Você está na página 1de 294

ELECTRIC DISTRIBUTION

CONSTRUCTION
STANDARDS









2013 EDITION
Scope

City Utilities of Springfield, Missouri must ensure its electric distribution system is
designed, constructed, operated, and maintained in accordance with all applicable
provisions of the most current and accepted criteria of the National Electrical Safety
Code (NESC) and all applicable electrical and safety requirements of State and local
governmental entities. All electrical standards established by City Utilities are in
addition to, and not in substitution for or a modification of, the most current and accepted
criteria of the NESC and all applicable electrical and safety requirements of State and
local governmental entities.

The specifications herein cover the material and construction details for overhead and
underground electric distribution for City Utilities, and are intended to meet or exceed the
minimum requirements of the most current and accepted criteria of the NESC. The text
and drawings are intended to coordinate with and supplement each other, and to establish
consistency in the design of additions and modifications to the City Utilities electric
distribution system.


Application

These specifications and standards of construction shall be followed without deviation for
all new construction and renewals or replacements of existing electric facilities. When
conditions require deviation from standard construction, approval must be obtained from
Electric T&D Engineering.

Existing lines shall not be changed solely to conform to these specifications unless
required to eliminate hazardous conditions, or when specifically directed. Generally, the
following procedure shall be observed:

a) When new poles are installed, all construction on the pole shall conform to
these specifications.

b) When additional circuits are installed, existing conductors are replaced, or
conductor sizes are increased, the arrangement of circuits, clearances, and
strength of guying and supporting structures to which the additional
circuits or new conductors are attached, shall conform to these
specifications.

c) When new primary and secondary distribution facilities are installed, all
construction shall conform to these specifications.

Every project design package shall include drawings and construction details referencing
these specifications, indicate the required materials to be used, and provide any other
information necessary to adequately represent the construction to be performed.

