Globul Project TP and External Alarm
connection and test guide

Page 2 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
TP and external alarm solution & cable connection
Ethernet cable connection from TP SMU02B to BBU
Outdoor TP cabinet sensor installation
Existing DDF sensor side alarm cable connection change
TP and external alarm test procedure
Content
Page 3 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
Indoor
TP Indoor
Reuse Existing PSS
TP outdoor
TP and external alarm solution & cable
connection typical scenarios
Page 4 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
Scenario1 TP Indoor
BTS BBU
Alarm System
Door
Temperature
&humidity
Smoke
Air-condition
Low fuel
DG.
Running
UIM02C
TP48200B
Existing
Krone
DDF Box
New connection from BBU
to TP SMU board 1 new
cable
New connection from BBU
to Existing Krone 4 new
cables
New connection from TP
UIM02C to Existing Krone 2
new cables
TP SMU
AC Power
Control
Page 5 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
Scenario 1 TP Indoor
Installation:
7 psc. of Ethernet cables should be installed for alarms connection

The black cables 2 pcs. prepared for UIM02C connection should be installed for alarm
connection between TP UIM02C and existing Krone box
The grey cables 4 psc. should be installed for alarm connection between BBU and existing
Krone box
One cable should connect IOOI on SMU02B and MON0 on BBU upper UPEU card

Alarms connection and definitions:

For Indoor sites External Alarms should be connected and defined 1:1 as per Globul
request. On the 15-20% of the sites the alarms are configured differently. This
configuration should be kept as it is.
File with existing alarm configuration is provided (Alarm_settings_SofiaBSCs_Moto.xlsx).
Also double definitions should be removed from some alarms. Details how the existing
alarm definition will be transformed are provided in the file AlarmMap_v0.9.xlsx


Page 6 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
Scenario 1 TP Indoor
Pay Attention:

1. On the most common case the TP cabinet will provide only 3 alarms
AC Main (Alarm 7) which combine AC SPD alarm, DC SPD alarm and
Fuse break alarm and should be set on the ALM relay 4 on UIM02C
Low DC Voltage alarm (Alarm 4) which should be set on 46.3V on the
ALM relay 6 on UIM02C
Rectifier failure alarm (Alarm 13) and should be set on ALM relay 8 on
UIM02C
2. The rest of Power alarms will be provided by existing Alarm system and
control units as per customer request
3. Mains failure (Alarm7) and One phase down (Alarm5) will be configured on
TP but not connected to the Krone in the common case. Only if the existing
Alarm system failed to report these alarms by some reason they will be
provided by TP.

Page 7 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
Scenario 1 TP Indoor
TP Alarm connection
TP
Alarm
no. TP Alarm reported
TP Alm
Cable no.
TP Alm
Cable pair
no.
TP Alm
Cable pair
collor
Position
on sensor
side -
Krone
Motorola
1
Spare 1 1 orrange
2
Spare 1 2 green
3
Spare 1 3 blue
4
AC main 1 4 brown 7
5
One phase down 2 1 orrange
6
Low DC voltage 2 2 green 4
7
Mains failure 2 3 blue
8
Rectifier failure 2 4 brown 13
External Alarms Transformation BBU to Krone connection
Alm No.
Alarm definition Globul
(old)
Alarm appearance M2000
Alarm ID
M2000
UPEU
module
on BBU
UPEU
alm
port
conn.
cable
pair no.
conn.
cable pair
collor
Position
on BTS
side -
Krone
Motorola
1 High/Low Temperature
For Reference - existing ext. alarms info
for the particular site from Motorola
alarm configuration file
Alarm_settings_SofiaBSCs_Moto.xlsx and
alarm maping rules from AlarmMap
V0.9.xlsx

