Você está na página 1de 20

Electronic Trip Circuit Breaker

Basics

Circuit Breaker Application Guide

GROUPE SCHNEIDER
When it comes to circuit breakers, no one

knows more than Square D. This Circuit

Breaker Application Guide is one of a

series designed to provide answers to

the most commonly asked questions

about selecting and applying circuit

breakers.

Along with a large network of Square D

field offices and authorized distributors,

this series of application guides helps

provide technical support unsurpassed

in the industry. So, when you need to

know more about circuit breakers, turn to

Square D.
TABLE OF CONTENTS

PART 1 – ELECTRONIC TRIP Trip Characteristics ........................................... 7


CIRCUIT BREAKERS ...................................... 1 Standard-function Trip Unit Functions ............... 8
Long-time Trip Function ................................ 9
What Is a Circuit Breaker? ................................ 1 Short-time Trip Function ................................ 9
Why Use Electronic Trip Circuit Breakers? ....... 1 Instantaneous Trip Function ........................ 10
Enhanced Coordination Capabilities ............. 1 Ground-fault Trip Function .......................... 10
Integral Ground-fault Detection ..................... 2 Full-function Trip Unit Functions ..................... 11
Communications Capabilities ........................ 3 Long-time Trip Function .............................. 11
Future Growth Potential ................................ 4 Short-time Trip Function .............................. 12
Instantaneous Trip Function ........................ 13
PART 2 – MICROLOGIC® TRIP SYSTEMS ......... 5 Ground-fault Trip Function .......................... 13
Ground-fault Alarm Function ....................... 14
General ............................................................. 5
RMS Sensing .................................................... 5 PART 3 – A LOOK AT COORDINATION ........... 15
Rating Plugs ...................................................... 6
Ammeter/Trip Indicator ...................................... 6 Coordination .................................................... 15
Memory Feature ................................................ 7 Coordination Under Ground-fault Conditions .. 15
Ground-fault Detection ...................................... 7 Zone-selective Interlocking ............................. 16

i
PART 1 – ELECTRONIC TRIP CIRCUIT BREAKERS

WHAT IS A CIRCUIT BREAKER? Electronic trip molded case circuit breakers


are designed to meet UL489, Underwriters
A circuit breaker has two primary functions: Laboratories Standard for Safety for Molded-
Case Circuit Breakers and Circuit Breaker
1. to provide a nonautomatic means to Enclosures.
energize and de-energize the circuit
WHY USE ELECTRONIC TRIP CIRCUIT
and BREAKERS?

2. to open automatically to protect the In most cases, the basic overcurrent protection
circuit from damage due to an provided by standard thermal-magnetic circuit
overcurrent condition. breakers will meet the requirements of the
electrical system design. In some cases, how-
In other words, a circuit breaker must be able ever, basic overcurrent protection might not be
to be switched on and off, and it must open enough.
automatically during an overcurrent condition.
Electronic trip circuit breakers can provide the
In order to open automatically, circuit breakers additional features needed in those cases.
are equipped with some type of tripping mecha- Reasons to use electronic trip circuit breakers
nism. Some circuit breakers employ electro- include
mechanical tripping mechanisms, some use
hydromechanical tripping mechanisms, and • enhanced coordination capabilities
some use electronic tripping mechanisms. • integral ground-fault detection
• communication capabilities
Electronic trip circuit breakers from Square D • future growth potential
Company use the MICROLOGIC® tripping
system, which includes current sensors, a Enhanced Coordination Capabilities
microprocessor-based trip unit and a tripping
solenoid. In electrical systems where downtime could
have critical consequences, electronic trip cir-
cuit breakers provide more versatility to achieve
Figure 1 – MICROLOGIC Electronic Trip coordination. For instance, certain installa-
Circuit Breakers
tions serving continuous processes may be
required to continue operating during a fault
condition because shutting the system down
would be more costly than the damage done by
the fault itself. Or, in critical care facilities, a
loss of power could result in the loss of life.

These situations require that coordination be


optimized at all costs. In order to maximize
coordination, downstream branch devices
should operate very fast – with no intentional
delay – and main devices should delay opera-
tion so that the downstream devices have time
to clear the fault.