Any details of these specifications not clearly understood shall be referred to Electric
T&D Engineering. These standards shall be reviewed and updated regularly by the
Electric T&D Standards Committee. Suggestions for changes to these specifications
should be submitted in writing to the Supervisor Electric T&D Engineering. If further
review indicates a suggestion will achieve improvements in safety, operations, and/or
economics, the suggestion will be considered for incorporation into these standards.
Updates will be made to the standards annually and provided in bound and/or electronic
format to assigned users.
ANC-1
ANC-2
ANC-3*
ANC-S*
DG-P*
DG-N*
DG-L1
SG-*
OHG-*
DOWNGUY, SIDEWALK
ANCHOR, HEAVY DUTY
ANCHOR, ROCK
ANCHORS
GUYS
DOWNGUY, PHASE
DOWNGUY, NEUTRAL
ANCHOR, SCREW-IN
ANCHORS / GUYS INDEX
ANCHOR, STANDARD DUTY
OVERHEAD GUY
DOWNGUY, STREETLIGHT / SECONDARY
City Utilities of Springfield, Missouri
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
ROD SIZE
3/4"
3/4"
1"
1"
1"
2,000 2,500 3,000 3,500 4,000 4,500
SCREW- IN-ANCHORS
APPLICATION GUIDE
ANCHOR TYPE # & SIZE OF GUYS MIN. TORQUE
GUY WIRE STRENGTH
12,000 17,000 20,000 N/A
* ULTIMATE STRENGTH FOR 3/4" ANCHOR ROD = 23,000#
** ULTIMATE STRENGTH FOR 1" ANCHOR ROD = 36,000#
MAX TORQUE
1- 3/8" SIEMENS 2,000 ' # 3,000 ' #
ANCHOR TYPE INSTALLATION TORQUE (In Foot lbs)
ANC-S2
10" SINGLE HELIX
ANC-S2
10" SINGLE HELIX 2- 3/8" SIEMENS 2,000 ' # 4,500 ' #
1 - 7/16" EHS 3,000 ' # 4,500 ' #
SCREW- IN-ANCHORS
ESTIMATED HOLDING STRENGTH
1 - 7/16" EHS 2,500 ' # 4,500 ' #
ANC-S3
12" SINGLE HELIX
ANC-S1
8" SINGLE HELIX
ANC-S1
8" SINGLE HELIX 2- 3/8" SIEMENS 2,500 ' # 3,000 ' #
N/A
15,000 18,000 21,000 25,000 27,000 31,000
N/A
34,000 18,000 21,000 24,000 27,000 30,000
ULTIMATE STRENGTH FOR 3/8" SEIMENS-MARTIN = 6,950#
ULTIMATE STRENGTH FOR 7/16" EHS = 20,800#
WHEN THE SCREW-IN -ANCHOR AND ROD ARE PROPERLY INSTALLED:
THE ANCHOR WILL HAVE BEEN INSTALLED WITHIN THE MINIMUM AND MAXIMUM
TORQUE LIMITS, AND THE TWINEYE NUT SHOULD BE BETWEEN 6" AND 10" ABOVE THE
UNDISTURBED GRADE.
ANC-S1
8" SINGLE HELIX
WITH 3/4" ROD *
ANC-S2
10" SINGLE HELIX
WITH 1" ROD **
ANC-S3
12" SINGLE HELIX
WITH 1" ROD **
ANCHOR ROD STRENGTH
CAP-BK*
CAP-TSC
CAP-VSC
CAP-MISC
CAPACITOR CONTROLS
VAR, SWITCH CONTROL
CAPACITOR EQUIPMENT
MISCELLANEOUS CAPACITOR REPAIR EQUIPMENT
TIME / TEMPERATURE, SWITCH CONTROL
CAPACITORS INDEX
CAPACITOR BANKS
CAPACITOR BANK (WITH OIL SWITCHES) (WITHOUT CONTROL)
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
City Utilities of Springfield, Missouri
OH-COND
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
City Utilities of Springfield, Missouri
CONDUCTORS INDEX
OVERHEAD CONDUCTOR STANDARDS
XM-4
XM-6
XM-8
XM-EHS
XM-F10C
XM-F10N
CROSSARM, FIBERGLASS, 10', CN, DEADEND
CROSSARM, WOOD, 4 PIN
CROSSARM, WOOD, EHS
CROSSARM, WOOD, 6 PIN
CROSSARM, WOOD, 8 PIN
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
City Utilities of Springfield, Missouri
CROSSARMS INDEX
CROSSARM, FIBERGLASS, 10' NCN, DEADEND
