Você está na página 1de 11

1014-M00-ILS-003 OTE Doc.

Number:
B2 14-02-2012 RE - APPROVED FOR DESIGN MC PKS KP HH
HH KP PKS MC RE - APPROVED FOR DESIGN 26-12-2011 B1
03-10-2011 PKS
Approved Engr Checked Prepared Description Rev Date
CHARTER HIRE OF FPSO FOR D1 FIELD
FGS I/O LIST
BUMI ARMADA
ENGINEERING
21010-BAE-70000-IN-RL-0003
Page
Revision:
BAE Doc. Number:
CHARTER HIRE OF FPSO FOR D1 FIELD
B2
1/11
A0 ISSUED FOR REVIEW HH SVS PVT
B0 06-12-2011 APPROVED FOR DESIGN PKS RM HH MC
-
- -
-
-
-
5
-
-
132
3
-
22
DIGITAL OUTPUTS ( DO NON I.S )
8
4
-
-
-
M00
1014-M00-ILS-003 OTE Doc. Number:
1. THIS I/O LIST CONTAINS HARDWIRED SIGNALS.
2. FIRE AND GAS IO LIST IS GENERATED WITH THE FOLLOWING REFERRENCE DOCUMENTS
a) FIRE AND GAS CAUSE AND EFFECT MATRIX DOC.NO - 21010-BAE-70000-IN-RL-0007, REV A0
b) FIRE AND GAS LOCATION PLAN DOC.NO
i. 21010-BAE-70000-IN-DW-0031, REV A0
ii. 21010-BAE-70000-IN-DW-0032, REV A0
iii. 21010-BAE-70000-IN-DW-0033, REV A0
iv. 21010-BAE-70020-IN-DW-0031, REV B0
v. 21010-BAE-70030-IN-DW-0031, REV B0
vi. 21010-BAE-70050-IN-DW-0031, REV B0
vii. 21010-BAE-70060-IN-DW-0031, REV B1
viii. 21010-BAE-70070-IN-DW-0031, REV B1
ix. 21010-BAE-70090-IN-DW-0031, REV B1

M90
230
4
-
46
-
-
M30
2/11
B2
CHARTER HIRE OF FPSO FOR D1 FIELD
FGS I/O LIST
BAE Doc. Number:
Revision:
Page
21010-BAE-70000-IN-RL-0003
NOTES:
S.NO
ANALOG INPUTS ( AI NON I.S.)
ANALOG OUTPUTS ( AO NON I.S.)
1
4
I/O TYPE
ANALOG OUTPUTS ( AO - I.S.)
7
2
5
8
ANALOG INPUTS ( AI - I.S.)
19
DIGITAL INPUTS ( DI I.S )
DIGITAL OUTPUTS ( DO I.S )
3
6
M10
-
-
-
-
-
3
-
-
25
-
M20
-
8
-
-
1
-
- -
-
1
-
-
-
3
-
M55 M50
-
3
-
-
-
1
-
-
11
-
-
-
-
-
-
1
-
-
-
10
-
M70 M60
-
45
-
-
9
-
30
-
FGS
I/O
DIGITAL INPUTS ( DI NON I.S )
18
BUMI ARMADA
ENGINEERING
I/O COUNT
48
Rev
BUMI ARMADA
ENGINEERING
I/O
Destination
1014-M00-ILS-003 OTE Doc. Number:
Function Tag Remarks Tag No Module
21010-BAE-70000-IN-RL-0003
Page
Revision:
BAE Doc. Number:
FGS I/O LIST
CHARTER HIRE OF FPSO FOR D1 FIELD
B2
3/11
I.S /
Non I.S
Instrument Service Instrument Type F&G Loc. Plan
Dwg No.
I/O Type System I/OSource Signal Type Disp. Range Units Alarm
LoLo
Alarm
Lo
Alarm
Hi
Alarm
HiHi
Set
Point Operating principle
M00
-
B2 - - - FLD - FGS I.S 2W4-20mA FGS AI
Flow element produce water overboard
00-FI-8100
Flow Indicator
BAE-55570-MA-DW-
0005
-
Newly Added - - - - -
M00
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-064 FGS N.I.S 3w 4-20mA FGS AI
Forward Fire Water Pump Room Portside Air
Intake
00-GD-4540-064
Gas Detector
21010-BAE-70000-IN-
DW-0031
-
20 60 - - -
M00
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-065 FGS N.I.S 3w 4-20mA FGS AI
Forward Fire Water Pump Room Portside Air
Intake
00-GD-4540-065
Gas Detector
21010-BAE-70000-IN-
DW-0031
-
20 60 - - -
M00
Air Intake IR Point Type
B1 %LEL 0 60 FLD GAH,GAHH-4540-066 FGS N.I.S 3w 4-20mA FGS AI
Forward Fire Water Pump Room Starboard side
00-GD-4540-066
Gas Detector
21010-BAE-70000-IN-
DW-0032
-
20 60 - - -
M00
Air Intake IR Point Type
B1 %LEL 0 60 FLD GAH,GAHH-4540-067 FGS N.I.S 3w 4-20mA FGS AI
Forward Fire Water Pump Room Starboard side
00-GD-4540-067
Gas Detector
21010-BAE-70000-IN-
DW-0032
-
20 60 - - -
M00
-
B2 - - - FLD - FGS N.I.S VFC FGS DI
Helideck Area MAC
00-MAC-4540-009
Manual Alarm Call Point
HOLD -
NEWLY ADDED - - - - -
M00
-
B2 - - - FLD - FGS N.I.S VFC FGS DI
Helideck Area MAC
00-MAC-4540-010
Manual Alarm Call Point
HOLD -
NEWLY ADDED - - - - -
M00
-
B2 - - - FLD NA FGS N.I.S VFC FGS DI
Zone A Deluge Valve Open
00-PSH-8100
Pressure Switch
55570-MA-DW-0005 -
Newly Added NA NA NA NA NA
M00
-
B2 - - - FLD NA FGS N.I.S VFC FGS DI
Zone B Deluge Valve Open
00-PSH-8102
Pressure Switch
55570-MA-DW-0003 -
Newly Added NA NA NA NA NA
M00
-
B2 - - - FLD NA FGS N.I.S VFC FGS DI
Zone C Deluge Valve Open
00-PSH-8103
Pressure Switch
55570-MA-DW-0003 -
Newly Added NA NA NA NA NA
M00
-
B2 - - - FLD NA FGS N.I.S VFC FGS DI
AFT Foam Deluge Valve Pressure
00-PSH-8310
Pressure Switch
-
Newly Added NA NA NA NA NA
M00
-
B2 mA TBA TBA FLD - FGS I.S 2W4-20mA FGS AI
E/R Jockey Pump Discharge Pressure
00-PT-8130
Pressure Transmitter
-
Newly Added - - - - -
M00
Transmitter Piezo-Electric
B2 - - - FLD NA FGS I.S 2w 4-20mA FGS AI
AFT Firewater On Deck Ring Main Pressure
00-PZT-8101