1
MICROLOGIC electronic trip circuit breakers In order to coordinate better with these
can help optimize coordination: types of downstream devices, MICRO-
LOGIC circuit breakers offer inverse time
• Independent adjustments allow one dial set- delay characteristics on the long-time, short-
ting to be changed without affecting the rest time and ground-fault functions.
of the pickup and delay levels. This allows
the designer to better define the tripping • The ammeter/trip indicator displays the level
characteristics needed on the system. of ground-fault leakage current associated
with the circuit. The ground-fault pickup
• Interchangeable rating plugs allow the de- level on the circuit breaker may then be
signer to shift the entire trip characteristic adjusted somewhat higher than the amount
curve (except for ground fault) to improve of leakage current displayed on the amme-
coordination with other devices. MICRO- ter.
LOGIC rating plugs define the circuit
breaker's maximum current rating based on This assumes that ground-fault detection test-
a percentage of the circuit breaker sensor ing was done before the system was energized
size, and can be used on any frame size of and no ground-fault problems were found. In
circuit breaker within the MICROLOGIC retrofit situations the magnitude of leakage
family of circuit breakers. current may be significant due to the deterio-
rating effects of moisture, dirt, rodents, etc.,
• Withstand ratings give the designer a larger over time. New installations will also show
window of coordination potential. The with- some magnitude of leakage current at start-up.
stand rating is the level of rms symmetrical
current that a circuit breaker can carry with There are no hard and fast rules for selecting
the contacts in the closed position for a the proper level of ground-fault protection be-
certain period of time. At current levels cause the level of leakage current on each
above the withstand rating (and less than or system is different. The system engineer should
equal to the interrupting rating), the circuit provide information on the proper levels of
breaker will trip instantaneously. In other protection.
words, the withstand rating is the highest
current level at which delay can be intro- Integral Ground-fault Detection
duced to maintain coordination with down-
stream devices. Withstand ratings are avail- Electronic trip circuit breakers simplify the in-
able only on full-function trip systems stallation of equipment ground-fault detection
ordered with the adjustable short-time into the electrical system.
function.
Externally-mounted ground-fault detection
• Inverse time delay characteristics allow for systems require the specifying of five different
better coordination with fusible switches or parts – a circuit breaker, a ground-fault relay,
thermal-magnetic circuit breakers down- a ground-fault sensor, a shunt trip for the
stream. Devices that respond to heat gen- circuit breaker, and testing means. Additional
erated by current flow (such as fuses and wiring is also required to install the system.
thermal-magnetic circuit breakers) have
inverse time tripping characteristics. This Electronic trip circuit breakers include most of
means that as current increases, the time the detection equipment within the circuit
that it takes the device to trip will decrease. breaker housing. The phase current sensors,
summing toroid, pickup and delay adjustments,
tripping solenoid, and a push-to-test feature
are all enclosed within the molded case.

2
The only part that is not within the circuit MICROLOGIC full-function circuit breakers are
breaker case is the optional neutral sensor equipped with ZSI communication capabilities
required for a four-wire system. That means as a standard feature. For more information on
that ground-fault detection plus overcurrent ZSI, see Circuit Breaker Application Guide
protection is as easy as specifying and mount- 0600SC9102R6/95, Reducing Fault Stress
ing one device (except four-wire systems which With Zone-selective Interlocking.
require an additional neutral sensor).
Communication between circuit breakers and
MICROLOGIC circuit breakers are available the POWERLOGIC power monitoring system
with two different ground-fault detection op- allows the user to monitor each circuit and
tions: record energy usage, power surges, normal
operating modes, harmonic contribution, etc.
• ground-fault protection for equipment In addition, the MICROLOGIC full-function trip
• ground-fault alarm system can communicate the following infor-
mation through the POWERLOGIC system:
The ground-fault protection for equipment op-
tion is available on circuit breakers with either • history of last trip
the MICROLOGIC standard-function or full- • trip unit pickup and delay levels
function trip system, and will trip the circuit • impending trip conditions
breaker in the event of a ground fault. • operating currents for each phase
• ground-fault leakage current associated with
The ground-fault alarm option is available on the circuit
circuit breakers with the MICROLOGIC full- • ground-fault alarm signal
function trip system only. This function will
signal a remote POWERLOGIC ® station, but The ground-fault alarm signal allows a ground
will not trip due to a ground fault – maintaining fault to be reported without interrupting power
system continuity. to the system. It is especially useful when
continuity of service must be maintained at all
Communications Capabilities costs and where the maintenance staff is trained
to locate and correct any fault problems before
MICROLOGIC circuit breakers can communi- an unplanned outage takes place.
cate with each other and with the
POWERLOGIC power monitoring systems. For more information on POWERLOGIC sys-
tems, see publication 3050SM9101R11/91,
Communication between circuit breakers at POWERLOGIC Product Interface for MICRO-
different levels in the system allows the down- LOGIC Circuit Breakers.
stream circuit breaker closest to the fault to
ignore its preset delay time and trip without any
intentional time delay on a short circuit or
ground fault. This form of communication is
known as zone-selective interlocking (ZSI).

