upper busbars for severe operating conditions for SM6-24 bb enlarged low-voltage control cabinet for SM6-24 bb 50 W heating element for SM6-24
52
AMTED398078EN
PM Fused-switch unit
DE53526
Electrical characteristics
DE59714
kA 25 20 16 12.5
Ir = 200 A
Ir = 63 A
Ur 7.2 12 17.5 24 36 kV
Basic equipment:
bb switch and earthing switch bb three-phase busbars bb CIT operating mechanism bb voltage presence indicator bb connection pads for dry-type cables bb downstream earthing switch 2 kA rms making capacity bb equipment for three UTE (for SM6-24) or DIN striker fuses bb 150 W heating element for SM6-36
Version:
Optional accessories:
bb motor for operating mechanism bb auxiliary contacts bb digital ammeter bb key-type interlocks bb mechanical indication system for blown fuses bb 1250 A three-phase upper busbars bb 630 A cable connection by the top (no internal arc withstand if selected) bb UTE (for SM6-24) or DIN striker fuses bb visibility of main contacts bb pressure indicator device bb 630 A three-phase upper busbars for severe operating conditions for SM6-24 bb enlarged low-voltage control cabinet for SM6-24 bb 50 W heating element for SM6-24 bb Release units for SM6-36
AMTED398078EN
53
Electrical characteristics
DE59715
kA 25 20
Ur kV
Basic equipment:
bb SF1 disconnectable circuit breaker bb disconnector and earthing switch bb three-phase busbars bb circuit breaker operating mechanism RI bb disconnector operating mechanism CS bb voltage presence indicator bb three CTs bb auxiliary contacts on circuit breaker bb mechanical interlocking between circuit breaker and disconnector bb 150 W heating element for SM6-36 bb three-phase bottom busbars
bb connection pads for dry-type cables bb downstream earthing switch 2 kA rms making capacity at 630 A and 25 kA rms making capacity at 1250 A
Version:
bb LPCT (only with Sepam series 20, 40, 60, 80) bb SFset circuit breaker disconnectable (only for 400-630 A performances and SM6-24)
Optional accessories:
bb cubicle: vv auxiliary contacts on the disconnector vv protection using Sepam programmable electronic unit vv three voltage transformers vv key-type interlocks vv 1250 A three-phase upper busbars at Ir 630 A vv 630 A cable connection by the top (no internal arc withstand if selected)
vv 630 A three-phase upper busbars for severe operating conditions for SM6-24 vv enlarged low-voltage control cabinet for SM6-24 vv 50 W heating element for SM6-24 vv connection pads for two dry-type single-core cables for SM6-36
vv surge arresters vv 630 A busbars earthing switch cabinet for SM6-24 (not available for internal arc IEC62271-200)
54
AMTED398078EN
Electrical characteristics
DE59212-Isc
kA 25 20 16 12.5
DE59721
kA 25 20
Ir = 630 A
Ir = 630 16
Ur kV
12.5 7.2
Ur kV
Basic equipment:
bb SF1 disconnectable circuit breaker bb disconnector and earthing switch bb three-phase busbars bb circuit breaker operating mechanism RI bb disconnector operating mechanism CS bb auxiliary contacts on circuit breaker bb mechanical interlocking between circuit breaker and disconnector bb three CTs bb 150 W heating element for SM6-36
bb VIP relay bb three CR sensors for VIP relay protection bb voltage presence indicator bb connection pads for dry-type cables bb downstream earthing switch 2 kA rms making capacity
Version:
Optional accessories:
bb cubicle: vv key-type interlocks
bb cubicle: vv protection using Sepam programmable electronic unit vv auxiliary contacts on disconnectors vv 2 voltage transformers phase-to-phase or 3 voltage transformers phase-to-earth bb 630 A cable connection by the top (no internal arc withstand if selected) vv 50 W heating element for SM6-24
vv 1250 A three-phase upper busbars at Ir 630 A vv 630 A three-phase upper busbars for severe operating conditions for SM6-24 vv enlarged low-voltage control cabinet for SM6-24 bb circuit breaker: vv motor for operating mechanism vv release units (coil) vv operation counter on manual operating mechanism
AMTED398078EN
55
Electrical characteristics
DE59715 DE59226
kA 25 20
kA 25 20
Ir = 630 - 1250 A 16 12.5 Ir = 400 - 630 - 1250 A 7.2 12 17.5 24 36 16 12.5 7.2
Ir = 1250 A
Ur kV
Ur 12 17.5 24 kV
Basic equipment:
bb SF1 withdrawable circuit breaker bb disconnector and earthing switch bb three-phase busbars bb circuit breaker operating mechanism RI bb disconnector operating mechanism CS bb voltage presence indicator bb three CTs bb auxiliary contacts on circuit breaker
bb mechanical interlocking between circuit breaker and disconnector bb earthing switch operating mechanism CC bb connection pads for dry-type cables bb downstream earthing switch 25 kA rms making capacity bb three-phase busbars
Version:
bb LPCT (only with Sepam series 20, 40, 60 and 80) bb circuit breaker: vv motor for operating mechanism vv release units (coil) vv operation counter on manual operating mechanism
Optional accessories:
bb cubicle: vv auxiliary contacts on the disconnector vv protection using Sepam programmable electronic unit vv key-type interlocks vv three voltage transformers for SM6-24 vv connection enclosure for cabling from above for SM6-24 vv 50 W heating element for SM6-24 vv enlarged low-voltage control cabinet for SM6-24 vv 1250 A three-phase upper busbars at Ir 630 A vv 630 A three-phase upper busbars for severe operating conditions for SM6-24 vv surge arresters (only for 630 A and SM6-24)
56
AMTED398078EN
Electrical characteristics
DE59227
kA 25 20 16 12.5
Ir = 630 - 1250 A
Ur kV
Basic equipment:
bb Evolis circuit breaker frontal bb switch and earthing switch for 400 - 630 A bb disconnector and earthing switch for 1250 A bb three-phase busbars bb circuit breaker operating mechanism P2 bb disconnector and switch operating mechanism CIT bb voltage presence indicator bb auxiliary contacts on circuit breaker bb 3 CR sensors for VIP relay bb VIP protection relay bb connection pads for dry-type cables bb downstream earthing switch 25 kA rms making capacity
bb three CTs bb Sepam series 20 programmable electronic unit bb connection pads for dry-type cables bb downstream earthing switch 25 kA rms making capacity
Optional accessories:
bb cubicle: bb circuit breaker: vv auxiliary contacts on the disconnector vv motor for operating mechanism vv three voltage transformers vv release units (coil) vv key-type interlocks vv operation counter on manual operating mechanism vv 50 W heating element vv 1250 A three-phase upper busbars at Ir 630 A vv 630 A three-phase upper busbars for severe operating conditions vv enlarged low-voltage control cabinet vv 630 A cable connection by the top (no internal arc withstand if selected)
AMTED398078EN
57
Electrical characteristics
DE59228
kA 25 20 16 12.5
DE59717
kA 25 20
Ur 7.2 12 17.5 24 kV
Ur kV
Basic equipment:
bb Evolis circuit breaker lateral disconnectable bb disconnector and earthing switch bb mechanical interlocking between circuit breaker and disconnector bb three-phase busbars bb circuit breaker operating mechanism RI bb disconnector operating mechanism CS bb voltage presence indicator bb auxiliary contacts on circuit breaker bb 3 CTs bb connection pads for dry-type cables bb downstream earthing switch 2 kA rms making capacity
Optional accessories:
bb cubicle: bb circuit breaker: vv auxiliary contacts on the disconnector vv motor for operating mechanism vv three voltage transformers vv release units (coil) vv key-type interlocks vv operation counter on manual operating mechanism vv 50 W heating element vv 1250 A three-phase upper busbars at Ir 630 A vv 630 A three-phase upper busbars for severe operating conditions vv enlarged low-voltage control cabinet vv Sepam relay protection vv surge arresters
58
AMTED398078EN
Electrical characteristics
DE59220 DE59221
kA
kA 25
Isc
10 8 6.3
Ur kV
Basic equipment:
bb vacuum contactor bb disconnector and earthing switch bb three-phase busbars bb contactor operating mechanism with magnetic holding or contactor with mechanical latching bb disconnector operating mechanism CS bb one to three current transformers bb auxiliary contacts on contactor bb connection pads for dry-type cables bb voltage presence indicator bb downstream earthing switch 2 kA rms making capacity bb operation counter on contactor bb enlarged low-voltage control cabinet bb mechanical interlocking between contactor and disconnector/earthing switch bb equipment for three DIN striker fuses bb mechanical indication system for blown fuses bb auxiliary contact for blown fuses
Version:
Optional accessories:
bb cubicle: vv auxiliary contacts on the disconnector vv protection using Sepam programmable electronic unit vv one to three voltage transformers vv key-type interlocks vv 50 W heating element vv 1250 A three-phase upper busbars vv 630 A three-phase upper busbars for severe operating conditions
AMTED398078EN
59
CM2 Voltage transformers unit for network with insulated neutral system
Electrical characteristics
DE59722
kA 25 20
Ik/1s
Ur kV
Basic equipment:
bb disconnector and earthing switch bb three-phase busbars bb operating mechanism CS bb LV circuit isolation switch bb LV fuses bb three 6.3 A UTE or DIN type fuses bb 150 W heating element for SM6-36 bb three-voltage transformers (phase-to-earth) bb two voltage transformers (phase-to-phase)
Optional accessories:
bb auxiliary contacts bb mechanical signalling for blown fuses bb auxiliary contact for blown fuses for SM6-24 bb 1250 A three-phase upper busbars bb 630 A cable connection by the top (no internal arc withstand if selected) bb 50 W heating element for SM6-24 bb 630 A three-phase upper busbars for severe operating conditions for SM6-24 bb enlarged low-voltage control cabinet for SM6-24
60
AMTED398078EN
Electrical characteristics
DE59709
kA 25 20
Ik/1s Ir = 1250 A
Ur kV
Basic equipment:
bb one to three CTs for SM6-24 bb three CTs for SM6-36 bb connection bars bb three-phase busbars bb 150 W heating element for SM6-36
Optional accessories:
bb 1250 A three-phase upper busbars at Ir 630 A for SM6-24 bb enlarged low-voltage control cabinet for SM6-24 bb three voltage transformers (phase-to-earth) or two voltage transformers (phase-to-phase) for SM6-24 bb 50 W heating element for SM6-24 bb 630 A cable connection by the top for SM6-36 (no internal arc withstand if selected)
AMTED398078EN
61
Electrical characteristics
DE59709 DE59212
kA 25 20
Ik/1s Ir = 1250 A
kA 25 20
Ik/1s
DE59709_2
kA 25 20 16
Ik/1s
kA 25 20
Ik/1s
Ir = 630 - 1250 A 16 12.5 Ir = 400 - 630 - 1250 A 7.2 12 17.5 24 36 16 12.5 7.2
Ir = 630 A
Ir = 630 A
Ir = 630 A Ur 36 kV
Ur kV
Ur kV
12.5 24
Ur kV
Basic equipment:
bb connection bars bb three-phase busbars for outgoing lines right or left bb 150 W heating element for SM6-36
bb metallic envelop
Optional accessories:
bb 1250 A three-phase upper busbars at Ir 630 A bb enlarged low-voltage control cabinet for SM6-24 bb 630 A cable connection by the top for SM6-36 (no internal arc withstand if selected)
bb LV-continuity
62
AMTED398078EN
Electrical characteristics
DE59719
kA 25 20 16 12.5
DE59709
kA 25 20
Ik/1s Ir = 1250 A
Ir = 630 1250 A
Ur kV
Ur kV
Basic equipment:
bb three-phase busbars bb voltage presence indicator bb connection pads for dry-type cables bb connection bars bb 150 W heating element for SM6-36 bb downstream earthing switch 25 kA rms making capacity bb operating mechanism CC for SM6-24 bb operating mechanism CS for SM6-36
Optional accessories:
bb fault indicator bb digital ammeter bb 1250 A three-phase upper busbars at Ir 630 A bb enlarged low-voltage control cabinet for SM6-24 bb 630 A cable connection by the top (no internal arc withstand if selected) bb 50 W heating element for SM6-24 bb auxiliary contacts bb key-type interlocks bb surge arresters for SM6-24
AMTED398078EN
63
SM Disconnector unit
DE59704 DE53557
Electrical characteristics
DE59709 DE59722
kA 25 20
Ik/1s Ir = 1250 A
kA 25 20
Ik/1s
DE59212
kA 25 20
Ik/1s
Ir = 630 - 1250 A 16 12.5 Ir = 400 - 630 - 1250 A 7.2 12 17.5 24 36 16 12.5 7.2 12
Ir = 50 A 16 12.5 7.2
Ir = 630 A
Ur kV
Ur 17.5 24 36 kV
Ur kV
Basic equipment:
bb disconnector and earthing switch bb three-phase busbars bb operating mechanism CS bb 150 W heating element for SM6-36 bb connection pads for dry-type cables bb voltage presence indicator bb two 6.3 A fuses, UTE (for SM6-24) or DIN type bb LV circuit isolating switch bb one voltage transformer (phase-to-phase)
bb earthing switch bb connection bars three phase bb operating mechanism CIT bb installation on 630 A IM 375 mm or DM1-A units (not available for internal arc IEC 62271-200) bb require a key-type interlocks adapted to the switchboard network
Optional accessories:
bb auxiliary contacts bb key-type interlocks bb 1250 A three-phase upper busbars at Ir 630 A bb 630 A cable connection by the top (no internal arc withstand if selected) bb enlarged low-voltage control cabinet for SM6-24 bb 50 W heating element for SM6-24 bb 630 A three-phase upper busbars for severe operating conditions for SM6-24 bb digital ammeter for SM6-24 bb surge arrester for SM6-36 bb mechanical signalling for blown fuses bb auxiliary contact for blown fuses for SM6-24
bb auxiliary contacts
64
AMTED398078EN
Operating mechanisms
The control devices required for the unit operating mechanisms are centralised on the front panel. The different types of operating mechanism are presented in the table opposite. Operating speeds do not depend on the operator, except for the CS.
Units
IM, IMB IMC PM QM QMC, QMB CM, CM2, CVM DM1-A, DM1-D, DM1-S, DM1-Z, DM2, DMVL-A, DMVL-D DM1-A (2), DM1-W DMV-A, DMV-D, DMV-S NSM-cables, NSM-busbars GAM 24 kV SM, TM, GAM 36 kV EMB
b b b
v v v b b
v v v(1) v v b b b b b b b b b b
CIT
Load-break switch Fused switch Closing Opening Hand lever Hand lever Motor Motor 1 to 2 s 1 to 2 s Remote control network management Closing Hand lever Opening Hand lever
CI1
Load-break switch Fuse switch combination Closing Opening Hand lever Push button Motor Coil 4 to 7 s 35 ms Remote control transformer protection Closing Hand lever Opening Hand lever
CI2
Load-break switch Fuse switch combination Mechanism Closing Opening charging Hand lever Push button Push button Motor Coil Coil 4 to 7 s 55 ms 35 ms Remote control network management, need of quick reconfiguration (generator source, loop) N/A Closing Opening Hand lever Hand lever Hand lever
CS
Disconnector Closing Hand lever N/A N/A N/A Closing Hand lever Opening Hand lever N/A N/A
61029N
AMTED398078EN
65
Operating mechanisms
61030N
61031N
61032N
66
AMTED398078EN
Operating mechanisms
Single-function operating mechanism for the SF circuit breakers 24 kV and 36 kV and Evolis 24 kV lateral
bb Circuit-breaker function vv independent-operation closing in two steps. First operating mechanism recharge by motor or lever, then release of the stored energy by push-button (I) or trip unit. vv independent-operation opening by push-button (O) or trip units. bb Auxiliary contacts vv circuit breaker (4 O + 4 C), vv mechanism charged (1 C). bb Mechanical indications Operation counter. bb Opening releases vv Mitop (low energy), vv shunt trip, vv undervoltage. bb Closing release vv shunt trip bb Motor option (option and installation at a later date possible). Possible combinations between opening releases SF1
Release type Mitop (low energy) Shunt trip Undervoltage Combinations 1 b 2 b b b 3 b b b b b 4 5 6
PE57163
SFset
Combinations 1 b 2 b b b 3 b 4
61035N
P2 stored energy operating mechanism for the Evolis circuit breaker 17.5 kV frontal
bb Circuit-breaker function vv independent-switching operating closing in two steps. First operating mechanism recharge by motor or lever, then release of the stored energy by push-button (I) or trip unit. vv independent-operation opening by push-button (O) or trip units. vv spring energy release. bb Auxiliary contacts vv circuit breaker (4 O + 4 C), vv mechanism charged (1 C). bb Mechanical indications Operation counter. bb Opening releases vv Mitop (low energy), vv shunt trip. bb Closing release vv shunt trip bb Motor option (option and installation at a later date possible).