Pressure Transmitter
BAE-55570-MA-DW-
0003
-
Newly Added NA NA NA NA NA
M00
-
B2 - - - FLD NA FGS I.S 2w 4-20mA FGS AI
Fire Water Main Ring Pressure
00-PZT-8102
Pressure Transmitter
55570-MA-DW-0003 -
Newly Added NA NA NA NA NA
M00
Photo Electric/Ionisation
B2 - - - FLD - FGS N.I.S 2W4-20mA FGS AI
Forward Fire Water Pump Room No1
00-SD-4540-014
Smoke Detector
HOLD -
DELETED - - - - -
M00
Photo Electric/Ionisation
B2 - - - FLD - FGS N.I.S 2W4-20mA FGS AI
Forward Fire Water Pump Room No1
00-SD-4540-015
Smoke Detector
HOLD -
DELETED - - - - -
M00
Photo Electric/Ionisation
B2 - - - FLD - FGS N.I.S 2W4-20mA FGS AI
Forward Fire Water Pump Room No2
00-SD-4540-016
Smoke Detector
HOLD -
DELETED - - - - -
M00
Photo Electric/Ionisation
B2 - - - FLD - FGS N.I.S 2W4-20mA FGS AI
Forward Fire Water Pump Room No2
00-SD-4540-017
Smoke Detector
HOLD -
DELETED - - - - -
M00
-
B2 - - - LCP NA FGS N.I.S VFC FGS DI
E/R AFT Fire Pump Common Alarm
00-XA-8110
Alarm
-
Newly Added NA NA NA NA NA
M00
-
B2 - - - FWD FWLCP NA FGS N.I.S VFC FGS DI
FWD Port Fire pump Common Alarm
00-XA-8120
Common Alarm
-
Newly Added NA NA NA NA NA
M00
-
B2 - - - FLD NA FGS N.I.S VFC FGS DI
FWD Stbd Fire Pump Common Alarm
00-XA-8125
Alarm
-
Newly Added NA NA NA NA NA
M00
-
B2 - - - FGS NA FGS N.I.S VFC FLD DO
E/R AFT Fire Pump Remote Start
00-XC-8110
Command
-
Newly Added NA NA NA NA NA
M00
-
B2 - - - FGS NA FGS N.I.S VFC FLD DO
CAAP E/R AFT Fire Pump Running
00-XC-8111
Command
-
Newly
Added,Tag.No
Changed
NA NA NA NA NA
M00
-
B2 - - - FGS NA FGS N.I.S VFC FWD FWLCP DO
FWD Port Fire Pump Remote Start
00-XC-8120
Command
70000-IN-RL-0007 -
Newly Added NA NA NA NA NA
M00
-
B2 - - - FGS NA FGS N.I.S VFC FLD DO
CAAP FWD Port Fire Pump Running
00-XC-8121
Command
-
Newly
Added,Tag.No
changed
NA NA NA NA NA
M00
-
B2 - - - FGS NA FGS N.I.S VFC FLD DO
FWD Stbd Fire Pump Remote Start
00-XC-8125
Command
-
Newly Added NA NA NA NA NA
M00
-
B2 - - - FGS NA FGS N.I.S VFC FLD DO
CAAP Forward Stbd Fire Pump Running
00-XC-8126
Command
-
Newly
Added,Tag.No
changed
NA NA NA NA NA
M00
-
B2 - - - FGS NA FGS N.I.S VFC MCC- Engine
Room
DO
Fire Jockey Pump remote Start/Stop
00-XC-8130
Command
52980-MA-DW-0004 -
Newly Added NA NA NA NA NA
Rev
BUMI ARMADA
ENGINEERING
I/O
Destination
1014-M00-ILS-003 OTE Doc. Number:
Function Tag Remarks Tag No Module
21010-BAE-70000-IN-RL-0003
Page
Revision:
BAE Doc. Number:
FGS I/O LIST
CHARTER HIRE OF FPSO FOR D1 FIELD
B2
4/11
I.S /
Non I.S
Instrument Service Instrument Type F&G Loc. Plan
Dwg No.
I/O Type System I/OSource Signal Type Disp. Range Units Alarm
LoLo
Alarm
Lo
Alarm
Hi
Alarm
HiHi
Set
Point Operating principle
M00
-
B2 - - - FLD NA FGS N.I.S VFC FGS DI
Confirm Fire
00-XE-4510
Status
-
Newly Added NA NA NA NA NA
M00
-
B2 - - - FLD NA FGS N.I.S VFC FGS DI
Confirm Gas
00-XE-4520
Status
-
Newly Added NA NA NA NA NA
M00
-
B2 - - - MCC- Engine
Room
NA FGS N.I.S VFC FGS DI
E/R AFT Fire Pump Local/ Remote Status
00-XE-8110
Status
-
Newly Added NA NA NA NA NA
M00
-
B2 - - - MCC- Engine
Room
NA FGS N.I.S VFC FGS DI
FWD Port Fire Pump Local/ Remote Status
00-XE-8120
Status
-
Newly Added NA NA NA NA NA
M00
-
B2 - - - MCC- Engine
Room
NA FGS N.I.S VFC FGS DI
FWD Stbd Fire Pump Local/ Remote Status
00-XE-8125
Status
-
Newly Added NA NA NA NA NA
M00
-
B2 - - - MCC- Engine
Room
NA FGS N.I.S VFC FGS DI
Jockey Pump Local/Remote Status
00-XE-8130
Status
52980-MA-DW-0004 -
Signal Type Change NA NA NA NA NA
M00
-
B2 - - - MCC- Engine
Room
NA FGS N.I.S VFC FGS DI
E/R AFT Fire Pump Running Indication
00-XI-8110
Indication
-
Newly Added NA NA NA NA NA
M00
-
B2 - - - MCC- Engine
Room
NA FGS N.I.S VFC FGS DI
CAAP E/R AFT Fire Pump Running Ind.
00-XI-8110A
Indication
-
Newly Added NA NA NA NA NA
M00
-
B2 - - - MCC- Engine
Room
NA FGS N.I.S VFC FGS DI
FWD Port Fire Pump Running Indication
00-XI-8120
Indication
-
Newly Added NA NA NA NA NA
M00
-
B2 - - - MCC- Engine
Room
NA FGS N.I.S VFC FGS DI
CAAP FWD Port Fire Pump Running Ind.
00-XI-8120A
Indication
-
Newly Added NA NA NA NA NA
M00
-
B2 - - - MCC- Engine
Room
NA FGS N.I.S VFC FGS DI
FWD Stbd Fire Pump Running Indication
00-XI-8125
Indication
-
Newly Added NA NA NA NA NA
M00
-
B2 - - - FLD NA FGS N.I.S VFC FGS DI
CAAP Forward Stbd Fire Pump Running Ind.
