Electrical Load List

ELECTRICAL
Duty
Rating(for each
drive)
Shaft Power Voltage Speed
KW KW V nom RPM Primary Secondary Status POS Ind. Ammeter
1 Tranformer - Rectifier
Indoor (Chlorination
Plant)
3 1 Continous 380 350 415V, 3, 50Hz. NA None DOL / ACB No
Control
Panel
None ON / TRIP NA No MCC
2 Dosing Pump - CW
Outdoor (Chlorination
Plant)
2 1 Shock 3.7 2.4 415V, 3, 50Hz. 2900 None DOL No
Control
Panel
None ON / TRIP NA No MCC
3 Dosing Pump - PT Plant
Outdoor (Chlorination
Plant)
1 1 Continous 0.74 0.38 415V, 3, 50Hz. 2900 None DOL No
Control
Panel
None ON / TRIP NA No MCC
4 Dosing Pump - Potable water- Plant
Outdoor (Chlorination
Plant)
1 1 Continous 0.37 0.015 415V, 3, 50Hz. 2900 None DOL No
Control
Panel
None ON / TRIP NA No MCC
5 Dosing Pump - Potable water- Colony
Outdoor (Chlorination
Plant)
1 1 Continous 0.37 0.015 230V, 1, 50Hz. 1440 None DOL No
Control
Panel
None ON / TRIP NA No MCC
6 Blower
Outdoor (Chlorination
Plant)
1 1 Continous 5.5 4.2 415V, 3, 50Hz. 2900 None DOL No
Control
Panel
None ON / TRIP NA No MCC
7 Self cleaning strainers
Outdoor (Chlorination
Plant)
1 1 Continous 3.7 ------- 415V, 3, 50Hz. 1500 None DOL No
Control
Panel
None ON / TRIP NA No MCC
8 Feed Water Pump Outdoor (S) 1 1 Continous 11 9.11 415V, 3, 50Hz. 2900 None DOL No
Control
Panel
None ON / TRIP NA No MCC
9 Chiller Water Pump
Indoor - For chilled
water circulation
4 1 Continous 3.7 2.6 415V, 3, 50Hz. 2900 None DOL No
Control
Panel
None NA NA No MCC
10 Brine Pump
Outdoor (Chlorination
Plant)
1 1 Continous 5.5 2.78 415V, 3, 50Hz. 2900 None DOL No
Control
Panel
None ON / TRIP NA No MCC
11 Acid recirc. Pump
Outdoor (Chlorination
Plant)
1 1 Continous 2.2 1.34 415V, 3, 50Hz. 2900 None DOL No
Control
Panel
None NA NA No MCC
12 Chiller Compressor
Indoor (Chlorination
Plant)
4 1 Continous 18 16 415V, 3, 50Hz. NA None DOL No
Control
Panel
None ON / TRIP NA No MCC
13 Circulating water pump
Outdoor (Chlorination
Plant)
1 1 Continous 11 9.65 415V, 3, 50Hz. 1500 None DOL No
Control
Panel
None ON / TRIP NA No MCC
14 Sump-Pump
Outdoor (Chlorination
Plant)
1 1
Intermittent
(3 to 4 hrs)
0.37 0.2 415V, 3, 50Hz. 1500 None DOL No
Control
Panel
None ON / TRIP NA No MCC
15 Local control Panel
Indoor (Chlorination
Plant)
1 1 Continous 5 ------ 240V, 1, 50Hz. NA None MCB No NA None NA NA No UPS power supply
16 Cooling Tower Fan
Outdoor (Chlorination
Plant)
1 0 Continous 5.5 ------ 415V, 3, 50Hz. 750 None DOL No
Control
Panel
None NA NA No MCC
No. of feeders 25 15
No. of feeders
S.P.Pal SJ JK
PREPARED CHECKED APPVD
Tel Fax 0 21.10.2013 Rev.
+91 22 40910000 +91 22 40910010 Rev. No. Date 4
Contact
Work ELECTRO-CHLORINATION SYSTEM
Grand Total 40
RAJASTHAN RAJYA VIDYUT UTPADAN NIGAMLTD. Client
Project
Contractor LARSEN & TOUBRO LIMITED
System
SystemSupplier
CAPITAL CONTROLS INDIA
PVT. LTD.
Remarks
REMARKS
TITLE
Electrical Load List
Doc. No.
Total
Consultant L&T S&L LIMITED 15 A/J, Laxmi Estate, Andheri,
Mumbai - 400 053
Preliminary Submission
www.capitalcontro
lsindia.com
Auto
Selection
Mode of
Control
MECHANICAL
Client's
Ref. Dwg.
2 660 MWCHHABRA SUPERCRITICAL TPS,
4 x 60 Kg/h Electro chlorination System
S. No.
Power Source Working Standby
Location Description
Quantity
Control Location Indication on field panel
OPERATION / MCC INTERLOCKING
Sheet 1 of 1 7/17/2014