AMTED398078EN
67
Auxiliaries
61036N
Power supply
Un
(V)
DC
24 200
48
110
125
220
AC (50 Hz)*
120 230
Motor option
(W) (VA) Operating time for CIT Charging time for CI1, CI2 200 1 to 2 (s) 4 to 7 (s) 300 300 300 400 35 750
Opening releases
Shunt trip Response time Undervoltage Pick-up Hold Response time (W) (VA) (ms) (W) (VA) (W) (VA) (ms) (W) (VA) (ms)
550 40
Closing release
Shunt trip Response time 750
Motor option and releases for SF6 type circuit breakers and Evolis 24 kV lateral
Operating mechanism RI may be equipped with the motor option for the recharging function.
PE57164
Power supply
Un
(V) (W) (VA) (s) (W) (ms) (W) (VA) (ms) (W) (VA) (W) (VA) (ms) (W) (VA) (ms)
DC
24 300
48
110
125
220
AC (50 Hz)*
120 230
Motor option
380 15 3 30 85 45 160 280 10 55 85 180 65 65 50 55 40 550 15
Charging time
Opening releases
Mitop (low energy) Response time Shunt trip Response time Undervoltage Pick-up Hold Response time 30 180 45
Closing release
Shunt trip Response time
68
AMTED398078EN
Auxiliaries
Motor option and releases for Evolis circuit breakers 17.5 kV frontal
Charging motor and associated mechanism (P2)
Power supply Threshold Consumption Charging time Switching rate CH contact Power supply Threshold Response time to the circuit breaker at Ur (VA or W) Motor overcurrent (Vac 50/60 Hz) (Vdc) 24/30 0.85 to 1.1 Ur 180 2 to 3 Ir during 0.1 s 6 s max. 3 cycles per minute max. 10 A 240 V Direct current 0.6 A < I < 3 A 50 ms (protection relay setting) 48/60 48/60 100/130 100/125 200/240 200/250
61035N
PE57842
Open release characteristics Power supply (Vdc) 48 Consumption (W) 470 Response time (ms) 20-40
AMTED398078EN
69
Units QMC
TC ARJP1 ARM3 ARJP2 ARJP3 CLP2 TLP130 ARM4
CVM
b (*)
b (*) Transformer ARJP1/N2F bb characteristics according to IEC standard 61869-2 bb single primary winding bb double secondary winding for measurement and protection. Short-time withstand current Ith (kA)
I1n (A) Ith (kA) t (s) Measurement and protection 10 20 30 1.2 2.4 3.6 1 15 VA - class 0.5 2.5 VA - 5P20 50 6 75 10 100 10 150 10 200 10
ARJP1
5A 5A
Transformer ARJP1/N2F bb characteristics according to IEC standard 61869-2 bb single primary winding bb double secondary winding for measurement and protection.
ARJP1
5A 5A
Transformer ARM3/N2F bb characteristics according to IEC standard 61869-2 bb double primary winding bb single secondary winding for measurement and protection. Short-time withstand current Ith (kA)
I1n (A) Ith (kA) t (s) Measurement and 5 A protection 1A 5A * For 5 A protection 10/20 20/40 5 12.5 1 0.8 7.5 VA - class 0.5 1 VA - 10P30 5 VA - 5P10 50/100 12.5/21* 1
ARM3
100/200 12.5/25*
200/400 12.5/25*
300/600 25
5 VA - 5P15
bb characteristics according to IEC standard 61869-2 bb double primary winding bb double secondary winding for measurement and protection. Short-time withstand current Ith (kA)
I1n (A) Ith (kA) t (s) Measurement and protection 50/100 14.5 1 30 VA - class 0.5 5 VA - 5P15 7.5 VA - 5P10 100/200 25 200/400 25 300/600 25
5A 5A 5A
ARM4
(*) Consult us
Transformer ARM4 bb characteristics according to IEC standard 61869-2 bb single or double primary winding bb up to 3 secondary windings (for measure and/or for protection) bb rated highest voltage 7,2 - 12 - 17,5 - 24kV bb rated primary current up to 630A (for SM6 cubicles) bb secondary currents 5A or 1A bb version with one secondary winding: ARM4/N1F bb version with two secondary windings: ARM4/N2F bb version with three secondary windings: ARM4/N3F for further characteristics please consult us.
AMTED398078EN
70
ARJP3
Transformer ARJP3/N2F bb characteristics according to IEC standard 61869-2 bb single primary winding bb double secondary winding for measurement and protection. Short-time withstand current Ith (kA)
I1n (A) Ith (kA) t (s) Measurement and protection Measurement and protection 1A 1A 5A 5A 1000 25 1 30 VA - class 0.5 10 VA - 5P20 30 VA - class 0.5 10 VA - 5P20 1250
PE55661
Low Power Current Transformer (LPCT) CLP2 bb characteristics according to IEC standard 60044-8 bb large primary current range bb direct output voltage for measurement and protection bb RJ45-8 pts secondary connector bb insulation level 24 kV.
Minimum rated primary current Rated nominal primary current Rated extended primary current Rated nominal secondary output Accuracy class for measurement Accuracy class for protection Accuracy limit factor Rated short time thermal current Highest voltage (Um) Rated power-frequency withstand 5A 100 A 1250 A 22.5 mV 0.5 5P 400 40 kA 1s 24 kV 50 kV
Low Power Current Transformer (LPCT) TLP130 bb characteristics according to IEC standard 60044-8 bb large primary current range bb direct output voltage for measurement and protection bb RJ45-8 pts secondary connector bb insulation level 0.72 kV bb internal diameter 130 mm.
Minimum rated primary current Rated nominal primary current Rated extended primary current Rated nominal secondary output Accuracy class for measurement Accuracy class for protection Accuracy limit factor Rated short time thermal current Highest voltage (Um) Rated power-frequency withstand 5A 100 A 1250 A 22.5 mV 0.5 5P 250 25 kA 1s 0.72 kV 3 kV
PE57162
AMTED398078EN
71
PE57222
PE57162
TLP 130
Minimum rated primary current Rated extended primary current Secondary output Accuracy class for measurement Accuracy class for protection Accuracy limit factor Rated short time thermal current Highest voltage (Um) Rated power-frequency withstand 5A 1250 A 22.5 mV - 100 A 0.5 5P 250 25 kA 1 s 0.72 kV 3 kV
TLP 190
5A 2500 A 22.5 mV - 100 A 0.5 5P 400 40 kA 1 s 0.72 kV 3 kV
72
AMTED398078EN
Units CM b
CVM b
TM
b b
VRQ2
VRC2
PE55648
Transformer VRM3-n/S2 (phase-to-earth and protected by fuses 0.3 A) 50 or 60 Hz bb characteristics according to IEC standard 61869-3.
Rated voltage (kV) Primary voltage (kV) Secondary voltage (V) First secondary Thermal power (VA) Accuracy class Rated output for single primary (VA) Second secondary Thermal power (VA) Accuracy class Rated output 12 10/3 200 0.5 30-50 100 3P 50 17.5 15/3 24 20/3
100/3 - 100/3
AMTED398078EN
73
VRC1
DE53562
DE58408
Surge arresters
For units IM500, DM1-A, DM1-W, GAM, DMV-A*, DMVL-A
In (A) Un (kV) 400/630 7.2 10 12 17.5 24 Note: the rated voltage of the surge arrester is according to units rated voltage. (*) limited up to 17.5 kV for DMV-A circuit breaker cubicles.