00-XI-8126
Indication
-
Newly
Added,Tag.No
changed
NA NA NA NA NA
M00
-
B2 - - - MCC- Engine
Room
NA FGS N.I.S VFC FGS DI
Jockey Pump Running indication
00-XI-8130
Status
52980-MA-DW-0004 -
Newly Added NA NA NA NA NA
M00
-
B2 - - - FGS NA FGS N.I.S VFC FLD DO
E/R AFT Fire Pump Unit Tripped
00-XS-8110
Command
-
Newly Added NA NA NA NA NA
M00
-
B2 - - - FGS NA FGS N.I.S VFC FLD DO
E/R AFT Fire Pump Start Inhibit
00-XS-8111
Command
-
Newly Added NA NA NA NA NA
M00
-
B2 - - - FGS NA FGS N.I.S VFC FWD FWLCP DO
FWD Port Fire Pump Unit Tripped
00-XS-8120
Command
- -
Newly Added NA NA NA NA NA
M00
-
B2 - - - FGS NA FGS N.I.S VFC AFT FWLCP DO
FWD Port Fire pump Start Inhibit
00-XS-8121
Command
70000-IN-RL-0007 -
FWP LCP NA NA NA NA NA
M00
-
B2 - - - FGS NA FGS N.I.S VFC FWD FWLCP DO
FWD Stbd Fire Pump Unit Tripped
00-XS-8125
Command
- -
Newly Added NA NA NA NA NA
M00
-
B2 - - - FGS NA FGS N.I.S VFC FWD FWLCP DO
FWD Stbd Fire Pump Start Inhibit
00-XS-8126
Command
- -
Newly Added NA NA NA NA NA
M00
-
B2 - - - FGS NA FGS N.I.S VFC FLD DO
Fire Jockey Pump Unit Tripped
00-XS-8130
Command
-
Newly Added NA NA NA NA NA
M00
-
B2 - - - FGS NA FGS N.I.S 24V DC FLD DO
FWD Foam Deluge Valve Open Zone A
00-XV-8100
Command
-
Newly Added NA NA NA NA NA
M00
-
B2 - - - FGS NA FGS N.I.S 24V DC FLD DO
AFT Foam Deluge Valve Open Zone B
00-XV-8102
Command
-
Newly Added NA NA NA NA NA
M00
-
B2 - - - FGS NA FGS N.I.S 24V DC FLD DO
FWD Foam Deluge Valve Open Zone A
00-XV-8103
Command
-
Newly Added NA NA NA NA NA
M00
-
B2 - - - FGS NA FGS N.I.S 24V DC FLD DO
AFT Foam Deluge Valve Open
00-XV-8310
Command
-
Newly Added NA NA NA NA NA
M10
Multi Spectrum IR
B0 mA 0 20 FLD FAH,FAHH-4540-031 FGS N.I.S 3w 4-20mA FGS AI
Slug Suppression System Flame Detector
10-FD-4540-031
Flame Detector
HOLD -
16 20 - - -
M10
Multi Spectrum IR
B0 mA 0 20 FLD FAH,FAHH-4540-032 FGS N.I.S 3w 4-20mA FGS AI
Slug Suppression System Flame Detector
10-FD-4540-032
Flame Detector
HOLD -
16 20 - - -
M10
Multi Spectrum IR
B0 mA 0 20 FLD FAH,FAHH-4540-033 FGS N.I.S 3w 4-20mA FGS AI
Turret Head - Main Deck Flame Detector
10-FD-4540-033
Flame Detector
HOLD -
16 20 - - -
M10
Multi Spectrum IR
B0 mA 0 20 FLD FAH,FAHH-4540-034 FGS N.I.S 3w 4-20mA FGS AI
Turret Head - Main Deck Flame Detector
10-FD-4540-034
Flame Detector
HOLD -
16 20 - - -
Rev
BUMI ARMADA
ENGINEERING
I/O
Destination
1014-M00-ILS-003 OTE Doc. Number:
Function Tag Remarks Tag No Module
21010-BAE-70000-IN-RL-0003
Page
Revision:
BAE Doc. Number:
FGS I/O LIST
CHARTER HIRE OF FPSO FOR D1 FIELD
B2
5/11
I.S /
Non I.S
Instrument Service Instrument Type F&G Loc. Plan
Dwg No.
I/O Type System I/OSource Signal Type Disp. Range Units Alarm
LoLo
Alarm
Lo
Alarm
Hi
Alarm
HiHi
Set
Point Operating principle
M10
Multi Spectrum IR
B0 mA 0 20 FLD FAH,FAHH-4540-035 FGS N.I.S 3w 4-20mA FGS AI
Turret Head - 01 Level Deck Flame Detector
10-FD-4540-035
Flame Detector
HOLD -
16 20 - - -
M10
Multi Spectrum IR
B0 mA 0 20 FLD FAH,FAHH-4540-036 FGS N.I.S 3w 4-20mA FGS AI
Turret Head - 01 Level Deck Flame Detector
10-FD-4540-036
Flame Detector
HOLD -
16 20 - - -
M10
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-031 FGS N.I.S 3w 4-20mA FGS AI
Turret Head - Swivel Stack Gas Detector
10-GD-4540-031
Gas Detector
HOLD -
20 60 - - -
M10
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-032 FGS N.I.S 3w 4-20mA FGS AI
Turret Head - Swivel Stack Gas Detector
10-GD-4540-032
Gas Detector
HOLD -
20 60 - - -
M10
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-033 FGS N.I.S 3w 4-20mA FGS AI
Turret Head - Main Deck Gas Detector
10-GD-4540-033
Gas Detector
HOLD -
20 60 - - -
M10
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-034 FGS N.I.S 3w 4-20mA FGS AI
Turret Head - Main Deck Gas Detector
10-GD-4540-034
Gas Detector
HOLD -
20 60 - - -
M10
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-035 FGS N.I.S 3w 4-20mA FGS AI
Turret Head - 01 Level Deck Gas Detector
10-GD-4540-035
Gas Detector
HOLD -
20 60 - - -
M10
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-036 FGS N.I.S 3w 4-20mA FGS AI
Turret Head - 01 Level Deck Gas Detector
10-GD-4540-036
Gas Detector
HOLD -
20 60 - - -
M10
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-060 FGS N.I.S 3w 4-20mA FGS AI
Slug Suppression System Gas Detector
10-GD-4540-060
Gas detector
HOLD -
20 60 - - -
M10
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-061 FGS N.I.S 3w 4-20mA FGS AI
Slug Suppression System Gas Detector
10-GD-4540-061
Gas detector
HOLD -
20 60 - - -
M10
IR Point Type
B2 %LEL 0 60 FLD GAH,GAHH-4540-062 FGS N.I.S 3w 4-20mA FGS AI
Bosun Store
10-GD-4540-062
Gas detector
21010-BAE-70000-IN-
DW-0033
-
Description changed 20 60 - - -
M10
IR Point Type
B2 %LEL 0 60 FLD GAH,GAHH-4540-063 FGS N.I.S 3w 4-20mA FGS AI
Bosun store
10-GD-4540-063
Gas detector
21010-BAE-70000-IN-
DW-0033
-
Description changed 20 60 - - -
M10
-
B0 - - - FLD - FGS N.I.S VFC FGS DI
Turret Head - 01 Level Deck MAC
10-MAC-4540-001A
Manual Alarm Call Point
HOLD -
- - - - -
M10
-
B0 - - - FLD - FGS N.I.S VFC FGS DI
Turret Head - Main Deck
10-MAC-4540-001B
Manual Alarm Call Point
HOLD -
- - - - -
M10
-
B0 - - - FLD - FGS N.I.S VFC FGS DI
Turret Head - Swivel Stack
10-MAC-4540-001C
Manual Alarm Call Point
HOLD -
- - - - -
M10
Photo Electric/Ionisation
B2 - - - FLD - FGS N.I.S 2W4-20mA FGS AI
Bosun store
10-SD-4540-031
Smoke Detector
21010-BAE-70000-IN-
DW-0033
-
Description changed - - - - -
M10
Photo Electric/Ionisation
B2 - - - FLD - FGS N.I.S 2W4-20mA FGS AI
Bosun store
10-SD-4540-032
Smoke Detector
21010-BAE-70000-IN-
DW-0033
-
Description changed - - - - -
M10
Photo Electric/Ionisation
B2 - - - FLD - FGS N.I.S 2W4-20mA FGS AI
Bosun store
10-SD-4540-033
Smoke Detector
21010-BAE-70000-IN-
DW-0033
-
Description changed - - - - -
M20
Multi Spectrum IR
B0 mA 0 20 FLD FAH,FAHH-4540-001 FGS N.I.S 3w 4-20mA FGS AI
Flare KOD Flame Detector
20-FD-4540-001
Flame Detector
21010-BAE-70020-IN-
DW-0003
-
16 20 - - -
M20
Multi Spectrum IR
B0 mA 0 20 FLD FAH,FAHH-4540-002 FGS N.I.S 3w 4-20mA FGS AI
Flare KOD Flame Detector
20-FD-4540-002
Flame Detector
21010-BAE-70020-IN-
DW-0003
-
16 20 - - -
M20
Multi Spectrum IR
B0 mA 0 20 FLD FAH,FAHH-4540-003 FGS N.I.S 3w 4-20mA FGS AI
Flare KOD Flame Detector
20-FD-4540-003
Flame Detector
21010-BAE-70020-IN-
DW-0003
-
16 20 - - -
M20
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-001 FGS N.I.S 3w 4-20mA FGS AI
Flare KOD GasDetector
20-GD-4540-001
Gas Detector
21010-BAE-70020-IN-
DW-0003
-
20 60 - - -
M20
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-002 FGS N.I.S 3w 4-20mA FGS AI
Flare KOD Gas Detector
20-GD-4540-002
Gas Detector
21010-BAE-70020-IN-
DW-0003
-
20 60 - - -
M20
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-003 FGS N.I.S 3w 4-20mA FGS AI
Flare KOD Gas Detector
20-GD-4540-003
Gas Detector
21010-BAE-70020-IN-
DW-0003
-
20 60 - - -
M20
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-004 FGS N.I.S 3w 4-20mA FGS AI
Flare KOD Gas Detector
20-GD-4540-004
Gas Detector
21010-BAE-70020-IN-
DW-0003
-
20 60 - - -
M20
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-005 FGS N.I.S 3w 4-20mA FGS AI
Flare KOD Gas Detector
20-GD-4540-005
Gas Detector
21010-BAE-70020-IN-
DW-0003
-
20 60 - - -
M20
-
A0 - - - FLD - FGS N.I.S VFC FGS DI
Flare KOD MAC
20-MAC-4540-001
Manual Alarm Call Point
21010-BAE-70020-IN-
DW-0003
-
- - - - -
M30
Multi Spectrum IR
B0 mA 0 20 FLD FAH,FAHH-4540-004 FGS N.I.S 3w 4-20mA FGS AI
CSU/PW/Fuel Gas system Flame Detector
30-FD-4540-004
Flame Detector
21010-BAE-70030-IN-
DW-0003
-
16 20 - - -
M30
Multi Spectrum IR
B0 mA 0 20 FLD FAH,FAHH-4540-005 FGS N.I.S 3w 4-20mA FGS AI
CSU/PW/Fuel Gas system Flame Detector
30-FD-4540-005
Flame Detector
21010-BAE-70030-IN-
DW-0003
-
16 20 - - -
Rev
BUMI ARMADA
ENGINEERING
I/O
Destination
1014-M00-ILS-003 OTE Doc. Number:
Function Tag Remarks Tag No Module
21010-BAE-70000-IN-RL-0003
Page
Revision:
BAE Doc. Number:
FGS I/O LIST
CHARTER HIRE OF FPSO FOR D1 FIELD
B2
6/11
I.S /
Non I.S
Instrument Service Instrument Type F&G Loc. Plan
Dwg No.