G1
G2
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
City Utilities of Springfield, Missouri
GROUNDING INDEX
GROUNDING ASSEMBLY, GROUND ROD
GROUNDING ASSEMBLY, GROUND PLATE
MISC-DE*
MISC-PI*
MISC-SR*
SEC-BKR*
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
City Utilities of Springfield, Missouri
HARDWARE INDEX
DEADEND ASSEMBLIES
PIN INSULATOR ASSEMBLIES
SECONDARY INSULATOR ASSEMBLIES
SECONDARY BREAKER, 1/0 ACSR ALUM & COPPER SECONDARY
WP-*
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
City Utilities of Springfield, Missouri
POLES INDEX
WOOD POLES
A1
A1-NC
A2
A2-NC
A3
A4
A4-NC
A5
A5-NC
A6
A6-NC
C1-*
C1-D*
C1-U*
C1-UD*
C1-NC
C1-V*
C2-*
C2-NC* 3-PHASE, SMALL ANGLE, NON-COMMON NEUTRAL
C2-V*
C3-*
C4-*
C5-*
C7-F*
C7-FNC*
C7
C7-H*
C7-NC
C7-NCH 3-PHASE, CROSSARM DEADEND, NON COMMON NEUTRAL, HEAVY
C8-*
C8-NC*
C1- HEND
C2-HEND
C7-HEND
HEND-TAP
3-PHASE, CROSSARM DOUBLE DEADEND, NON COMMON NEUTRAL
HENDRIX
3-PHASE, TANGENT, 397 HENDRIX
3-PHASE, SMALL ANGLE, 397 HENDRIX
3-PHASE, DEADEND, 397 HENDRIX
HENDRIX CABLE, TAP INSTALLATION
3-PHASE, FIBERGLASS CROSSARM DEADEND, CN
3-PHASE, FIBERGLASS CROSSARM DEADEND, NCN
3-PHASE, CROSSARM DEADEND, #2 ACSR
3-PHASE, CROSSARM DEADEND, HEAVY
3-PHASE, CROSSARM DEADEND, NON COMMON NEUTRAL
3-PHASE, CROSSARM DOUBLE DEADEND
3-PHASE, VERTICAL TANGENT, 2ACSR
3-PHASE, SMALL ANGLE
3-PHASE, VERTICAL SMALL ANGLE
3-PHASE, SWING CORNER, 2ACSR
3-PHASE, VERTICAL, LARGE ANGLE
3-PHASE, VERTICAL DEADEND
3-PHASE
3-PHASE, TANGENT, 2ACSR
3-PHASE, DOUBLE CROSSARM TANGENT, 636ACSR
3-PHASE, TANGENT, UNDERBUILD
3-PHASE, DOUBLE CROSSARM TANGENT, UNDERBUILD
3-PHASE, TANGENT, NON-COMMON NEUTRAL
1-PHASE, LARGE ANGLE, 2ACSR
1-PHASE, LARGE ANGLE, 2ACSR, NON-COMMON NEUTRAL
1-PHASE, DEADEND, 2ACSR
1-PHASE, DEADEND, NON-COMMON NEUTRAL, 2ACSR
1-PHASE, DOUBLE DEADEND, 2ACSR
1-PHASE, DOUBLE DEADEND, NON-COMMON NEUTRAL, 2ACSR
1-PHASE
1-PHASE, TANGENT, 2ACSR
1-PHASE, TANGENT, NON-COMMON NEUTRAL, 2ACSR
1-PHASE, SMALL ANGLE, 2ACSR
1-PHASE, SMALL ANGLE, NON-COMMON NEUTRAL, 2ACSR
1-PHASE, SWING CORNER, 2ACSR
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
City Utilities of Springfield, Missouri
SECTION 8 - POLE TOP ASSEMBLIES
C7-PMO
C7-PMU
3-PHASE, PRI METER POLE, CUSTOMER OVERHEAD SERVICE
3-PHASE, PRI METER POLE, CUSTOMER UNDERGROUND SERVICE
City Utilities of Springfield, Missouri
PRIMARY METERING INDEX
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
REG-100
REG-219
City Utilities of Springfield, Missouri
REGULATORS INDEX
1-PHASE, VOLTAGE REGULATOR, 100A
1-PHASE, VOLTAGE REGULATOR, 219A
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
CO-*-*
LA-*
REC-1
REC-3
US-LB
US-NLB
US-TIE
US-GP*
SWITCH, UNDERSLUNG, 3-PHASE, 900A, NON LOAD BREAK
SWITCH, UNDERSLUNG, 3-PHASE, 900A, NON LOAD BREAK TIE
SWITCH, GROUP OPERATED
LIGHTNING ARRESTER ASSEMBLIES
1-PHASE, RECLOSER, VACUUM, SOLID DIELECTRIC, PROGRAMABLE
3-PHASE, OIL RECLOSER
SWITCH, UNDERSLUNG, 3-PHASE, 600A, LOAD BREAK (RET ONLY)
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
