COMMISSIONING PROCEDURE

PROJECT : 5 x 660MW Mundra Power Project.

COMMNG /
ELEC / 043

PRECOMMISSIONING CHECK LIST AND TEST REPORT - HT MOTOR


1. LOCATION
2. DESIGNATION

:
:

3. NAME PLATE DETAILS :


MAKE

POWER
VOLTAGE

:
:

FULL LOAD CURRENT :


SERIAL NO.

MODEL NO.

FREQUENCY
COS

:
:

EFFICIENCY
IP
SPEED
CONNECTION
INSULATION CLASS
FRAME SIZE

:
:
:
:
:

ROTOR TYPE

AMB.TEMP.
NO. OF START

:
:

DUTY
BEARING DE/NDE

:
:

4. MOTOR SPACE HEATER :


POWER RATING
:
VOLTAGE RATING

RESISTANCE VALUE

: OHMS

INSULATION RESISTANCE .

SEPCO-III

(Applied Voltage : V)

Adani Project

Adani
Commissioning
Page 1 of 6

COMMISSIONING PROCEDURE

PROJECT : 5 x 660MW Mundra Power Project.

CURRENT MEASURED

HEATER OPERATION

5. SWITCHBOARD NAME & FEEDER NO. FOR HT MOTOR

6. BREAKER TYPE

7. BREAKER STARTER TYPE

8. MOTOR POWER CABLE SIZE

9. MOTOR CONTROL CABLE SIZE

10. MOTOR ANTI CONDENSATION HEATER CABLE SIZE

11.EARTHING CABLE / STRIP SIZE

12.MOTOR TERMINALS TIGHTNESS


13.OUTDOOR MOTOR CANOPY

:
:

14. LOCAL CONTROL STATION INSTALLATION

15. FIELD AMMETER AS PER THE CT SPECIFICATION

16. PANEL AMMETER AS PER THE CT SPECIFICATION

COMMNG /
ELEC / 043

17. LOCAL CONTROL STATION EARTHING INSTALLATION :


18. ELECTRICAL CLEARANCE TO THE BODY

19. HT MOTOR RTD VALUE ( FOR Winding / Bearing)


:
( RTD VALUE AT AMBIENT TEMPERATURE )
BEARING TEMPERATURE GAUGE READING AT AMBIENT TEMPERATURE
1) DRIVING END
:
2) NON DRIVING END :
TERMINAL
RESISTANCE
TERMINAL
WINDING
BEARING
NO.
VALUE
NO.
Rph
DRIVING END

SEPCO-III

Adani Project

RESISTANCE
VALUE

Adani
Commissioning
Page 2 of 6

COMMISSIONING PROCEDURE

PROJECT : 5 x 660MW Mundra Power Project.

COMMNG /
ELEC / 043

NON DRIVING
END

Yph

Bph

20. INSULATION RESISTANCE VALUE OF MOTOR :

Megger Make :
Megger Sl.no :
Voltage Rating of Megger :S.NO

REFERENCE

1.
2.

U1 V1 + W1 + EARTH
V1 U1 + W1 + EARTH

SEPCO-III

5 kV
R15

R60

R600

Adani Project

POLARISATION
INDEX = R600 / R15

Adani
Commissioning
Page 3 of 6

COMMISSIONING PROCEDURE

PROJECT : 5 x 660MW Mundra Power Project.

3.

COMMNG /
ELEC / 043

W1 U1 + V1 + EARTH

21. ROTOR INSULATION RESISTANCE TEST :

Megger Make :.
Megger Sl.no :
Voltage Rating of Megger ..V.
S.NO
1.

REFERENCE

IR VALUE

22. WINDING RESISTANCE TEST : ( microohms / milliohms / ohms )


U1 U2

V1 V2

W1 W2

23. POLARITY TEST :


S.NO
1.

DESCRIPTION

U1 U2

V1 V2

W1 W2

24. HIGH VOLTAGE TEST :


THIS TEST WILL BE CONDUCTED, ONLY IF RECOMMENDED BY MANUFACTURER /
VENDOR.
VOLTAGE APPLIED : 10kV (AC ).
TIME DURATION
: 60 SECONDS.
S.NO
1.
2.
3.

REFERENCE
U1 EARTH
V1 EARTH
W1 EARTH

SEPCO-III

EARTHED
V1 + W1 EARTH
W1 + U1 EARTH
U1 + V1 EARTH

LEAKAGE CURRENT (milliamps)

Adani Project

REMARK

Adani
Commissioning
Page 4 of 6

COMMISSIONING PROCEDURE

PROJECT : 5 x 660MW Mundra Power Project.

COMMNG /
ELEC / 043

25. CHECK LIST

Check List

S.NO

Status o.k / not o.k

1.

Check that motor base frame ( solo plate ) is properly


grouted / bolted to the foundation.

2.

Check that motor is firmly bolted to the base frame.

3.

Check that motor is free to rotate by hand , without any


abnormal sound.

4.

Check the condition of grease in motor bearings.

5.

Check continuity of earthing up to earth riser / grid.

6.

Check Continuity / IR value proper termination at


both ends for following points.

6.1

Power cable (Including Phase Indication)

6.2

Space heater cable.

6.3

Local start/stop station cable.

7.

Check that Motor / Drive is clearly labelled.

8.

Check for cleanliness of Motor & its terminal box.


Check Local start / stop station functionally upto HT
Feeder.
Check that Motors and push button stations in hazardous
are designed for the same.
Check that Cable glands are properly installed and
terminals covers are properly closed.
Direction of motor from driving end.
Check speed switch(if provided) upto HT Feeder.
Check Space Heater operation from HT feeder.

9.
10.
11.
12.
13.
14.

SEPCO-III

Adani Project

Remarks

Adani
Commissioning
Page 5 of 6

COMMISSIONING PROCEDURE
COMMNG /
ELEC / 043

PROJECT : 5 x 660MW Mundra Power Project.

26. CHECK STABILITY OF MOTOR DIFFERENTIAL PROTECTION:


Current Measured in Motor Differential Relay.
(i) When Current is injected B/W Uphase & Vphase.Bypassing the Uphase & Vphase winding by
putting the loop across the winding.
Description
Phase Side
Neutral Side
I d Differential Current
I r Restraint Current

Uph

Vph

Wph

3Io

-----

(ii) When Current is injected B/W V phase & W phase. Bypassing the V phase & W phase winding
by putting the loop across the winding.
Description
Phase Side
Neutral Side
I d Differential Current
I r Restraint Current

SEPCO-III

Uph

Vph

Wph

3Io

-----

Adani Project

Adani
Commissioning
Page 6 of 6