I/O Type System I/OSource Signal Type Disp. Range Units Alarm
LoLo
Alarm
Lo
Alarm
Hi
Alarm
HiHi
Set
Point Operating principle
M30
Multi Spectrum IR
B0 mA 0 20 FLD FAH,FAHH-4540-006 FGS N.I.S 3w 4-20mA FGS AI
CSU/PW/Fuel Gas system Flame Detector
30-FD-4540-006
Flame Detector
21010-BAE-70030-IN-
DW-0003
-
16 20 - - -
M30
Multi Spectrum IR
B0 mA 0 20 FLD FAH,FAHH-4540-007 FGS N.I.S 3w 4-20mA FGS AI
CSU/PW/Fuel Gas system Flame Detector
30-FD-4540-007
Flame Detector
21010-BAE-70030-IN-
DW-0003
-
16 20 - - -
M30
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-006 FGS N.I.S 3w 4-20mA FGS AI
CSU/PW/Fuel Gas system GasDetector
30-GD-4540-006
Gas Detector
21010-BAE-70030-IN-
DW-0003
-
20 60 - - -
M30
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-007 FGS N.I.S 3w 4-20mA FGS AI
CSU/PW/Fuel Gas system Gas Detector
30-GD-4540-007
Gas Detector
21010-BAE-70030-IN-
DW-0003
-
20 60 - - -
M30
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-008 FGS N.I.S 3w 4-20mA FGS AI
CSU/PW/Fuel Gas system Gas Detector
30-GD-4540-008
Gas Detector
21010-BAE-70030-IN-
DW-0003
-
20 60 - - -
M30
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-009 FGS N.I.S 3w 4-20mA FGS AI
CSU/PW/Fuel Gas system Gas Detector
30-GD-4540-009
Gas Detector
21010-BAE-70030-IN-
DW-0003
-
20 60 - - -
M30
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-010 FGS N.I.S 3w 4-20mA FGS AI
CSU/PW/Fuel Gas system Gas Detector
30-GD-4540-010
Gas Detector
21010-BAE-70030-IN-
DW-0003
-
20 60 - - -
M30
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-011 FGS N.I.S 3w 4-20mA FGS AI
CSU/PW/Fuel Gas system Gas Detector
30-GD-4540-011
Gas Detector
21010-BAE-70030-IN-
DW-0003
-
20 60 - - -
M30
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-012 FGS N.I.S 3w 4-20mA FGS AI
CSU/PW/Fuel Gas system Gas Detector
30-GD-4540-012
Gas Detector
21010-BAE-70030-IN-
DW-0003
-
20 60 - - -
M30
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-013 FGS N.I.S 3w 4-20mA FGS AI
CSU/PW/Fuel Gas system Gas Detector
30-GD-4540-013
Gas Detector
21010-BAE-70030-IN-
DW-0003
-
20 60 - - -
M30
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-014 FGS N.I.S 3w 4-20mA FGS AI
CSU/PW/Fuel Gas system Gas Detector
30-GD-4540-014
Gas Detector
21010-BAE-70030-IN-
DW-0003
-
20 60 - - -
M30
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-015 FGS N.I.S 3w 4-20mA FGS AI
CSU/PW/Fuel Gas system GasDetector
30-GD-4540-015
Gas Detector
21010-BAE-70030-IN-
DW-0003
-
20 60 - - -
M30
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-016 FGS N.I.S 3w 4-20mA FGS AI
CSU/PW/Fuel Gas system GasDetector
30-GD-4540-016
Gas Detector
21010-BAE-70030-IN-
DW-0003
-
20 60 - - -
M30
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-017 FGS N.I.S 3w 4-20mA FGS AI
CSU/PW/Fuel Gas system GasDetector
30-GD-4540-017
Gas Detector
21010-BAE-70030-IN-
DW-0003
-
20 60 - - -
M30
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-018 FGS N.I.S 3w 4-20mA FGS AI
CSU/PW/Fuel Gas system GasDetector
30-GD-4540-018
Gas Detector
21010-BAE-70030-IN-
DW-0003
-
20 60 - - -
M30
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-019 FGS N.I.S 3w 4-20mA FGS AI
CSU/PW/Fuel Gas system GasDetector
30-GD-4540-019
Gas Detector
21010-BAE-70030-IN-
DW-0003
-
20 60 - - -
M30
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-020 FGS N.I.S 3w 4-20mA FGS AI
CSU/PW/Fuel Gas system GasDetector
30-GD-4540-020
Gas Detector
21010-BAE-70030-IN-
DW-0003
-
20 60 - - -
M30
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-021 FGS N.I.S 3w 4-20mA FGS AI
CSU/PW/Fuel Gas system GasDetector
30-GD-4540-021
Gas Detector
21010-BAE-70030-IN-
DW-0003
-
20 60 - - -
M30
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-022 FGS N.I.S 3w 4-20mA FGS AI
CSU/PW/Fuel Gas system GasDetector
30-GD-4540-022
Gas Detector
21010-BAE-70030-IN-
DW-0003
-
20 60 - - -
M30
IR Point Type
B2 FLD GAH,GAHH-4540-022 FGS N.I.S 3w 4-20mA FGS AI
Fuel Gas skid GasDetector
30-GD-4540-048
Gas Detector
21010-BAE-70030-IN-
DW-0003
-
NEWLY ADDED 15 45 - - -
M30
IR Point Type
B2 FLD GAH,GAHH-4540-022 FGS N.I.S 3w 4-20mA FGS AI
Fuel Gas skid GasDetector
30-GD-4540-049
Gas Detector
21010-BAE-70030-IN-
DW-0003
-
NEWLY ADDED 15 45 - - -
M30
IR Point Type
B2 FLD GAH,GAHH-4540-022 FGS N.I.S 3w 4-20mA FGS AI
Fuel Gas skid GasDetector
30-GD-4540-050
Gas Detector
21010-BAE-70030-IN-
DW-0003
-
NEWLY ADDED 15 45 - - -
M30
IR Point Type
B2 FLD GAH,GAHH-4540-022 FGS N.I.S 3w 4-20mA FGS AI
Fuel Gas skid GasDetector
30-GD-4540-051
Gas Detector
21010-BAE-70030-IN-
DW-0003
-
NEWLY ADDED 15 45 - - -
M30
-
A0 - - - FLD - FGS N.I.S VFC FGS DI
CSU/PW/Fuel Gas system MAC
30-MAC-4540-002
Manual Alarm Call Point
21010-BAE-70030-IN-
DW-0003
-
- - - - -
M30
-
A0 - - - FLD - FGS N.I.S VFC FGS DI
CSU/PW/Fuel Gas system MAC
30-MAC-4540-003
Manual Alarm Call Point
21010-BAE-70030-IN-
DW-0003
-
- - - - -
M30
-
A0 - - - FLD - FGS N.I.S VFC FGS DI
CSU/PW/Fuel Gas system MAC
30-MAC-4540-004
Manual Alarm Call Point
21010-BAE-70030-IN-
DW-0003
-
- - - - -
M50
Multi Spectrum IR
B0 mA 0 20 FLD FAH,FAHH-4540-008 FGS N.I.S 3w 4-20mA FGS AI
Sea Water Injection system Flame Detector
50-FD-4540-008
Flame Detector
21010-BAE-70050-IN-
DW-0003
-
16 20 - - -
M50
Multi Spectrum IR
B0 mA 0 20 FLD FAH,FAHH-4540-009 FGS N.I.S 3w 4-20mA FGS AI
Sea Water Injection system Flame Detector
50-FD-4540-009
Flame Detector
21010-BAE-70050-IN-
DW-0003
-
16 20 - - -
M50
Multi Spectrum IR
B0 mA 0 20 FLD FAH,FAHH-4540-010 FGS N.I.S 3w 4-20mA FGS AI
Sea Water Injection system Flame Detector
50-FD-4540-010
Flame Detector
21010-BAE-70050-IN-
DW-0003
-
16 20 - - -
Rev
BUMI ARMADA
ENGINEERING
I/O
Destination
1014-M00-ILS-003 OTE Doc. Number:
Function Tag Remarks Tag No Module