74
AMTED398078EN
PE57223
PE57224
For units TM
Transformer VRC3/S1 (phase-to-phase) bb single primary winding bb single secondary bb characteristics according to IEC standard 61869-3
Rated voltage (kV) Primary voltage (kV) Secondary voltage (V) Thermal power (VA) 36 30 220 1000
DE58408
Surge arresters
For units IM, DM1-A, SM, GAM2
In (A) Un (kV) 630 36
AMTED398078EN
75
The current rating of fuses installed in units depends on: bb motor current rating In bb starting current Id bb frequency of starts. The fuses rating is calculated such that a current equal to twice the starting current does not blow the fuse within period equal to the starting time. The adjacent table indicated the ratings which should be used, based on the following assumptions: bb direct on-line startup bb Id/In y 6 bb pf = 0.8 (P y 500 kW) or 0.9 (P > 500 kW) bb = 0.9 (P y 500 kW) or 0.94 (P > 500 kW). The indicated values are for Fusarc fuses (to DIN standard 43-625). Example: Consider a 950 kW motor at 5 kV.
In = P pf = 130 A
30 3
250 200 200 160 160 160 125 100 100 100 80
Id = 6 x Ie
3.3 1100 942 785 6.6 628 565 502 439 377 314 251 188 126
Ie
183 157 131 105 94 84 73 63 52 42 31 21
3
250 250 200 160 160 125 125 100 100 100 80 50
6
250 250 200 160 160 160 125 125 100 100 100 50
3
250 250 200 160 160 160 125 100 100 100 100 63
6
250 200 200 160 160 160 125 100 100 100 80
6
250 250 200 160 160 160 160 125 100 100 80
Id = 6 x In = 780 A Then select the next higher value, i.e. 790 A. For six 5-second starts per hour, select fuses rated 200 A.
Note: the same motor could not be protected for 12 starts per hour since the maximum service voltage for the required 250 A rated fuses is 3.3 kV.
Fuse selection method: bb if Id 6 x Ie, use Id to select the fuses bb if Id < 6 x Ie, use Ie to select the fuses.
Note: Fuses are 292 mm long (Fusarc fuses). Fuses are only for short circuit protection. For 250 A fuses, it is necessary to delay the opening of the contactor.
76
AMTED398078EN
Protection of transformers
Fuse ratings for SM6 protection units such as PM, QM, QMB and QMC depend, among other things, on the following criteria: bb service voltage bb transformer rating bb fuse technology (manufacturer) Different types of fuses with medium loaded striker may be installed: vv Solefuse fuses as per standard UTE NCF 64.210 vv Fusarc CF fuses as per IEC 60.282.1 recommendation and dimensions are related to DIN 43.625 standard. For fuse-switch combination unit type QM, QMB, QMC, refer only to the selection table and reference list of fuses. For all other type of fuses, consult us. Example: for the protection of a 400 kVA transformer at 10 kV, select either Solefuse fuses rated 43 A or Fusarc CF fuses rated 50 A.
PE57161
The color code is linked to the rated voltage of the fuse Rating in A - no overload at 5C < t < 40C, 1000 m altitude.
Service Transformer rating (kVA) Rated voltage 25 50 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 voltage (kV) (kV) Solefuse (UTE NFC standards 13.100. 64.210) 5.5 6.3 16 31.5 31.5 63 63 63 63 63 7.2 10 6.3 6.3 16 16 31.5 31.5 31.5 63 63 63 63 15 6.3 6.3 16 16 16 16 16 43 43 43 43 43 63 20 6.3 6.3 6.3 6.3 16 16 16 16 43 43 43 43 43 63 24 Solefuse (general case, UTE NFC standard 13.200) 3.3 16 16 31.5 31.5 31.5 63 63 100 100 7.2 5.5 6.3 16 16 31.5 31.5 63 63 63 80 80 100 125 6.6 6.3 16 16 16 31.5 31.5 43 43 63 80 100 125 125 10 6.3 6.3 16 16 16 31.5 31.5 31.5 43 43 63 80 80 100 12 13.8 6.3 6.3 6.3 16 16 16 16 31.5 31.5 31.5 43 63 63 80 17.5 15 6.3 6.3 16 16 16 16 16 31.5 31.5 31.5 43 43 63 80 20 6.3 6.3 6.3 6.3 16 16 16 16 31.5 31.5 31.5 43 43 63 24 22 6.3 6.3 6.3 6.3 16 16 16 16 16 31.5 31.5 31.5 43 43 63 Fusarc CF and SIBA(1) (general case for QM, QMB and QMC cubicle according to IEC 62271-105) 3.3 16 25 40 50 50 80 80 100 125 125 160(1) 200(1) 7.2 5 10 16 31.5 40 40 50 63 80 80 125 125 160(1) 5.5 10 16 31.5 31.5 40 50 50 63 80 100 125 125 160(1) 160(1) 6 10 16 25 31.5 40 50 50 63 80 80 125 125 160(1) 160(1) 6.6 10 16 25 31.5 40 50 50 63 80 80 100 125 125 160(1) 10 6.3 10 16 20 25 31.5 40 50 50 63 80 80 100 100 125(1) 200(1) 12 11 6.3 10 16 20 25 25 31.5 40 50 50 63 80 100 100 125(1) 160(1) 13.8 6.3 10 16 16 20 25 31.5 31.5 40 50 50 63 80 80 100(1) 125(1) 125(1) 17.5 15 6.3 10 10 16 16 20 25 31.5 40 50 50 63 80 80 100(1) 125(1) 125(1) 20 6.3 6.3 10 10 16 16 25 25 31.5 40 40 50 50 63 80 100(1) 125(1) 24 22 6.3 6.3 10 10 10 16 20 25 25 31.5 40 40 50 50 80 80 100(1) (2) Fusarc CF for dry type transformers 30 10 10 16 20 25 31.5 31.5 50 50 63 63 36 31.5 10 10 16 20 25 25 31.5 50 50 63 63 33 6.3 10 16 20 25 25 31.5 40 50 50 63 34.5 6.3 10 16 20 25 25 31.5 40 50 50 63 Fusarc CF oil immersed type transformers (2) 30 10 10 16 20 25 31.5 31.5 40 40 50 63 36 31.5 10 10 16 20 25 31.5 31.5 40 40 50 63 33 10 10 16 20 25 25 31.5 31.5 40 40 50 34.5 10 10 16 20 25 25 31.5 31.5 40 40 50
(1) SIBA fuses (2) This selection table has been prepared according to the technical characteristics of France Transfo. The characteristics of transformers and fuses may change according to manufactures and standards. AMTED398078EN
77
Protection of transformers
Fuses dimensions
DE53563
(mm) 55 55 55 55
Weight (kg) 2 2 2 2
35
DE57467
450
23
35
24
SIBA
DE57467
45
Ur (kV) 7.2 12
(mm) 85 85 67 85 85 85 85 85
33
33
23 17.5 24
78
AMTED398078EN
Interlocks
Switch units
bb the switch can be closed only if the earthing switch is open and the access panel is in position. bb the earthing switch can be closed only if the switch is open. bb the access panel for connections can be opened only if the earthing switch is closed. bb the switch is locked in the open position when the access panel is removed. The earthing switch may be operated for tests. bb the disconnector(s) can be closed only if the circuit breaker is open and the front panel is locked (interlock type 50). bb the earth switch(es) can be closed only if the disconnector(s) is/are open. bb the access panel for connections can be opened only if: vv the circuit breaker is locked open, vv the disconnector(s) is/are open, vv the earth switch(es) is/are closed.
Functional interlocks
These comply with IEC recommendation 62271-200 and EDF specification HN 64-S-41 (for 24 kV). In addition to the functional interlocks, each disconnector and switch include: bb built-in padlocking capacities (padlocks not supplied) bb four knock-outs that may be used for keylocks (supplied on request) for mechanism locking functions.
Circuit-breaker units
Units
Unit interlock
Interlock
A1 C1 C4 A3 b b b A4 b A5 50 b 52 P1 b P2 P3 P5
IM, IMB, IMC PM, QM, QMB, QMC, DM1-A, DM1-D, DM1-W, DM1-Z, DM1-S, DMV-A, DMV-D, DMV-S, DMVL-A, DMVL-D CVM NSM GAM SM DM2 b
b b b b
b b b b b b
Note: it is possible to lock the disconnector(s) in the open position for no-load operations with the circuit breaker.
DE53565
A1 type
O
Key-type interlocks
Outgoing units
Aim: bb to prevent the closing of the earthing switch on a transformer protection unit unless the LV circuit breaker is locked in open or disconnected position.
DE53566
C1 type
bb to prevent the access to the transformer if the earthing switch for transformer protection has not first been closed.