City Utilities of Springfield, Missouri
SECTIONALIZING / PROTECTION INDEX
CUTOUT ASSEMBLIES
TR-CSP-*
TR2B-*
TBD-75
TBD-100
TBD-150
TBD-200
TBD-300
TBD-367
TBY-75
TBY-150
TBY-300
TBY-75C
TBY-150C
TBY-300C
TBK-OD
XFMR-* CONVENTIONAL, 2 BUSHING, TRANSFORMER UPGRADES
3-PHASE, TRANSFORMER BANK, 300KVA (120/240V DELTA)
3-PHASE, TRANSFORMER BANK, 367KVA (120/240V DELTA)
3-PHASE, TRANSFORMER BANK, 75KVA (120/208V WYE)
3-PHASE, TRANSFORMER BANK, 150KVA (120/208V WYE)
3-PHASE, TRANSFORMER BANK, 300KVA (120/208V WYE)
3-PHASE, OPEN WYE-OPEN DELTA BANK (RETIREMENT ONLY)
1-PHASE, TRANSFORMER, COMPLETELY SELF-PROTECTED
1-PHASE, TRANSFORMER, 2 BUSHING, 10KVA (120/240V)
3-PHASE, TRANSFORMER BANK, 75KVA (120/240V DELTA)
3-PHASE, TRANSFORMER BANK, 100KVA (120/240V DELTA)
3-PHASE, TRANSFORMER BANK, 150KVA (120/240V DELTA)
3-PHASE, TRANSFORMER BANK, 200KVA (120/240V DELTA)
3-PHASE, TRANSFORMER BANK, 75KVA (277/480V WYE)
3-PHASE, TRANSFORMER BANK, 150KVA (277/480V WYE)
3-PHASE, TRANSFORMER BANK, 300KVA (277/480V WYE)
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
City Utilities of Springfield, Missouri
SECTION 12 - TRANSFORMERS
UG-CABLE
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
City Utilities of Springfield, Missouri
CABLES INDEX
UNDERGROUND CABLE STANDARDS
CONDUIT
ELH*
ELV*
ELH-H*
ELV-H* CONDUIT ELBOWS FOR VERTICAL BENDS, HDPE CONDUIT RUNS
CONDUIT ELBOWS FOR HORIZONTAL BENDS, RIGID / PVC CONDUIT RUNS
CONDUIT ELBOWS FOR VERTICAL BENDS, RIGID / PVC CONDUIT RUNS
CONDUIT ELBOWS FOR HORIZONTAL BENDS, HDPE CONDUIT RUNS
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
City Utilities of Springfield, Missouri
CONDUIT / DUCT INDEX
CONDUIT SPECIFICATIONS
PD-TRP
PD-TR
PD-TR1
PD-TR2
PD-TR3
PD-TR4
PD-PFC
PD-PMC-2
PD-PMC-6
PD-SJC
PD-ATC2
PD-ATSC6
PV-61
VL-PV61
VL-PV611
PV-62
VL-PV62
PV-C*
PRIMARY VAULT, 3-PHASE, 600A, 36X 11
VAULT LID FOR PV-6-2 VAULT, JUNCTION CABINET
PRIMARY VAULT, CONDUIT INSTALLATION
PAD, 3-PHASE, 600A, AUTOMATIC TRANSFER SWITCH (S&C)
PRIMARY VAULT, 3-PHASE, 600A, 11X 7
VAULT LID FOR PV-6-1 VAULT, SW GEAR OR JUN CAB OR COOPER ATS
VAULT LID, 3-PHASE, 600A, PRIMARY METER CABINET OR S & C ATS
PAD, 3-PHASE, 200A, PRIMARY METER CABINET
PAD, 3-PHASE, 600A, PRIMARY METER CABINET
PAD, 3000A SECONDARY JUNCTION CABINET
PAD, 3-PHASE, 200A, AUTOMATIC TRANSFER SWITCH (COOPER)
PAD, 3-PHASE, 200A, TRANSFORMER (750-1000KVA)
PAD, 3-PHASE, 200A, TRANSFORMER (1500-2000KVA)
PAD, 3-PHASE, 200A, TRANSFORMER (25000KVA)
PAD, 3-PHASE, 200A, PRIMARY FUSE CABINET
PADS / VAULTS / LIDS INDEX
PAD, PLASTIC, 1-PHASE, 200A, TRANSFORMER
PAD, CONCRETE, 1-PHASE, 200A, TRANSFORMER
PAD, 3-PHASE, 200A, TRANSFORMER (75-500KVA)
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
City Utilities of Springfield, Missouri
MISC-PC
OPEN- PT
LBE-*
NLBE-500
NLBE-750
T-NLBE-5
T-NLBE-7 600A, MANHOLE INSTALLATIONS, NON-LOAD BREAK ELBOW FOR 750 KCM PRI
200A, LOAD BREAK ELBOWS
600A, NON-LOAD BREAK ELBOW FOR 500 KCM PRI
600A, NON-LOAD BREAK ELBOW FOR 750 KCM PRI