21010-BAE-70000-IN-RL-0003
Page
Revision:
BAE Doc. Number:
FGS I/O LIST
CHARTER HIRE OF FPSO FOR D1 FIELD
B2
7/11
I.S /
Non I.S
Instrument Service Instrument Type F&G Loc. Plan
Dwg No.
I/O Type System I/OSource Signal Type Disp. Range Units Alarm
LoLo
Alarm
Lo
Alarm
Hi
Alarm
HiHi
Set
Point Operating principle
M50
-
A0 - - - FLD - FGS N.I.S VFC FGS DI
Sea water Injection System MAC
50-MAC-4540-005
Manual Alarm Call Point
21010-BAE-70050-IN-
DW-0003
-
- - - - -
M55
Multi Spectrum IR
B0 mA 0 20 FLD FAH,FAHH-4540-011 FGS N.I.S 3w 4-20mA FGS AI
Fiscal Metering system Flame Detector
55-FD-4540-011
Flame Detector
21010-BAE-70055-IN-
DW-0003
-
16 20 - - -
M55
Multi Spectrum IR
B0 mA 0 20 FLD FAH,FAHH-4540-012 FGS N.I.S 3w 4-20mA FGS AI
Fiscal Metering system Flame Detector
55-FD-4540-012
Flame Detector
21010-BAE-70055-IN-
DW-0003
-
16 20 - - -
M55
Multi Spectrum IR
B0 mA 0 20 FLD FAH,FAHH-4540-013 FGS N.I.S 3w 4-20mA FGS AI
Fiscal Metering system Flame Detector
55-FD-4540-013
Flame Detector
21010-BAE-70055-IN-
DW-0003
-
16 20 - - -
M55
-
A0 - - - FLD - FGS N.I.S VFC FGS DI
Fiscal Metering system MAC
55-MAC-4540-006
Manual Alarm Call Point
21010-BAE-70055-IN-
DW-0003
-
- - - - -
M60
IR Point Type
B0 %LEL 0 45 FLD GAH,GAHH-4530-001 FGS N.I.S 3w 4-20mA FGS AI
Transformer Room Gas Detector
60-GD-4530-001
Gas Detector
21010-BAE-70060-IN-
DW-0003
-
15 45 - - -
M60
IR Point Type
B0 %LEL 0 45 FLD GAH,GAHH-4530-002 FGS N.I.S 3w 4-20mA FGS AI
Transformer Room Gas Detector
60-GD-4530-002
Gas Detector
21010-BAE-70060-IN-
DW-0003
-
15 45 - - -
M60
IR Point Type
B0 %LEL 0 45 FLD GAH,GAHH-4530-003 FGS N.I.S 3w 4-20mA FGS AI
Battery Room Gas Detector
60-GD-4530-003
Gas Detector
21010-BAE-70060-IN-
DW-0003
-
15 45 - - -
M60
IR Point Type
B0 %LEL 0 45 FLD GAH,GAHH-4530-004 FGS N.I.S 3w 4-20mA FGS AI
Switchgear Room Gas Detector
60-GD-4530-004
Gas Detector
21010-BAE-70060-IN-
DW-0003
-
15 45 - - -
M60
IR Point Type
B0 %LEL 0 45 FLD GAH,GAHH-4530-005 FGS N.I.S 3w 4-20mA FGS AI
Switchgear Room Gas Detector
60-GD-4530-005
Gas Detector
21010-BAE-70060-IN-
DW-0003
-
15 45 - - -
M60
IR Point Type
B0 %LEL 0 45 FLD GAH,GAHH-4530-006 FGS N.I.S 3w 4-20mA FGS AI
C&I Room Gas Detector
60-GD-4530-006
Gas Detector
21010-BAE-70060-IN-
DW-0003
-
15 45 - - -
M60
IR Point Type
B0 %LEL 0 45 FLD GAH,GAHH-4530-101 FGS N.I.S 3w 4-20mA FGS AI
E-House Air intake Gas Detector
60-GD-4530-101
Gas Detector
21010-BAE-70060-IN-
DW-0003
-
15 45 - - -
M60
IR Point Type
B0 %LEL 0 45 FLD GAH,GAHH-4530-102 FGS N.I.S 3w 4-20mA FGS AI
E-House Air intake Gas Detector
60-GD-4530-102
Gas Detector
21010-BAE-70060-IN-
DW-0003
-
15 45 - - -
M60
IR Point Type
B0 %LEL 0 45 FLD GAH,GAHH-4530-103 FGS N.I.S 3w 4-20mA FGS AI
E-House Air intake Gas Detector
60-GD-4530-103
Gas Detector
21010-BAE-70060-IN-
DW-0003
-
15 45 - - -
M60
IR Point Type
B0 %LEL 0 45 FLD GAH,GAHH-4530-104 FGS N.I.S 3w 4-20mA FGS AI
E-House Air intake Gas Detector
60-GD-4530-104
Gas Detector
21010-BAE-70060-IN-
DW-0003
-
15 45 - - -
M60
IR Point Type
B0 %LEL 0 45 FLD GAH,GAHH-4530-105 FGS N.I.S 3w 4-20mA FGS AI
E-House Air intake Gas Detector
60-GD-4530-105
Gas Detector
21010-BAE-70060-IN-
DW-0003
-
15 45 - - -
M60
IR Point Type
B0 %LEL 0 45 FLD GAH,GAHH-4530-106 FGS N.I.S 3w 4-20mA FGS AI
E-House Air intake Gas Detector
60-GD-4530-106
Gas Detector
21010-BAE-70060-IN-
DW-0003
-
15 45 - - -
M60
IR Point Type
B0 %LEL 0 45 FLD GAH,GAHH-4530-107 FGS N.I.S 3w 4-20mA FGS AI
E-House Air intake Gas Detector
60-GD-4530-107
Gas Detector
21010-BAE-70060-IN-
DW-0003
-
15 45 - - -
M60
IR Point Type
B0 %LEL 0 45 FLD GAH,GAHH-4530-108 FGS N.I.S 3w 4-20mA FGS AI
E-House Air intake Gas Detector
60-GD-4530-108
Gas Detector
21010-BAE-70060-IN-
DW-0003
-
15 45 - - -
M60
IR Point Type
B0 %LEL 0 45 FLD GAH,GAHH-4530-109 FGS N.I.S 3w 4-20mA FGS AI
E-House Air intake Gas Detector
60-GD-4530-109
Gas Detector
21010-BAE-70060-IN-
DW-0003
-
15 45 - - -
M60
IR Point Type
B1 %LEL 0 60 FLD GAH,GAHH-4530-026 FGS N.I.S 3w 4-20mA FGS AI
Store-1 Air Intake Gas Detector
60-GD-4540-026
Gas Detector
21010-BAE-70060-IN-
DW-0003
-
20 60 - - -
M60
IR Point Type
B1 %LEL 0 60 FLD GAH,GAHH-4530-027 FGS N.I.S 3w 4-20mA FGS AI
Store-1 Air Intake Gas Detector
60-GD-4540-027
Gas Detector
21010-BAE-70060-IN-
DW-0003
-
20 60 - - -
M60
IR Point Type
B1 %LEL 0 60 FLD GAH,GAHH-4530-028 FGS N.I.S 3w 4-20mA FGS AI
Store-2 Air Intake Gas Detector
60-GD-4540-028
Gas Detector
21010-BAE-70060-IN-
DW-0003
-
20 60 - - -
M60
IR Point Type
B1 %LEL 0 60 FLD GAH,GAHH-4530-029 FGS N.I.S 3w 4-20mA FGS AI
Store-2 Air Intake Gas Detector
60-GD-4540-029
Gas Detector
21010-BAE-70060-IN-
DW-0003
-
20 60 - - -
M60
Point Type
A0 TBA TBA TBA FLD - FGS N.I.S VFC FGS DI
Switch Gear Room Heat Detector
60-HD-4530-001
Heat Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Point Type
A0 TBA TBA TBA FLD - FGS N.I.S VFC FGS DI
Control & Instrument Room Heat Detector
60-HD-4530-002
Heat Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Point Type
A0 TBA TBA TBA FLD - FGS N.I.S VFC FGS DI
Store 1 Heat Detector
60-HD-4540-001
Heat Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Point Type
A0 TBA TBA TBA FLD - FGS N.I.S VFC FGS DI
Store 1 Heat Detector
60-HD-4540-002
Heat Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Point Type
A0 TBA TBA TBA FLD - FGS N.I.S VFC FGS DI
Store 2 Heat Detector
60-HD-4540-003
Heat Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
Rev
BUMI ARMADA
ENGINEERING
I/O
Destination
1014-M00-ILS-003 OTE Doc. Number:
Function Tag Remarks Tag No Module
21010-BAE-70000-IN-RL-0003
Page
Revision:
BAE Doc. Number:
FGS I/O LIST
CHARTER HIRE OF FPSO FOR D1 FIELD
B2
8/11
I.S /
Non I.S
Instrument Service Instrument Type F&G Loc. Plan
Dwg No.