S
DE53567
C4 type
O
S O
bb to prevent the closing of the earthing switch on a transformer protection unit unless the LV circuit breaker is locked in open or disconnected position. bb to prevent the access to the transformer if the earthing switch for transformer protection has not first been closed.
MT20240EN
AMTED398078EN
79
Interlocks
DE53568
A3 type
O
Ring units
Aim: bb to prevent the closing of the earthing switch of a load-side cubicle unless the line-side switch is locked open.
O
DE53569
A4 type
O O
DE53570
A5 type
O
bb to prevent the closing of the earthing switch of the casing unit unless the downstream and the upstream switches are locked in the open position.
O S
MT20240EN
80
AMTED398078EN
Interlocks
DE53572
P1 type
O X
bb to prevent the closing of an earthing switch if the switch of the other unit has not been locked in the open position.
DE53573
P2 type
X O O
bb to prevent on-load operation of the disconnector unless the switch is locked open bb to prevent the closing of the earthing switches unless the disconnector and the switch are locked open.
DE53574
P3 type
AX O
bb to prevent on-load operation of the disconnector unless the switch is locked open bb to prevent the closing of the earthing switches with the unit energised, unless the disconnector and the switch are locked open bb to allow off-load operation of the switch.
DE53575
P5 type
P
bb to prevent the closing of the earthing switch of the incoming unit unless the disconnector and the switch is locked open.
DE53571
50 type
O O
Functional interlocks
Prevents bb on-load switching of the disconnectors. Allows bb off-load operation of the circuit breaker with the disconnectors open (double isolation). bb off-load operation of the circuit breaker with the disconnector open (single isolation).
DE59203
Type 52
O O
Prevents bb on-load switching of the disconnectors. Allows bb off-load operation of the contactor with the disconnectors open (double isolation). bb off-load operation of the contactor with the disconnector open (single isolation).
MT20240EN
AMTED398078EN
81
82
AMTED398078EN
Connections
Contents
84 84 85 85 86 87 88 89 89 90 90
AMTED398078EN
83
Connections
PE50775
PE57840
Round connector
PE50776
Square connector
Note: b The cable end terminals, covered by a field distributor, can be square, b PM/QM type cubicle, round end connections 30 mm max.
84
AMTED398078EN
Connections
630 A
IM, NSM-cables, NSM-busbars SM IMC PM, QM QMC CVM DM1-A DMVL-A DMV-S DM1-W GAM2 GAM DMV-A DM1-S 945 945 400 400 400 430 430 430 320 370 760 470 320 543
1250 A
945
320
DE58678
CVM
GAM, GAM2
DE58679 DE53581
H
H
200
200 420
275
DMV-A (1250 A)
H 330
333
789
145 145
445
371,5
510,5
X 313
AMTED398078EN
85
Connections
DE53585
b Through trenches: the trench depth P is given in the following table for usual dry single-core cables type (for tri-core cables consult us). b With stands: to reduce depth P or avoid trenches, by placing the units on 400 mm concrete footings. b With floor void: the trench depth is given in the following table for usual types of cables. 630 A
Cable section (mm2) All cubicles expect ... 12.5 kA/1s S < 120 330 16 kA/1s 550 550 Other cubicles DMVA 12-16 kA/1s 550 800 CVM 12.5 kA/1s 330 16 kA/1s 550 DM1A, DM1S, DM1W, DMVLA 12.5 kA/1s 16 kA/1s 550 SM, GAM 12-16 kA/1s 1000 DM1A, DMV-A, DM1-W 12-16 kA/1s
1250 A
Depth P (mm)
330 1400 120 < S < 240 330 S > 400 Opposite to Under the 550 circuit breaker: circuit breaker: 330 450
187.5
630 A units
100
100
P 480
445 P P
100 P
600 740 50
600 740 50
840 740 50
600 740 50
86
AMTED398078EN
Connections
100
P2
P
P3
P1
600 25
25
25
IM
IM QMC
IM
IM IM
DM1
DM1 IM
DE57180
PE50797
On each 630 A unit of the range, except those including a low-voltage control cabinet and EMB compartment, the connection is made with dry-type and single-core cables.
Remarks: bb Not available for internal arc IEC 62271-200. bb Not available in 1250 A.
DE57182
AMTED398078EN
87
Connections
550 minimu m
70
50 740 70 50
110 min
. 930
90 min . 120
Installation with cable trench for 12.5 kA 1s and 16 kA 1s downwards exhaust for 16 kA 1s and 20 kA 1s upwards exhaust
bb Position of fixing holes b depends on the width of the unit:
Cubicle width (mm) 125 375 500 625 750 b (mm) 95 345 470 595 720 2150 minimu m
DE57196
4 x M8
330 minimu m
100 50
740 600
88
AMTED398078EN
Connections
The ageing resistance of the equipment in an MV/LV substation depends on three key factors:
b the need to make connections correctly New cold fitted connection technologies offer ease of installation that favours resistance over time. Their design enables operation in polluted environments under severe conditions. b the impact of the relative humidity factor The inclusion of a heating element is essential in climates with high humidity levels and with high temperature differentials. b ventilation control The dimension of the grills must be appropriate for the power dissipated in the substation. They must only traverse the transformer area. Network cables are connected: bb on the switch terminals bb on the lower fuse holders bb on the circuit breakers connectors. The bimetallic cable end terminals are: bb round connection and shank for cables y 240 mm2. Crimping of cable lugs to cables must be carried out by stamping. The end connectors are of cold fitted type Schneider Electrics experience has led it to favour this technology wherever possible for better resistance over time. The maximum admissible copper(*) cable cross section: bb 2 x (1 x 240 mm2 per phase) for 1250 A incomer and feeder cubicles bb 240 mm2 for 630 A incomer and feeder cubicles bb 95 mm2 for transformer protection cubicles with fuses. Access to the compartment is interlocked with the closing of the earthing disconnector. The reduced cubicle depth makes it easier to connect all phases. A 12 mm pin integrated with the field distributor enables the cable end terminal to be positioned and attached with one hand. Use a torque wrench set to 50 mN.
(*) Consult us for alu cable cross sections
Note: the unit and the cables requiring the greatest depth must be taken into account when determining the depth P for single-trench installations. In double-trench installations must be taken into account to each type of unit and cable orientations.
All units through trenches bb the trench depth P is given in the table opposite for commonly used types of cables.
Trench diagrams
DE59723 DE59724 DE59725
100
100
100
P2 300 1000
200 1000
P1 P2
P2 300 1000
200
QM IM IM
100
QM IM IM
100
100
QM IM IM
100 100
200
100
100
100
AMTED398078EN
89
Connections
Side view
IM, SM units
DE59727 DE57183
QM, PM units
DE57184
DM1-A units
DE59730
GAM2 unit
1210 400 350 700 350 350 700 350 540 456 632
Front view
DE57185
IM, SM
QMC
GAM
GAM2
QM, PM
DM1-A
490
455
375
375
510
90
AMTED398078EN
Installation
Contents
Dimensions and weights for SM6-24 Units dimensions for SM6-24 Civil engineering for SM6-24 Layout examples for SM6-24 Dimensions and weights for SM6-36 Civil engineering for SM6-36 Layout examples for SM6-36
92 93 95 96 97 98 99
AMTED398078EN
91
Installation
DE57186
90 Exhaust channelling
(1) Add to height 450 mm for low-voltage enclosures for control/monitoring and protection functions. To ensure uniform presentation, all units (except GIM and GEM) may be equipped with low-voltage enclosures. (2) Depending on the busbar configuration in the VM6 unit, two types of extension units may be used: b to extend a VM6 DM12 or DM23 unit, use an extension unit with a depth of 1060 mm b for all other VM6 units, a depth of 930 mm is required. (3) For the 1250 A unit.
