Marina View Hosereel (Pump Feed from roof)

Date : 12.04.09

HYDRAULIC CALCULATIONS FOR THE HOSEREEL SYSTEM


Minimum Requirement (CP29:1998 & Fire Precaution Act in Building 2002) Hosereel Nozzle discharge pressure required : 200 kPa Minimum Throw : 10m Minimum Flow : 0.4L/s (24 L/min per Hosereel) Design Data Hosereel Pipe diameter Pipe length from pump discharge to hydraulically most favourable hosereel No. of bends and fittings Equivalent length of bends and fittings (3m per bend) Total Equivalent Length Total Flow Rate Type of Pipe (1=Steel / 2=DICL / 3=Cast Iron) Constant for class of pipe Height from Pump to Remote Hosereel Using Hazen-William formula: Pipe Frictional Loss P = 6.05 x 107 x P= Pressure Summary : Static Gain = Hx10Kpa/m Pipe Frictional Loss = PxL Nozzle minimum discharge Total Pressure required (Minimun Pump Head) Hosereel Pump Selected Q1.85 C x d4.87 0.0637 Kpa/m
1.85

d=

L= Q= C= H=

50 220 23 69 289 50 1 120 1

mm m nos. m m l/min

10.00 Kpa 18.42 Kpa 200.00 Kpa 228.42 Kpa

50

l/min @

228.42 kPa