upper ALM0 1 orrange 1
2 Fire/Smoke upper ALM0 2 green 2
3 Door Open upper ALM0 3 blue 3
4 Low DC Voltage upper ALM0 4 brown 4
5 R-Ph down/One Ph Down upper ALM1 1 orrange 5
6 Flood upper ALM1 2 green 6
7 AC Main upper ALM1 3 blue 7
8 Aviation Light Failure upper ALM1 4 brown 8
9 Tamper lower ALM0 1 orrange 9
10 Air Conditioner Failure lower ALM0 2 green 10
11 S-Ph/GNR Run lower ALM0 3 blue 11
12 T-Ph/GNR Fail lower ALM0 4 brown 12
13 Rectifier Down/Low Oil lower ALM1 1 orrange 13
14 Alarm System Low Battery lower ALM1 2 green 14
15 Alarm Sys Main AC down lower ALM1 3 blue 15
16
Personnel on Site
lower ALM1 4 brown 16
AlarmMap_v0.9.xlsx
Alarm_settings_SofiaBSCs_Moto.xlsx
Page 8 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
Scenario1 Reuse existing PSS
BTS BBU
Alarm System
Door
Temperature
&humidity
Smoke
Air-condition
Low fuel
DG.
Running
Existing Guardian PSS
Existing
Krone
DDF Box
New connection from BBU
to Existing Krone 4 new
cables
AC Power
Control
Page 9 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
Scenario 1 Reuse Existing PSS
Installation:
4 psc. of Ethernet cables should be installed for alarms connection

The grey cables 4 psc. should be installed for alarm connection between BBU and existing
Krone box

Alarms connection and definitions:

For Indoor sites External Alarms should be connected and defined 1:1 as per Globul
request. On the 15-20% of the sites the alarms are configured differently. This
configuration should be kept as it is.
File with existing alarm configuration is provided (Alarm_settings_SofiaBSCs_Moto.xlsx).
Also double definitions should be removed from some alarms. Details how the existing
alarm definition will be transformed are provided in the file AlarmMap_v0.9.xlsx


Page 10 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
Scenario 1 Reuse existing PSS
External Alarms Transformation BBU to Krone connection
Alm No.
Alarm definition Globul
(old)
Alarm appearance M2000
Alarm ID
M2000
UPEU
module
on BBU
UPEU
alm
port
conn.
cable
pair no.
conn.
cable pair
collor
Position
on BTS
side -
Krone
Motorola
1 High/Low Temperature
For Reference - existing ext. alarms info for
the particular site from Motorola alarm
configuration file
Alarm_settings_SofiaBSCs_Moto.xlsx and
alarm maping rules from AlarmMap
V0.9.xlsx

upper ALM0 1 orrange 1
2 Fire/Smoke upper ALM0 2 green 2
3 Door Open upper ALM0 3 blue 3
4 Low DC Voltage upper ALM0 4 brown 4
5
R-Ph down/One Ph Down
upper ALM1 1 orrange 5
6 Flood upper ALM1 2 green 6
7 AC Main upper ALM1 3 blue 7
8 Aviation Light Failure upper ALM1 4 brown 8
9 Tamper lower ALM0 1 orrange 9
10 Air Conditioner Failure lower ALM0 2 green 10
11 S-Ph/GNR Run lower ALM0 3 blue 11
12 T-Ph/GNR Fail lower ALM0 4 brown 12
13 Rectifier Down/Low Oil lower ALM1 1 orrange 13
14 Alarm System Low Battery lower ALM1 2 green 14
15 Alarm Sys Main AC down lower ALM1 3 blue 15
16
Personnel on Site
lower ALM1 4 brown 16
AlarmMap_v0.9.xlsx
Alarm_settings_SofiaBSCs_Moto.xlsx
Page 11 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
Scenario1 TP Outdoor
BTS BBU
UIM02C
TP48200A
New connection from BBU
to TP SMU board 1 new
cable
New connection from BBU
to TP 2 new cables
TP SMU
Aviation
light
Box
TP SMU
Page 12 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
Scenario 1 TP Outdoor
Installation:
4 psc. of Ethernet cables should be installed for alarms connection