600A, MANHOLE INSTALLATIONS, NON-LOAD BREAK ELBOW FOR 500 KCM PRI
City Utilities of Springfield, Missouri
PRIMARY ELBOWS / CONNECTORS INDEX
MISCELLANEOUS PRIMARY CONNECTORS
LOADBREAK, PRIMARY OPEN POINTS
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
PMC-2
PMC-6
3-PHASE, 200A, PRIMARY METER CABINET
3-PHASE, 600A, PRIMARY METER CABINET
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
City Utilities of Springfield, Missouri
PRIMARY METERING INDEX
PR1-*
PR-2*
PR3-*
PR3V-*
PR-4*
PR3-500
PR3-750
PR-6*
3-PHASE, 4 PRIMARY RISER, VERTICAL CONSTRUCTION
3-PHASE, 4 PRIMARY RISER, CONDUIT INSTALLATION
3-PHASE, 600A, 500MCM CU, PRIMARY RISER
3-PHASE, 600A, 750MCM CU, PRIMARY RISER
3-PHASE, 6 PRIMARY RISER CONDUIT INSTALLATION
PRIMARY RISERS INDEX
1-PHASE, 2 PRIMARY RISER
1-PHASE, 2 PRIMARY RISER, CONDUIT INSTALLATION, NO POLE
3-PHASE, 4 PRIMARY RISER, CROSSARM CONSTRUCTION
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
City Utilities of Springfield, Missouri
C-*-*
C-1T-*
C-3T-*
C-SP-*
CONNECTORS FOR SINGLE PHASE PADMOUNTED TRANSFORMERS
CONNECTORS FOR THREE PHASE PADMOUNTED TRANSFORMERS
SUBMERSIBLE CONNECTORS FOR SECONDARY SERVICE & SPLICE PEDESTALS
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
City Utilities of Springfield, Missouri
SECONDARY CONNECTORS INDEX
SECONDARY UNDERGROUND CONNECTORS
SP1-*
SP-2C
SP1-500
SP3-*
SP-4C
SP-SPL
SP-LT
SJC
SECONDARY SPLICE PEDESTAL (3X5X3)
STREET LIGHT PEDESTAL (RETIREMENT ONLY)
SECONDARY JUNCTION CABINET (3000A)
1-PHASE, SECONDARY PEDESTAL, 2" CONDUIT INSTALLATION
1-PHASE, LARGE SECONDARY PEDESTAL
1 & 3-PHASE, LARGE SECONDARY PEDESTAL
1 & 3-PHASE, LARGE SECONDARY PEDESTAL, CONDUIT INSTALLATION
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
City Utilities of Springfield, Missouri
SECONDARY PEDESTALS / CABINETS INDEX
1-PHASE, SECONDARY PEDESTAL, BELOW GRADE
SR1-*
SR-2*
SR1-500
SR3-*
SR-4*
1-PHASE, 500MCM CU
1 & 3-PHASE, 4" SECONDARY RISER
1 & 3-PHASE, 4 SECONDARY RISER CONDUIT INSTALLATION
City Utilities of Springfield, Missouri
SECONDARY RISERS INDEX
1-PHASE, 2", SECONDARY RISERS
1-PHASE, 2 SECONDARY RISER, CONDUIT INSTALLATION
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
JC1-2
JC1-2C
JC3-2
JC3-2C
JC3-6
PFC-LOOP
PFC-RAD
SG3-13C
SG3-22C
SG3-31C
ATS-C2
ATS-C6
ATS-SC6
FI-*
3-PHASE, 600A, AUTOMATIC TRANSFER SWITCH (COOPER)
3-PHASE, 600A, AUTOMATIC TRANSFER SWITCH (S&C)
FAULT INDICATORS
3-PHASE, 600A, SWITCHGEAR, 1-SW & 3-TAP (COOPER)
3-PHASE, 600A, SWITCHGEAR, 2-SW & 2-TAP (COOPER)
3-PHASE, 600A, SWITCHGEAR, 3-SW & 1-TAP (COOPER)
3-PHASE, 200A, AUTOMATIC TRANSFER SWITCH (COOPER)
3-PHASE, 200A, JUNCTION CABINET CONDUIT
3-PHASE, 600A, JUNCTION CABINET
3-PHASE, 200A, PRIMARY FUSE CABINET, LOOP
3-PHASE, 200A, PRIMARY FUSE CABINET, RADIAL (RET ONLY)
SECTIONALIZING / PROTECTION INDEX
1-PHASE, 200A, JUNCTION CABINET
1-PHASE, 200A, JUNCTION CABINET CONDUIT
3-PHASE, 200A, JUNCTION CABINET
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
City Utilities of Springfield, Missouri
UTRD-*
UTLP-*