92
AMTED398078EN
Installation
IM, IMB, PM, QM, QMB, SM, IMC, QMC, CM, CM2
DE58661 DE58662
GBM, GAM2
450
1600
1600
1600
90
840
30 70
90
840
30 70
90
840
30 70
GAM
DE58664 DE58665
GIM
DE58666
GEM
1600
1600
1600
90
840
30 70
930
930 1060
GBC-A, GBC-B
DE58667 DE58668
1600
1600
90
840
100
90
840
30 70
AMTED398078EN
93
Installation
450
503
450
1600
1600
1600
90
840
200 100
90
840
90
DMV-A 630 A
DE58672 DE58673
DMV-A 1250 A
1680
1680
DMV-D
DE58674 DE58675
DMV-S
1680
1600
90 85 840 100
94
AMTED398078EN
Installation
Fixing of units
With each other The units are simply bolted together to form the MV switchboard (bolts supplied). Busbar connections are made using a torque wrench set to 28 mN. On the ground bb For switchboards comprising up to three units, the four corners of the switchboard must be secured to the ground with using: vv M8 bolts (not supplied) screwed into nuts set into the ground using a sealing pistol vv screw rods grouted into the ground. bb For switchboards comprising more than three units, each unit may be fixed to the ground bb In circuit-breaker or contactor units, fixing devices are installed on the opposite side of the switchgear.
AMTED398078EN
95
Installation
10
930
25 (minimum)
300 (minimum)
300 (minimum)
930
300 (minimum)
Evacuation duct
To enable the evacuation of gases by the top, users must install a conduit fixed to the coupling flange at right or left of the switchboard. For IP3X protection performance, a flap must be installed with this coupling flange on the lateral side of the cubicle duct. The end of the duct must block water, dust, moisture, animals, etc. from entering and at the same time enable the evacuation of gases into a dedicated area through a device situated at the outer end of the duct (not supplied). Evacuation duct example The evacuation duct must be made of metal sheet of sufficient thickness to withstand pressure and hot gases.
PE57235
Installation of a switchboard classified IAC: A-FL & A-FLR with upwards exhaust left side (ceiling height u 2150 mm)
DE58651
1600
96
AMTED398078EN
Installation
(1) The depth measures are given for the floor surface. (2) The depth in these units are 1615 mm with the enlarged low voltage compartment. (3) The depth in these units are 1500 mm with the standard low voltage compartment.
Dimensions
IM, SM, IMC, QM, PM, IMB, GBM, GAM, GAM2, GBC-A,GBC-B QMB, QMC units
DE59662 DE59663
DE59664
100
215
215
2250
2250
2250
1400
32
1400
32
1400
32 230
AMTED398078EN
97
Installation
Units may be installed on ordinary concrete grounds, with or without trenches depending on the type and cross-section of cables. Required civil works are identical for all units.
A B 50
150
DE5961
Fixing of units
With each other The units are simply bolted together to form the MV switchboard (bolts supplied). Busbar connections are made using a torque wrench set to 28 mN. On the ground bb for switchboards comprising up to three units, the four corners of the switchboard must be secured to the ground using: vv bolts (not supplied) screwed into nuts set into the ground using a sealing pistol vv screw rods grouted into the ground bb for switchboards comprising more than three units, the number and position of fixing points depends on local criteria (earthquake withstand capacities, etc.) bb position of fixing holes depends on the width of units.
Unit type IM, IMC, IMB, QM, PM, SM, CM, CM2, TM GBC-A, GBC-B, GBM, GAM2, IMB, GAM, QMB DM1-A, DM1-D, QMC DM2 GIM A (mm) 750 1000 1500 250 B (mm) 650 900 1400 150
14.2 x 25
98
AMTED398078EN
Installation
Side view
100
100
100
100
Minimum required dimensions (mm) (1) In case of upper incoming option: it must be 2730 mm (no internal arc withstand performance available) (2) In case of upper incoming option: it must be 2830 mm (no internal arc withstand performance available)
Top view
DE59667
100
AMTED398078EN
99
100
AMTED398078EN
Contents
Appendices
Trip curves for VIP 300 LL or LH relays Trip curves for VIP 35 relays Fusarc CF fuses Solefuse fuses
102 103 104 105
Order form
SM6 - Switching
Switching Automatic Transfer System 106 106 107 108 108 110 111 112 113 114 115 116 117
SM6 - Protection
Circuit breaker Fuse switch Vacuum contactor (Direct Motor Starter) for 24 kV
SM6 - Metering SM6 - Other functions SF1 - Lateral disconnectable or withdrawable SFset - Lateral disconnectable for SM6-24 Evolis - Frontal fixed version for SM6-24 (up to 17.5 kV) Evolis - Lateral disconnectable version for SM6-24 (up to 24 kV)
AMTED398078EN
101
Appendices
t>
t>
t >>
t >>
Is 1.2 Is
10 Is
I >>
Is 1.2 Is 10 Is
I >>
VI curve
t (s) 100
100
10
10
1 0.6 0.4 0.3 0.2 0.15 0.1 0.07 0.05 I/Is 1 1.2 10 100
0.1
0.1
0.6 0.4 0.3 0.2 0.15 0.1 0.07 0.05 I/Is 1 1.2 10 100
0.01
0.01
EI curve
t (s)
DE53616
RI curve
t (s) 10
1000
100
1 10 0.6 0.4 0.3 1 0.1 0.6 0.4 0.3 0.2 0.15 0.1 0.07 0.05 1 1.2 10 0.2 0.15 0.1 0.07 0.05
0.1
0.01
I/Is 100
0.01 1 10
I/Is 100
102
AMTED398078EN
Appendices
100
The trip curve shows the time before the relay acts, to which must be added 70 ms to obtain the breaking time.
10
0.1
AMTED398078EN
103
Appendices
Fusarc CF fuses
DE53618
100
250 A
Current (A)
8 6 4
Ia
8 1.
Ik
Is
Ik
10 8 6 4
1 8 6 4
4A
0.1
0.1
10
100
104
AMTED398078EN
Appendices
Solefuse fuses
DE53620
100
100 A 125 A
Current (A)
8 6 4
Ia
8 1.
Ik
Is
Ik
2
125 A 100 A 80 A 63 A 43 A 31.5 A 25 A 20 A 16 A 10 A 6.3 A
10 8 6 4
1 8 6 4
0.1 0.1
10
100
AMTED398078EN
105
Order form
SM6
Switching
Only one of the boxes (ticked X or filled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.
Basic cubicle
Rated voltage Ur Service voltage Short-circuit current Isc Rated current Ir Internal arc withstand Type of cubicle 24 kV 36 kV SM 375 IM 375 IM 500 IM 750 IMC 750 Middle IMC 500 12.5 kA 1s for SM6-24
Quantity (kV) (kV) (kA) (A) 16 kA 1s for SM6-36 IMB 375 IMB 750 Last on right Right 36 kV
Left (impossible as first cubicle of switchboard) Cable connection by the bottom (1x single core, cable maxi 240 mm2)
Options
Common options
Replacement of CIT by Electrical driving motorization and/or coil voltage (not applicable on SM cubicle) 24 Vdc 32 Vdc 48 Vdc 60 Vdc Signalling contact Interlocking 2 O & 2 C on SW CI1 110 Vdc 120-125 Vdc 137 Vdc 220 Vdc CI2 120/127 Vac (50 Hz) 220/230 Vac (50 Hz) 120/127 Vac (60 Hz) 220/230 Vac (60 Hz)
1 C on SW and 1O & 1C on ES (not applicable on SM cubicle) 2 O & 3 C on SW and 1O & 1C on ES Flat key type P1 SM6-SM6 On earthing switch Cubicle no. P3 SM6-SM6 Flair 23DV zero sequence Flair 22D Flair 23DM
Tubular key type For all cubicle (except SM) A4 Localisation of 2nd lock for A3 Localisation of 2nd lock for A4 SM cubicle only A3 SM6-SM6 On switch
P2 SM6-SM6 Replacement of 630 A upper busbar by 1250 A (not possible for IMB) Digital ammeter or fault current indicator Visibility of main contacts Pressure indicator device Pressure switch AMP 21D Flair 21D
Analogic manometer without visibility of main contacts Analogic manometer with visibility of main contacts
SM6-24 options
Remote control signalling 2 lights 2 lights and 2 PB 2 lights and 2 PB + 1 switch 220 V
Voltage of the lights (must be the same than electrical driving mechanism) 24 V 48 V 110/125 V Roof configuration (A, B or C only one choice possible) A - Cable connection by the top (cable maxi 240 mm2 with VPIS) Single core B - Low voltage control cabinet (h = 450 mm) C - Wiring duct Cable connection by the bottom (not applicable on IMB, cable maxi 240 mm2) Three core 50 W heating element Surge arresters for IM 500 7.2 kV 10 kV Operation counter CTs for IMC (quantity) 12 kV 17.5 kV 24 kV 3 20 kA 1s Upwards Single core 2 x single core 2 x single core With unpunched door
2 1 Busbar field distributors for severe conditions (only for 630 A) Internal arc version (not possible with top incomer option) 16 kA 1s Gaz exhaust direction Downwards (only for 16 kA 1s)
SM6-36 options
Cable connection by the top (single core cable maxi 240 mm2 with VPIS) Cable connection by the bottom (2 x single core, cable maxi 240 mm2, not applicable on IMC) Surge arresters (not applicable on IMB, IMC cubicles) 36 kV
106
AMTED398078EN
Order form
SM6
Switching
Only one of the boxes (ticked X or filled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.