I/O Type System I/OSource Signal Type Disp. Range Units Alarm
LoLo
Alarm
Lo
Alarm
Hi
Alarm
HiHi
Set
Point Operating principle
M60
Catalytic
A0 TBA TBA TBA FLD - FGS N.I.S 3w 4-20mA FGS AI
Battery Room Hydrogen gas Detecor
60-HYD-4530-001
Hydrogen Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Catalytic
A0 TBA TBA TBA FLD - FGS N.I.S 3w 4-20mA FGS AI
Battery Room Hydrogen gas Detecor
60-HYD-4530-002
Hydrogen Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
-
A0 - - - FLD - FGS N.I.S VFC FGS DI
Transformer Room MAC
60-MAC-4530-001
Manual Alarm Call Point
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
-
A0 - - - FLD - FGS N.I.S VFC FGS DI
Battery Room MAC
60-MAC-4530-002
Manual Alarm Call Point
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
-
A0 - - - FLD - FGS N.I.S VFC FGS DI
Switchgear Room MAC
60-MAC-4530-003
Manual Alarm Call Point
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
-
A0 - - - FLD - FGS N.I.S VFC FGS DI
C&I Room MAC
60-MAC-4530-004
Manual Alarm Call Point
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Photo Electric/Ionisation
A0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
Battery room (Ceiling) Smoke Detector
60-SD-4530-0006
Smoke Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Photo Electric/Ionisation
A0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
Transformer room (Ceiling) Smoke Detector
60-SD-4530-001
Smoke Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Photo Electric/Ionisation
A0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
Transformer room (Ceiling) Smoke Detector
60-SD-4530-002
Smoke Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Photo Electric/Ionisation
A0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
Transformer room (Ceiling) Smoke Detector
60-SD-4530-003
Smoke Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Photo Electric/Ionisation
A0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
Transformer room (Ceiling) Smoke Detector
60-SD-4530-004
Smoke Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Photo Electric/Ionisation
A0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
Battery room (Ceiling) Smoke Detector
60-SD-4530-005
Smoke Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Photo Electric/Ionisation
A0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
Switch Gear Room (Ceiling) Smoke Detector
60-SD-4530-007
Smoke Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Photo Electric/Ionisation
A0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
Switch Gear Room (Ceiling) Smoke Detector
60-SD-4530-008
Smoke Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Photo Electric/Ionisation
A0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
Switch Gear Room (Ceiling) Smoke Detector
60-SD-4530-009
Smoke Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Photo Electric/Ionisation
A0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
Switch Gear Room (Ceiling) Smoke Detector
60-SD-4530-010
Smoke Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Photo Electric/Ionisation
A0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
C&I Room (Ceiling) Smoke Detector
60-SD-4530-011
Smoke Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Photo Electric/Ionisation
A0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
C&I Room (Ceiling) Smoke Detector
60-SD-4530-012
Smoke Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Photo Electric/Ionisation
A0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
Battery room (Ceiling) Smoke Detector
60-SD-4530-013
Smoke Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Photo Electric/Ionisation
A0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
Switch Gear Room (False Floor) Smoke
Detecotor
60-SD-4530-021
Smoke Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Photo Electric/Ionisation
A0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
Switch Gear Room (False Floor) Smoke
Detecotor
60-SD-4530-022
Smoke Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Photo Electric/Ionisation
A0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
Switch Gear Room (False Floor) Smoke
Detecotor
60-SD-4530-023
Smoke Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Photo Electric/Ionisation
A0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
Switch Gear Room (False Floor) Smoke
Detecotor
60-SD-4530-024
Smoke Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Photo Electric/Ionisation
A0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
Switch Gear Room (False Floor) Smoke
Detecotor
60-SD-4530-025
Smoke Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Photo Electric/Ionisation
A0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
Instrument (False Floor) Smoke Detecotor
60-SD-4530-026
Smoke Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Photo Electric/Ionisation
A0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
Instrument (False Floor) Smoke Detecotor
60-SD-4530-027
Smoke Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Photo Electric/Ionisation
A0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
Instrument (False Floor) Smoke Detecotor
60-SD-4530-028
Smoke Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Photo Electric/Ionisation
A0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
Store 1 (Ceiling) Smoke Detector
60-SD-4540-001
Smoke Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
Rev
BUMI ARMADA
ENGINEERING
I/O
Destination
1014-M00-ILS-003 OTE Doc. Number:
Function Tag Remarks Tag No Module
21010-BAE-70000-IN-RL-0003
Page
Revision:
BAE Doc. Number:
FGS I/O LIST
CHARTER HIRE OF FPSO FOR D1 FIELD
B2
9/11
I.S /
Non I.S
Instrument Service Instrument Type F&G Loc. Plan
Dwg No.