The black cables 2 pcs. prepared for UIM02C connection should be installed for alarm
connection between TP UIM02C and BBU
Optional in case of Alarm aviation box on site will be installed one more cable for
providing Aviation light alarm from aviation light box to BBU
One cable should connect IOOI on SMU02B and MON0 on BBU upper UPEU card

Alarms connection and definitions:

For Outdoor sites External Alarms should be connected as per table on next slide.
8 alarms will be reported by TP
Alarm 9 will reported by Aviation light abox in case is existing on the site
In case of Diesel Generator on site more alarm ports and cables can be used



Page 13 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
Scenario 2 TP Outdoor
External Alarms Transformation TP Outdoor
Alm No. Alarm definition Globul Alarm appearance M2000
Alarm ID
M2000
UPEU
module
on BBU
UPEU
alm
port
conn.
cable
pair no.
conn.
cable pair
collor
TP alarm
connection on
UIM02C
module
1
High/Low Temperature High or low temperature 65033 upper ALM0 1 orrange
ALM1
2
Fire/Smoke Fire or smoke 65034 upper ALM0 2 green
ALM2
3
Door open Door open 65042 upper ALM0 3 blue
ALM3
4
Fan Failure Fan failure 65048 upper ALM0 4 brown
ALM4
5
One phase down One phase down 65058 upper ALM1 1 orrange
ALM5
6
Low DC voltage Low DC voltage 65043 upper ALM1 2 green
ALM6
7
Mains failure Mains failure 65039 upper ALM1 3 blue
ALM7
8
Rectifier failure Rectifier failure 65040 upper ALM1 4 brown
ALM8
9
Aviation Light Failure Aviation Light Failure
65046 lower ALM0 1 orrange
-
Page 14 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
Appendix 1 Communication cable for BBU side
Page 15 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
Appendix 2
Communication cable for TP SMU and existing DDF side
8-Pin Cable 1 8-Pin Cable 2
ALM1+ ALM1- ALM2+ ALM2- ALM3+ ALM3- ALM4+ ALM4- ALM5+ ALM5- ALM6+ ALM6- ALM7+ ALM7- ALM8+ ALM8-
Orange&
White
Orange
Green
&White
Green
Blue&
White
Blue
Brown&
White
Brown
Orange
& White
Orange
Green
&White
Green
Blue&
White
Blue
Brown&
White
Brown
TP UIM
Page 16 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
Appendix 3 Globul project alarm setting guide attached
Page 17 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
TP and external alarm solution & cable connection
Ethernet cable connection from TP SMU02B to BBU
Outdoor TP cabinet sensor installation
Existing DDF sensor side alarm cable connection change
TP and external alarm test procedure
Content
Page 18 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
Ethernet Cable from SMU02B to BBU for all sites
TP48200A/200B
SMU02B
Ethernet cable
UPEU
Step detail:
Connect IOOI on SMU02B and MON0 on BBU UPEU card
with provided Ethernet cable. (If MON0 has been used, you can
use MON1 instead.
Page 19 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
TP and external alarm solution & cable connection
Ethernet cable connection from TP SMU02B to BBU
Outdoor TP cabinet sensor installation
Existing DDF sensor side alarm cable connection change
TP and external alarm test procedure
Content
Page 20 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
Outdoor TP Smoke sensor installation

Install the smoke sensor on the top of the cabinet
Page 21 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
Outdoor TP temperature and humidity sensor installation

Install the temperature sensor on the left rack in the cabinet
Page 22 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
TP and external alarm solution & cable connection
Ethernet cable connection from TP SMU02B to BBU
Outdoor TP cabinet sensor installation
Existing DDF Sensor side alarm cable connection change
TP and external alarm test procedure
Content
Page 23 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
Scenario 2 Motorola BTS with SMT EAS