Basic cubicle
Rated voltage Ur Service voltage Short-circuit current Isc Rated current Ir Internal arc withstand Type of cubicle/upper busbar for 24 kV Ir = 630 A, Ir busbar = 400 A Ir = 630 A, Ir busbar = 630 A Ir = 630 A, Ir busbar = 1250 A Position in the switchboard First on left Incoming bottom busbar for NSM busbar Middle NSM busbar NSM busbar 12.5 kA 1s for SM6-24
Left Cable connection by the bottom (cable maxi 240 mm2) for NSM cable Three core on both Stand by source Utility with paralleling Control unit HMI language French English Spanish Portuguese Single core on both
2 x single core on both Generator without paralleling Utility without paralleling Chinese
Options
Common options
Signalling contact Operation counter Interlocking SM6-SM6 1 x P1 2 x P1 1 x A3 2 x A3 Right cubicle Left cubicle Control and monitoring Protocol type Modem type DNP3 FFSK PSTN IEC 101/204 RS485 GSM Modbus (by default) RS232 (by default) FSK Right cubicle On switch On switch On switch Tubular key type Right cubicle Flat key type Left cubicle Right and left cubicle Left cubicle On earthing switch On earthing switch On earthing switch 1C on SW and 1O & 1C on ES
SM6-24 options
2 heating elements Busbar field distributors for severe conditions (only for 630 A) Internal arc version (not possible with top incomer option) 16 kA 1s Gaz exhaust direction Downwards (only for 16 kA 1s) 20 kA 1s Upwards
AMTED398078EN
107
Order form
SM6
Protection
Circuit breaker
Only one of the boxes (ticked X or filled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.
Basic cubicle
Rated voltage Ur Service voltage
Quantity
Common 24/36 kV
(kV) (kV) (kA) (A) 12.5 kA 1s for SM6-24 DM1-A 750 DM1-S 750 For SFset circuit breaker For Evolis frontal 630 A CB For Evolis lateral 630 A CB 36 kV For SF1 circuit breaker Position in the switchboard Circuit breaker Current transformers (CT) and LPCTs Cable connection by the bottom (1x single core, cable maxi 240 mm2) 36 kV DM1-A 1000 First on left DMV-A DM1-D left 750 DM1-Z 750 DM2 left 750 DM1-D left 750 DMV-S DMVL-A DM1-D left 1000 DM2 left 1500 Middle 16 kA 1s for SM6-36 DM1-D right 750 DM1-W 750 DM2 right 750 DM1-D right 750 DMV-D right DMVL-D DM1-D right 1000 DM2 right 1500 Last on right See specific order form See specific order form
Short-circuit current Isc Rated current Ir Internal arc withstand 24 kV For SF1 circuit breaker
Basic SM6-24
Busbar (Ir u Ir cubicle) For DM1-A, DM1-S, DM1-W, DMVL-A, DMVL-D ,DM1-D, DM2 400 A For DM1-A, DM1-D, DM1-W, DM1-Z For DMV-A, DMV-D For DMV-S Protection For DM1-S, DMV-S For DM1-S For DMV-A, DMV-D Control for DMV-A and DMV-D Local (shunt trip coil compulsory) Remote (opening coil and closing coil compulsory) Local and remote (opening coil and closing compulsory) Voltage of the auxiliaries Voltage of signalling 48/60 Vdc 48/60 Vdc 110/125 or 220/250 Vdc 110/130 or 220/240 Vac (50 Hz) 110/125 Vdc 220/250 Vdc 220/240 Vac (50 Hz) 110/130 Vac (50 Hz) Cable connection by the bottom For DM1-A, DM1-W, DMVL-A 3 x single core cable maxi 240 mm2 Current sensors CT 6 x single core cable maxi 240 mm2 LPCT ring type for DM1-A 630 A LPCT MV type for DM1-D VIP35 with CRc Sepam series 10 with CRa VIP300LL with CRa VIP300LL with CRb Sepam series 10 with CRb Sepam series 20/40 630 A 630 A 630 A 1250 A 1250 A 1250 A
Basic SM6-36
Current sensors CT LPCT ring type for DM1-A 630 A See following page
Options
108
AMTED398078EN
Order form
SM6
Protection
Circuit breaker
Only one of the boxes (ticked X or filled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.
Options
Interlocking
Common options
Tubular key type Not applicable on DM2 Signalling contact A1 C1 Flat key type C4 2 O & 2 C on SW (not applicable with VTs) 2 O & 3 C on SW and 1 O & 1 C on ES (not applicable with VTs) VTs (not applicable for DM1-S, DMV-S) 1 O & 2 C on SW (available only on cubicle with VTs) See specific order form
SM6-24 options
Roof configuration (not applicable on DMV-A, DMV-S, DMV-D) (A, B or C only one choice possible) A - Cable connection by the top (cable maxi 240 mm2 with VPIS) Single core DM2 B - Low voltage control cabinet DM2 C - Wiring duct Surge arrester 50 W heating element Replacement of 630 A upper busbars 400-630 A by 1250 A Busbar field distributors for severe conditions (only for 630 A) Internal arc version (not possible with top incomer option) 16 kA 1s Gaz exhaust direction Downwards (only for 16 kA 1s) 20 kA 1s Upwards DM2 Other cubicles 1 cabinet 1 set 1 set 2 cabinets 2 sets 1 set 2 x single core 2 sets
SM6-36 options
Cable connection by the top (single core cable maxi 240 mm2 with VPIS) Cable connection by the bottom (for DM1-A only) 3 x 2 x single core cable maxi 240 mm2 Surge arrester Sepam relay protection 36 kV See specific order form
AMTED398078EN
109
Order form
SM6
Protection
Fuse switch
Only one of the boxes (ticked X or filled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.