I/O Type System I/OSource Signal Type Disp. Range Units Alarm
LoLo
Alarm
Lo
Alarm
Hi
Alarm
HiHi
Set
Point Operating principle
M60
Photo Electric/Ionisation
A0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
Store 1 (Ceiling) Smoke Detector
60-SD-4540-002
Smoke Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
Photo Electric/Ionisation
A0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
Store 2 (Ceiling) Smoke Detector
60-SD-4540-003
Smoke Detector
21010-BAE-70060-IN-
DW-0003
-
- - - - -
M60
-
B1 - - - FGS NA FGS N.I.S 24V DC ESD DO
Flash Helideck Handing Lights
60-XI-3004
Helideck
NA -
NA NA NA NA NA
M60
-
B1 - - - FGS NA FGS N.I.S VFC EMG.GEN DO
Inhibit Emergency Generator Start
60-XS-0011
Command
NA -
NA NA NA NA NA
M60
-
B1 - - - FGS NA FGS N.I.S VFC EMG.GEN DO
Trip Emergency Generator Start
60-XS-0012
Command
- -
NA NA NA NA NA
M60
-
B1 - - - FGS NA FGS N.I.S VFC PAGA-A DO
General Alarm to PAGA A
60-XS-4104A
PAGA Interface
- -
NA NA NA NA NA
M60
-
B1 - - - FGS NA FGS N.I.S VFC PAGA-B DO
General Alarm to PAGA B
60-XS-4104B
PAGA Interface
- -
NA NA NA NA NA
M60
-
B1 - - - FGS NA FGS N.I.S VFC PAGA-A DO
Confirm Frie/Gas Alram to PAGA system A
60-XS-4105A
PAGA Interface
- -
NA NA NA NA NA
M60
-
B1 - - - FGS NA FGS N.I.S VFC PAGA-A DO
Confirm Frie/Gas Alram to PAGA system B
60-XS-4105B
PAGA Interface
- -
NA NA NA NA NA
M60
-
B1 - - - FGS NA FGS N.I.S VFC SWBD 7720 DO
Trip Essential Feeder to E-House at Emergency
SWB
60-XS-5143
Shunt Trip
70000-IN-RL-0007 -
NA NA NA NA NA
M60
Inergen System -
B1 - - - FGS NA FGS N.I.S VFC Inergen Sys. DO
Initiate inertgas Release Battery Room
60-XS-7522
Inergen Interface
- -
NA NA NA NA NA
M60
-
B1 - - - FGS NA FGS N.I.S VFC Batt Charger DO
Trip UPS Batt. Charger A&B
60-XS-7525
Battery Panel Interface
- -
NA NA NA NA NA
M60
Damper -
B1 - - - FGS NA FGS N.I.S VFC E-Hse HVAC DO
Trip Transformer Rm Ventilation Fan & Close Fire
60-XS-7610
HVAC Interface
- -
NA NA NA NA NA
M60
-
B1 - - - FGS NA FGS N.I.S VFC Inergen Sys. DO
Release Transformer Room Inergen System
60-XS-7612
Inergen Interface
- -
NA NA NA NA NA
M60
Damper -
B1 - - - FGS NA FGS N.I.S VFC E-Hse HVAC DO
Trip Battery Rm Ventilation Fan & Close Fire
60-XS-7620
HVAC Interface
- -
NA NA NA NA NA
M60
-
B1 - - - FGS NA FGS N.I.S VFC E-Hse HVAC DO
E-House HVAC 1&2 Close Fire Damper
60-XS-7630
HVAC Interface
- -
NA NA NA NA NA
M60
release -
B1 - - - FGS NA FGS N.I.S VFC E-Hse HVAC DO
E-House switchgear & instrument Room inert gas
60-XS-7632
HVAC Interface
- -
NA NA NA NA NA
M60
-
B1 - - - FGS NA FGS N.I.S VFC FWD FWLCP DO
Engineroom Firewater Pump start
60-XS-8100
FWPump Interface
- -
NA NA NA NA NA
M60
-
B1 - - - FGS NA FGS N.I.S VFC Fwd FWRm DO
Trip FWD FWP Room Vent Fan & Close Fire
Damper
60-XS-8111
Interface Signal
- -
NA NA NA NA NA
M60
-
B1 - - - FGS NA FGS N.I.S VFC Lab HVAC DO
Store-1 HVAC System Trip
60-XS-9711
Interface Signal
- -
NA NA NA NA NA
M60
-
B1 - - - FGS NA FGS N.I.S VFC Store HVAC DO
Store-1 Fire Dampers CLose Trip
60-XS-9712
Interface Signal
- -
NA NA NA NA NA
M60
-
B1 - - - FGS NA FGS N.I.S VFC Lab HVAC DO
Store-2 HVAC System Trip
60-XS-9721
Interface Signal
- -
NA NA NA NA NA
M60
-
B1 - - - FGS NA FGS N.I.S VFC Store HVAC DO
Store-2 Fire Dampers CLose Trip
60-XS-9722
Interface Signal
- -
NA NA NA NA NA
M60
-
B1 - - - FGS NA FGS N.I.S VFC ESD DO
Workshop HVAC system Trip
60-XS-9731
ESD Interface
- -
NA NA NA NA NA
M60
-
B1 - - - FGS NA FGS N.I.S VFC ESD DO
Workshop Fire Dampers close
60-XS-9732
ESD Interface
- -
NA NA NA NA NA
M60
-
B1 - - - FGS NA FGS N.I.S VFC FLD DO
FWDeluge to Zone A Module 10,20 Open
60-XY-8100
Deluge Valve SOV
55570-MA-DW-0003 -
NA NA NA NA NA
M60
-
B1 - - - FGS NA FGS N.I.S VFC FLD DO
FWDeluge to Zone c Modules 55,90, Open
60-XY-8102
Deluge Valve SOV
55570-MA-DW-0003 -
NA NA NA NA NA
M60
-
B1 - - - FGS NA FGS N.I.S VFC FLD DO
FWDeluge to Zone-B M30 Open
60-XY-8103
Deluge Valve SOV
55570-MA-DW-0005 -
NA NA NA NA NA
Rev
BUMI ARMADA
ENGINEERING
I/O
Destination
1014-M00-ILS-003 OTE Doc. Number:
Function Tag Remarks Tag No Module
21010-BAE-70000-IN-RL-0003
Page
Revision:
BAE Doc. Number:
FGS I/O LIST
CHARTER HIRE OF FPSO FOR D1 FIELD
B2
10/11
I.S /
Non I.S
Instrument Service Instrument Type F&G Loc. Plan
Dwg No.