Ext ALM
CODE TEXT STRING
New ALM
Need
Sensor side connection change for
New TP
Sensor side connection change for
Reusing Existing Power
ALM1 HIGH / LOW TEMPERATURE ALM1 No need No need
ALM2 FIRE/SMOKE ALM2 No need No need
ALM3 INTRUDER ALM3 Series Connect to Ext ALM3 Port Series Connect to Ext ALM3 Port
ALM4 LOW DC VOLTAGE None Remove ALM cable Remove ALM cable
ALM5 R PHASE BREAKDOWN ALM5 No need No need
ALM6 FLOOD None No need Remove ALM cable
ALM7 AC MAINS FAILURE ALM7 No need Series Connect to Ext ALM7 Port
ALM8 AVIATION LIGHT FAILURE None No need Remove ALM cable
ALM9 TAMPER ALM3 Series Connect to Ext ALM3 Port Series Connect to Ext ALM3 Port
ALM10 AIR CONDITIONER FAILURE ALM4 Connect to Ext ALM4 Port Connect to Ext ALM4 Port
ALM11 S PHASE BREAKDOWN ALM6 No need Connect to Ext ALM6 Port
ALM12 T PHASE BREAKDOWN ALM7 No need Series Connect to Ext ALM7 Port
ALM13 RECTIFIER FAILURE ALM8 No need Connect to Ext ALM8 Port
ALM14 ALARM SYSTEM LOW BATTERY None No need No need
ALM15 ALARM SYSTEM MAINS AC DOWN None No need No need
ALM16
PERSONNEL ON SITE /Alarm system
status/ None No need No need
Page 24 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
Scenario 3 BTS with A.C.S EAS



Ext ALM
CODE
TEXT STRING
New ALM
Need
Sensor side connection change for
New TP
Sensor side connection change for
Reusing Existing Power
ALM1 HIGH / LOW TEMPERATURE ALM1 No need No need
ALM2 FIRE/SMOKE ALM2 No need No need
ALM3 DOOR OPEN ALM3 Series Connect to Ext ALM3 Port Series Connect to Ext ALM3 Ple
ALM4 LOW DC VOLTAGE (psu1, psu2) None Remove ALM cable Remove ALM cable
ALM5 R or S or T PHASE DOWN ALM5 Series Connect to Ext ALM5 Port Series Connect to Ext ALM5 Port
ALM6 FLOOD None No need Remove ALM cable
ALM7 AC MAINS FAILURE (R and S and T down) ALM7 No need No need
ALM8 AVIATION LIGHT FAILURE None No need Remove ALM cable
ALM9 TAMPER ALM3 Series Connect to Ext ALM3 Port Series Connect to Ext ALM3 Port
ALM10 AIR CONDITIONER FAILURE ALM4 Connect to Ext ALM4 Port Connect to Ext ALM4 Port
ALM11 BACKUP GENERATOR RUNNING ALM6 No need Connect to Ext ALM6 Port
ALM12 SPARE (FREE COOLING ALARM) None No need No need
ALM13 RECTIFIER FAILURE (PSU1, PSU2,) ALM8 No need Connect to Ext ALM8 Port
ALM14 LOW FUEL LEVEL ALM5 Series Connect to Ext ALM5 Port Series Connect to Ext ALM5 Port
ALM15 FUEL TANK ALARM (where applicable) ALM3 Series Connect to Ext ALM3 Port Series Connect to Ext ALM3 Port
ALM16 PERSONNEL ON SITE None No need No need
Page 25 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
Existing DDF type on sites



Existing DDF on 2123 site Existing DDF on 2007 site
For indoor sites with new TP, make ALM1~ALM4 ports of
existing DDF 16 ports to report the 4 existing alarms from DDF to
Huawei BTS, ALM5~ALM8 from new TP to Huawei BTS.
For indoor sites reusing existing power, make ALM1~ALM8 ports of existing DDF 16 ports to report the 8 existing alarms
from DDF to Huawei BTS.