Basic cubicle
Rated voltage Ur Service voltage Short-circuit current Isc Rated current Ir Internal arc withstand Type of cubicle SM6-24 SM6-36 QM 375 QM 500 QM 750 Position in the switchboard Quantity of CTs Direction of lower busbars for QMB Left Cable connection by the bottom (1x single core, cable maxi 240 mm2) QMB 750 QMC 1000 QMB 375 QMC 625 12.5 kA 1s for SM6-24
Quantity (kV) (kV) (kA) (A) 16 kA 1s for SM6-36 PM 375 PM 750 Last on right 3 Right 36 kV
Middle First on left Current transformers for QMC 24 kV (to see price structure) 1 2
Options
Common options
Fuses (see fuse price structure) Replacement of mechanism Electrical driving motorization 24 Vdc 32 Vdc 48 Vdc 60 Vdc Shunt trip Opening (on CI1) 24 Vdc 32 Vdc 48 Vdc 60 Vdc Auxiliary contact signalling 2 O & 2 C on SW Interlocking A1 C1 C4 110 Vdc 120-125 Vdc 137 Vdc 220 Vdc Service voltage y 12 kV CIT by CI1 (only for PM) 120/127 Vac (50 Hz) 220/230 Vac (50 Hz) 120/127 Vac (60 Hz) 220/230 Vac (60 Hz)
Closing and opening (on CI2) 110 Vdc 120-125 Vdc 137 Vdc 220 Vdc 120/127 Vac (50 Hz) 220/230 Vac (50 Hz) 120/127 Vac (60 Hz) 220/230 Vac (60 Hz) 380 Vac (50/60 Hz) 1C on SW and 1O & 1C on ES 2 O & 3 C on SW and 1O & 1C on ES Flat key type
Replacement of 630 A upper busbar by 1250 A (not possible for QMB) Blown fuse signalling contact (for QM, QMB, QMC) Visibility of main contacts Pressure indicator device Pressure switch Analogic manometer without visibility of main contacts Analogic manometer with visibility of main contacts CI1 by CI2 (only for QM)
SM6-24 options
Replacement of mechanism Remote control signalling (for QM only) 2 lights 2 lights and 2 PB 2 lights and 2 PB + 1 switch Voltage of the lights (must be the same than electrical driving mechanism) 24 V 48 V 110/125 V 220 V Blown fuse signalling contact (mechanical indication PM, electrical for the other cubicles) Roof configuration (A, B or C only one choice possible) A - Cable connection by the top (cable maxi 240 mm2 with VPIS) Single core B - Low voltage control cabinet (h = 450 mm) C - Wiring duct 50 W heating element Operation counter Digital ammeter (not applicable for QMB) Busbar field distributors for severe conditions (only for 630 A) Internal arc version (not possible with top incomer option) 16 kA 1s Gaz exhaust direction Downwards (only for 16 kA 1s) 20 kA 1s Upwards AMP21D 2 x single core With unpunched door
SM6-36 options
Replacement of mechanism CIT by CI2 (only for PM) AMTED398078EN Cable connection by the top (single core cable maxi 240 mm2 with VPIS)
110
Order form
SM6
Protection
Basic cubicle
Rated voltage Ur Service voltage Short-circuit current Isc (6.3 kA without fuse) Rated current Ir (max. 400 A without fuse) Internal arc withstand Position in the switchboard Busbar Ir Phase current sensors Key interlockings for 52 type First on left 400 A 1 CT Middle 630 A 2 CT
Quantity (kV) (kV) (kA) (A) 12.5 kA 1s Last on right 1250 A 3 CT 3 LPCT ring type Tubular key type Flat key type
7.2
Options
MV fuses 25 A 31.5 A 40 A 50 A 200 A 63 A 250 A 80 A 100 A 125 A 160 A Busbar field distributors for severe conditions (only for 630 A) Key interlockings for C1 type Voltage transformer (quantity) Tubular key type
1 Internal arc version (not possible with top incomer option) Gaz exhaust direction
Contactor
Vacuum contactor Open release Closing coil Magnetic hold 48 Vdc 110 Vac/dc 220 Vac/dc Mechanical latching 125 Vdc 120 Vac/dc 240 Vac/dc 250 Vdc 125 Vac/dc 250 Vac/dc
AMTED398078EN
111
Order form
SM6
Metering
Only one of the boxes (ticked X or filled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.
Basic cubicle
Rated voltage Ur Service voltage
Quantity
Common SM6-24/SM6-36
(kV) (kV) (kA) (A) 12.5 kA 1s for SM6-24 CM CM CM CM 750 CM2 CM2 CM2 TM TM TM 16 kA 1s for SM6-36 GBC-A GBC-A GBC-A GBC-A CM2 750 TM 750 Position in the switchboard First on left Direction of lower busbars for GBC-A Signalling contact (for CM, CM2 and TM only) Fuses (for CM, CM2 and TM only) Cable connection by the bottom (1x single core, cable maxi 240 mm2) SM6-36 Middle Left GBC-B GBC-B GBC-B GBC-B GBC-A 750 GBC-B 750 Last on right Right 1 O and 1 C on SW See fuse price structure
Short-circuit current Isc Rated current Ir Internal arc withstand Type of cubicle/upper busbar for SM6-24 Ir = 630 A, Ir busbar = 400 A Ir = 630 A, Ir busbar = 630 A Ir = 630 A, Ir busbar = 1250 A Ir = 1250 A, Ir busbar = 1250 A Type of cubicle for SM6-36
Basic SM6-24
VTs for GBC (to see price structure) CTs for GBC (to see price structure) Ratio choice for GBC Protections 1 secondary 2 secondaries 1 high secondary 1 low secondary See specific order form Phase/phase Quantity 1 Phase/earth 2 3
Basic SM6-36
Voltage transformers
Options
SM6-24 options
Roof configuration (A, B or C only one choice possible) A - Cable connection by the top (cable maxi 240 mm2 with VPIS) Single core B - Low voltage control cabinet (h = 450 mm) C - Wiring duct 50 W heating element for CM, CM2, TM Busbar field distributors for severe conditions (only for 630 A and CM, CM2 and TM cubicles) Blown fuse auxiliary contact (for CM, CM2 and TM only) Internal arc version (not possible with top incomer option) 16 kA 1s Gaz exhaust direction Downwards (only for 16 kA 1s) 1 O and 1 C 20 kA 1s Upwards See specific order form 2 x single core With unpunched door
SM6-36 options
Current transformers and voltage transformers for GBC Cable connection by the top (single core cable maxi 240 mm2 with VPIS) Replacement of 630 A busbar by 1250 A (for CM, CM2 and TM only)
112
AMTED398078EN
Order form
SM6
Other functions
Only one of the boxes (ticked X or filled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.
Basic cubicle
Rated voltage Ur Service voltage Short-circuit current Isc Rated current Ir Internal arc withstand 12.5 kA 1s for SM6-24 Type of cubicle/upper busbar for SM6-24 Ir = 630 A, Ir busbar = 400 A Ir = 630 A, Ir busbar = 630 A Ir = 1250 A, Ir busbar = 1250 A Type of cubicle for SM6-36 Position in the switchboard GAM 500 GAM 500 GAM 500 GAM 750 GAM2 750 Middle GAM2 375 GAM2 375
Quantity (kV) (kV) (kA) (A) 16 kA 1s for SM6-36 GBM 375 GBM 375 GBM 375 GBM 750 Last on right Right SM6-36
Left (impossible on the first cubicle of the switchboard) Cable connection by the bottom (1x single core, cable maxi 240 mm2)
Options
SM6-24 options
Roof configuration (A, B or C only one choice possible) A - Cable connection by the top (cable maxi 240 mm2 with VPIS) Single core B - Low voltage control cabinet (h = 450 mm) C - Wiring duct Wiring duct for GBM ES auxiliary contact (only on GAM 500) Surge arresters for GAM 500, 630 A 7.2 kV 10 kV 12 kV 17.5 kV SM6-24 Flat key type P5 SM6-SM6 Cubicle no. Flair 23DV zero sequence Flair 23DV 20 kA 1s Upwards Interlocking on GAM 500 1 O and 1 C 2 x single core With unpunched door
Localisation of 2nd lock for P5 Heating element (on GAM 500 630 A and on GAM2) Digital ammeter or Fault current indicator AMP 21D (except GBM) Flair 21D Flair 22D
Internal arc version (not possible with top incomer option) 16 kA 1s Gaz exhaust direction Downwards (only for 16 kA 1s)
SM6-36 options
Cable connection by the top (single core cable maxi 240 mm2 with VPIS) Replacement of 630 A busbar by 1250 A (for GAM2 only) Surge arresters for GAM2
AMTED398078EN
113
Order form
SF1
by Only one of the boxes (ticked X or filled the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.
48 Vdc 125 Vdc Undervoltage release YM 24 Vdc 30 Vdc 48 Vdc Mitop 60 Vdc 110 Vdc 125 Vdc
48 Vdc 125 Vdc Undervoltage release YM 24 Vdc 30 Vdc 48 Vdc Mitop 60 Vdc 110 Vdc 125 Vdc
Remote control
Electrical motor M
Different releases combinations Shunt opening releases YO1/YO2 Undervoltage release YM Mitop
1 1 1
1 1
1 1 1 1 AMTED398078EN
114
Order form
SFset
Is = 10 to 50 A Is = 63 to 312 A Is = 10 to 50 A Is = 63 to 312 A
VIP 300LL
48 Vdc 125 Vdc Undervoltage release YM 24 Vdc 30 Vdc 48 Vdc 60 Vdc 110 Vdc 125 Vdc
Remote control
Electrical motor M
Different releases combinations Mitop Shunt opening release YO2 Undervoltage release YM AMTED398078EN
1 1
1 1
115
Order form
Evolis
If locks 2 identical locks 1 lock Disabling of O/C circuit breaker push buttons
1 1
1 1 AMTED398078EN
116
Order form
Evolis
Different releases combinations Shunt opening releases YO1 Shunt opening releases YO2 Undervoltage release YM Mitop AMTED398078EN
1 1
1 1
1 1
1 1 1
117
Notes
118
AMTED398078EN