UX-*A
UX-*B
UX-*C
TRANSFORMER, 3 PHASE 120/208 RADIAL FEED
TRANSFORMER, 3 PHASE 227/480 RADIAL FEED
City Utilities of Springfield, Missouri
TRANSFORMERS INDEX
SINGLE PHASE TRANSFORMER RADIAL FEED
SINGLE PHASE TRANSFORMER LOOP FEED
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
TRANSFORMER, 3 PHASE 120/240 RADIAL FEED
UT-*
UT-6* TRENCH DETAIL, 600 AMP
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
City Utilities of Springfield, Missouri
TRENCH INDEX
TRENCH, DETAIL W/ COMMUNICATIONS
SLSB
WWSB STEEL WHITEWAY POLE FOUNDATION
BAB-1
BAB-2
BREAKAWAY BASE, SMALL
BREAKAWAY BASE, LARGE
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
City Utilities of Springfield, Missouri
LIGHT BASES INDEX
RESIDENTIAL STREET LIGHT STEEL FOUNDATION
LT-10B
LT-10*
LT-10F DECORATIVE PEDESTRIAN LIGHT DOUBLE FIXTURE 14', 100W HPS
City Utilities of Springfield, Missouri
PEDESTRIAN LIGHTS INDEX
DECORATIVE PEDESTRIAN LIGHT 10', 100W HPS
DECORATIVE PEDESTRIAN LIGHT SINGLE FIXTURE 14', 100W HPS
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
LT-10A
LT-17A
SECURITY LIGHT 100W HPS
SECURITY LIGHT 175W MV
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
City Utilities of Springfield, Missouri
SECURITY LIGHTS INDEX
LT-15A
LT-15B RESIDENTIAL LIGHT, WOOD POLE, 150W HPS
LT-15C
LT-15D
LT-15E
LT-15F
LT-25A
LT-40A
LT-40B DECORATIVE STREET LIGHT, 400W HPS
CONCRETE DECORATIVE STREET LIGHT, 150W HPS
CONCRETE DECORATIVE STREET LIGHT, 150W HPS
REIDENTIAL STREET LIGHT, 250W HPS
DECORATIVE STREET LIGHT, 400W HPS
STREET LIGHTS INDEX
RESIDENTIAL STREET LIGHT, 150W HPS, ALUMINUM
RESIDENTIAL STREET LIGHT, 150W HPS, ALUMINUM, STEEL FOUNDATION
DECORATIVE STREET LIGHT, 150W HPS
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
City Utilities of Springfield, Missouri
WW25S* WHITEWAY 250W HPS, STEEL POLE
WW25P-F* WHITEWAY 250W HPS, PAINTED FLUTED STEEL POLE
WW25P-O* WHITEWAY 250W HPS, PAINTED OCTAGONAL STEEL POLE
WW25P-R* WHITEWAY 250W HPS, PAINTED ROUND STEEL POLE
WW40S* WHITEWAY 400W HPS, STEEL POLE
WW25W* WHITEWAY 250W HPS, WOOD POLE
WW40W* WHITEWAY 400W HPS, WOOD POLE
WWSRS-*
LT-40I INTERSTATE LIGHT, 400W HPS
WWC-S WHITEWAY CONTROLLER, SECONDARY SWITCHED
WWC-U WHITEWAY CONTROLLER, UNDERGROUND
WWC-P WHITEWAY CONTROLLER, PRIMARY SWITCHED
WHITEWAY 400W HPS, SNOWFLAKE READY
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
City Utilities of Springfield, Missouri
WHITEWAY LIGHTING INDEX
GN-SYMB
GN-PHASE
GN-XFORM
GN-CO
GN-FUSE
GN-WIRE
GN-OID
GN-UID
GN-GRD
GN-GATE
GN-DESIGN
MT-TRAN
GN-FRAME WOOD POLE FRAMING/BRANDING DETAILS
DISTRIBUTION DESIGN STANDARDS
OVERHEAD EQUIPMENT IDENTIFICATION
TRANSFORMER BANK CONNECTIONS
STANDARD SYMBOLS
STANDARD PHASE DESIGNATIONS
UNDERGROUND EQUIPMENT IDENTIFICATION
PADMOUNT EQUIPMENT GROUNDING
TRANSMISSION ACCESS GATE
MANUFACTURES TRANSFORMER TAGGING REQ.
GENERAL SPECIFICATIONS INDEX
ELECTRIC DISTRIBUTION CONSTRUCTION STANDARDS
City Utilities of Springfield, Missouri
STANDARD CUTOUT LOCATIONS
FUSING GUIDELINES
WIRE SPECIFICATIONS & RATINGS