I/O Type System I/OSource Signal Type Disp. Range Units Alarm
LoLo
Alarm
Lo
Alarm
Hi
Alarm
HiHi
Set
Point Operating principle
M60
-
B1 - - - FGS NA FGS N.I.S VFC ESD DO
FPSO ESD Level-1
60-XZ-0001
ESD Interface
NA -
NA NA NA NA NA
M60
-
B0 - - - LCP NA FGS N.I.S 24V DC FGS DO
Confirmed Fire at Topside
60-XZ-0001A
ESD Interface
- -
- - - - -
M60
-
B1 - - - FGS NA FGS N.I.S VFC ESD DO
FPSO ESD Level-1
60-XZ-0002
ESD Interface
NA -
NA NA NA NA NA
M60
-
B0 - - - LCP NA FGS N.I.S 24V DC FGS DO
Confirmed Gas at Topside
60-XZ-0002A
ESD Interface
- -
- - - - -
M70
Multi Spectrum IR
B0 mA 0 20 FLD FAH,FAHH-4540-014 FGS N.I.S 3w 4-20mA FGS AI
Power Gen/N2&Air System FlameDetector
70-FD-4540-014
Flame Detector
21010-BAE-70070-IN-
DW-0003
-
16 20 - - -
M70
Multi Spectrum IR
B0 mA 0 20 FLD FAH,FAHH-4540-015 FGS N.I.S 3w 4-20mA FGS AI
Power Gen/N2&Air System Flame Detector
70-FD-4540-015
Flame Detector
21010-BAE-70070-IN-
DW-0003
-
16 20 - - -
M70
Multi Spectrum IR
B0 mA 0 20 FLD FAH,FAHH-4540-016 FGS N.I.S 3w 4-20mA FGS AI
Power Gen/N2&Air System Flame Detector
70-FD-4540-016
Flame Detector
21010-BAE-70070-IN-
DW-0003
-
16 20 - - -
M70
Multi Spectrum IR
B0 mA 0 20 FLD FAH,FAHH-4540-017 FGS N.I.S 3w 4-20mA FGS AI
Power Gen/N2&Air System Flame Detector
70-FD-4540-017
Flame Detector
21010-BAE-70070-IN-
DW-0003
-
16 20 - - -
M70
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-023 FGS N.I.S 3w 4-20mA FGS AI
Power Gen/N2&Air System GasDetector
70-GD-4530-023
Gas Detector
21010-BAE-70070-IN-
DW-0003
-
20 60 - - -
M70
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-023 FGS N.I.S 3w 4-20mA FGS AI
Power Gen/N2&Air System GasDetector
70-GD-4530-024
Gas Detector
21010-BAE-70070-IN-
DW-0003
-
20 60 - - -
M70
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-024 FGS N.I.S 3w 4-20mA FGS AI
Power Gen/N2&Air System Gas Detector
70-GD-4530-025
Gas Detector
21010-BAE-70070-IN-
DW-0003
-
20 60 - - -
M70
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-041 FGS N.I.S 3w 4-20mA FGS AI
Ai rCompressor package Gas Detector (Air
Intake)
70-GD-4540-041
Gas Detector
21010-BAE-70070-IN-
DW-0003
-
20 60 - - -
M70
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-042 FGS N.I.S 3w 4-20mA FGS AI
Air Compressor package Gas Detector (Air
Intake)
70-GD-4540-042
Gas Detector
21010-BAE-70070-IN-
DW-0003
-
20 60 - - -
M70
IR Point Type
B0 %LEL 0 60 FLD GAH,GAHH-4540-043 FGS N.I.S 3w 4-20mA FGS AI
Air Compressor package Gas Detector (Air
Intake)
70-GD-4540-043
Gas Detector
21010-BAE-70070-IN-
DW-0003
-
20 60 - - -
M70
-
A0 - - - FLD - FGS N.I.S VFC FGS DI
Power Gen/N2&Air System MAC
70-MAC-4540-007
Manual Alarm Call Point
21010-BAE-70070-IN-
DW-0003
-
- - - - -
M90
Multi Spectrum IR
B0 mA 0 20 FLD FAH,FAHH-4540-018 FGS N.I.S 3w 4-20mA FGS AI
Laydown/chemical injection FlameDetector
90-FD-4540-018
Flame Detector
21010-BAE-70090-IN-
DW-0003
-
16 20 - - -
M90
Multi Spectrum IR
B0 mA 0 20 FLD FAH,FAHH-4540-019 FGS N.I.S 3w 4-20mA FGS AI
Laydown/chemical injection Flame Detector
90-FD-4540-019
Flame Detector
21010-BAE-70090-IN-
DW-0003
-
16 20 - - -
M90
Multi Spectrum IR
B0 mA 0 20 FLD FAH,FAHH-4540-020 FGS N.I.S 3w 4-20mA FGS AI
Laydown/chemical injection Flame Detector
90-FD-4540-020
Flame Detector
21010-BAE-70090-IN-
DW-0003
-
16 20 - - -
M90
IR Point Type
B1 %LEL 0 60 FLD GAH,GAHH-4540-044 FGS N.I.S 3w 4-20mA FGS AI
E&I workshop Air Intake Gas Detector
90-GD-4540-044
Gas Detector
21010-BAE-70090-IN-
DW-0003
-
20 60 - - -
M90
IR Point Type
B1 %LEL 0 60 FLD GAH,GAHH-4540-045 FGS N.I.S 3w 4-20mA FGS AI
E&I workshop Air Intake Gas Detector
90-GD-4540-045
Gas Detector
21010-BAE-70090-IN-
DW-0003
-
20 60 - - -
M90
IR Point Type
B1 %LEL 0 60 FLD GAH,GAHH-4540-046 FGS N.I.S 3w 4-20mA FGS AI
Workshop Air Intake Gas Detector
90-GD-4540-046
Gas Detector
21010-BAE-70090-IN-
DW-0003
-
20 60 - - -
M90
IR Point Type
B1 %LEL 0 60 FLD GAH,GAHH-4540-047 FGS N.I.S 3w 4-20mA FGS AI
Workshop Air Intake Gas Detector
90-GD-4540-047
Gas Detector
21010-BAE-70090-IN-
DW-0003
-
20 60 - - -
M90
Point Type
B0 - - - FLD - FGS N.I.S VFC FGS DI
E&I Work shop Heat Detector
90-HD-4540-004
Heat Detector
21010-BAE-70090-IN-
DW-0003
-
- - - - -
M90
Point Type
B0 - - - FLD - FGS N.I.S VFC FGS DI
E&I Work shop Heat Detector
90-HD-4540-005
Heat Detector
21010-BAE-70090-IN-
DW-0003
-
- - - - -
M90
Point Type
B0 - - - FLD - FGS N.I.S VFC FGS DI
Work shop Heat Detector
90-HD-4540-006
Heat Detector
21010-BAE-70090-IN-
DW-0003
-
- - - - -
M90
Point Type
B0 - - - FLD - FGS N.I.S VFC FGS DI
Work shop Heat Detector
90-HD-4540-007
Heat Detector
21010-BAE-70090-IN-
DW-0003
-
- - - - -
M90
-
A0 - - - FLD - FGS N.I.S VFC FGS DI
Laydown /Chemical Injection MAC
90-MAC-4540-008
Manual Alarm Call Point
21010-BAE-70090-IN-
DW-0003
-
- - - - -
M90
Photo Electric/Ionisation
B0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
E&I Workshop Smoke Detector
90-SD-4540-004
Smoke Detector
21010-BAE-70090-IN-
DW-0003
-
- - - - -
Rev
BUMI ARMADA
ENGINEERING
I/O
Destination
1014-M00-ILS-003 OTE Doc. Number:
Function Tag Remarks Tag No Module
21010-BAE-70000-IN-RL-0003
Page
Revision:
BAE Doc. Number:
FGS I/O LIST
CHARTER HIRE OF FPSO FOR D1 FIELD
B2
11/11
I.S /
Non I.S
Instrument Service Instrument Type F&G Loc. Plan
Dwg No.
I/O Type System I/OSource Signal Type Disp. Range Units Alarm
LoLo
Alarm
Lo
Alarm
Hi
Alarm
HiHi
Set
Point Operating principle
M90
Photo Electric/Ionisation
B0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
E&I Workshop Smoke Detector
90-SD-4540-005
Smoke Detector
21010-BAE-70090-IN-
DW-0003
-
- - - - -
M90
Photo Electric/Ionisation
B0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
Workshop Smoke Detector
90-SD-4540-006
Smoke Detector
21010-BAE-70090-IN-
DW-0003
-
- - - - -
M90
Photo Electric/Ionisation
B0 - - - E-House - FGS N.I.S 2W4-20mA FGS AI
Workshop Smoke Detector
90-SD-4540-007
Smoke Detector
21010-BAE-70090-IN-
DW-0003
-
- - - - -