Page 26 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
Existing DDF connection reusing existing Guardian Power



Existing DDF sensor side cable connection when reusing existing Guardian power
without generator.
Short circuit connection for
Alarm 6 port.

Because Guardian power
dont support S phase or T
phase down alarm.
Page 27 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
TP and external alarm solution & cable connection
Ethernet cable connection from TP SMU02B to BBU
Outdoor TP cabinet sensor installation
Existing DDF Sensor side alarm cable connection change
TP and external alarm test procedure
Content
Page 28 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
Mains failure alarm test procedure



1. Power on the system normally with battery back up;

2. Switch off the AC input breaker and wait several minutes, view the active alarm information on the LCD,
and view the alarm information on M2000 to check if the alarm is reported;

3. Switch on the AC input breaker, view the active alarm information on LCD, and view the alarm information
on M2000 to check if the alarm disappeared.

Indoor TP (TP48200B) Outdoor TP (TP48200A)
Page 29 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
Rectifier failure alarm test procedure



1. Insert a plastic stick to stop the rectifier fan and wait several minutes to check the rectifier fault. View the
active alarm information on the LCD, and view the alarm information on M2000 to check if the alarm is reported.

2. Remove the stick. View the active alarm information on LCD, and view the alarm information on M2000 to
check if the alarm disappeared.

Page 30 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
Smoke alarm test procedure



Below is described the usual way to check this alarm but in this project it will be not checked

1. Spray the smoker sensor to check if the alarm is reported with OMC if they view the alarm information
on M2000.
2. Wait several minutes after the alarm is active and check with OMC if the alarm is disappeared on M2000.
Page 31 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
Temperature and Door open alarm test procedure



High temperature alarm test

1. Carefully heat the temperature sensor with heat-air-gun to reach the threshold value. Keep the airflow away
from plastic details and cabinet insulation. View the active alarm information on the LCD, and view the alarm
information on M2000 to check if the alarm is reported.

2. Cool the temperature sensor or wait the temperature to be normal, view the alarm information on M2000 to
check if the alarm is disappeared.

Door open alarm test

1. Open the door of Cabinet or shelter to check the active alarm information on M2000 with OMC.

2. Close the door of Cabinet or shelter to check if the alarm is disappeared on M2000 with OMC.

Page 32 HUAWEI TECHNOLOGIES CO., LTD.
1.7cm
2.2cm
2.2cm
1.8cm
2.2cm
2.2cm
1.7cm
Coler Sample
The following nine groups of
colors are an example of how
our design colors can be used,
please take note that you
should only use one design
color group per slide.
For specific usage details,
refer to the Typesetting
Standard.
1.8cm
Cover
The main title: 50-60pt
Subtitle: 25-30pt
Line spacing: Same size like the title font
Color : R153 G0 B0
Font Internal: FrutigerNext LT Medium
Font External: Arial

Contents
The main title: 32pt
The main contents: 28pt
Sub contents: 20pt
Line spacing: 1.5 line
Color : R153 G0 B0
Other Color: R127 G127 B127
Font Internal: FrutigerNext LT Medium
Font External: Arial

Text
The main title: 32pt
Subtitle: 16-20pt
Text: 10-16pt
Line spacing: As need
Color: Black
Font Internal: FrutigerNext LT Regular
Font External: Arial
Air conditioner failure and D.G running alarm test procedure



Air conditioner failure alarm test

1. Shut down the precision air conditioner ( Floor mounted) or heat the temperature sensor of wall mounted air
Conditioner to check if there is a right alarm information on M2000 with OMC.

2. Start the precision air conditioner again and check with OMC if the alarm is disappeared on M2000.

D.G (Generator) running alarm test

1. Start the generator to check with OMC if the alarm is reported on M2000.

2. Shut down the generator to check with OMC if the alarm is disappeared on M2000.

Thank you