Coordination assures that continuity of service


is maximized during any type of overcurrent.
However, coordination does not eliminate the
stress on the system caused by the energy
dissipated during a fault. ZSI actually reduces
the stress on the system resulting from a fault
while maximizing continuity of service.

3
Future Growth Potential

Many of the adjustable features that enhance


coordination also provide means for increas-
ing the ampere rating of an electronic trip
circuit breaker to meet future growth needs.
The adjustability of a MICROLOGIC circuit
breaker enables a designer to plan for future
growth. A circuit breaker can be chosen based
on projected growth, and by changing the rat-
ing plug and/or changing the long-time pickup,
its ampacity can be reduced down to 20% of its
maximum. When growth occurs, the ampacity
may be increased up to the circuit breaker's
maximum. The versatility of the adjustments
on an electronic trip circuit breaker offers the
designer a multitude of options to meet initial
and future capacity requirements.

Another way to plan for future growth or to save


space and minimize cost is to specify 100%
rated electrical distribution equipment. A cir-
cuit breaker either carries a standard rating or
a 100% rating. The standard rating is subject
to NEC sizing rules which limit the application
to 80% of the circuit breaker rating when con-
tinuous loads are involved.

The National Electrical Code (NEC) recog-


nizes overcurrent devices that are listed for
operation at 100% of their rating for continuous
loading. This means that the equipment has
undergone additional testing to verify that it
can handle the additional heat rise associated
with this level of operation. 100% rated circuit
breakers are permitted to be loaded continu-
ously at their full rating (as long as minimum
enclosure requirements, venting configurations
and wire insulation requirements have been
met).

4
PART 2 – MICROLOGIC® TRIP SYSTEMS

GENERAL Adjustable rotary switches on the trip unit allow


the user to set the proper overcurrent or ground
Square D electronic trip circuit breakers are current protection required in the electrical sys-
equipped with either the MICROLOGIC ® Stan- tem. If current exceeds the set value for longer
dard-function Trip System or the MICROLOGIC than its set time delay, the trip system auto-
Full-function Trip System. Both trip systems matically opens the circuit breaker. All
provide adjustable tripping functions and char- MICROLOGIC protective functions are fully
acteristics using true root-mean-square (rms) fault powered, no external power source is
current sensing. required.

Figure 2 – Trip Units Circuit breakers are shipped with the long-time
pickup switch set at 1.0 and all other trip unit
RATING PLUG
CAT NO. : ARP100
Max. Ampere Rating (P) = Sensor (S) x 100%
.7
.6
.75 .8
.9
.95
3
2.5
4 5
6
7 3
4
5 6
7
8
.3

.25
.35 .45
.55
.65
adjustments set at their lowest settings. Actual
settings required for a specific application must
.5 1.0 2 8 2.5 OFF .2 .75
PICKUP PICKUP PICKUP PICKUP
x P x P x P x S
LONG TIME SHORT TIME INSTANT. GROUND FAULT
I2 t OUT I2 t IN I2 t OUT I2 t IN

4.5
3
2
6 8
10
12
14
.32
.2
.1
.5 .5
.32
.2
.1
.32
.2
.1
.5 .5
.32
.2
.1
be determined by a qualified consultant or plant
engineer. A coordination study is recommended
DELAY DELAY
DELAY
SEC. AT SEC. AT SEC. AT
6xP 12 x P 1xS
FLASH=90%
ON = OVERLOAD

STANDARD
SERIES B
to provide coordination between all overcurrent
protective devices in the distribution system.
Standard-function Trip Unit

4 5
RMS SENSING
.75 .8 5 6 .35 .45
RATING PLUG .7 .9 3 4 7 .3
6 .55
CAT NO. : ARP100
.6 .95 2.5 7 3 8 .25 .65
Max. Ampere Rating (P) = Sensor (S) x 100%
.5 1.0 2 8 2.5 OFF .2 .75

PHASE
SELECT
AMMETER / TRIP INDICATOR
PICKUP
x P
LONG TIME
PICKUP
x P
SHORT TIME
I2 t OUT I2 t IN
PICKUP
x P
INSTANT.
PICKUP
x S

GROUND FAULT
I2 t OUT I2 t IN
The sensing system on an electronic trip circuit
6 8 .5 .5 .5

breaker responds to the flow of current through


P .5
H 4.5 10 .32 .32 .32 .32
INDICATOR A
RESET S 3 12 .2 .2 .2 .2
E
Press and Hold
for Ammeter Reset ----- 2
DELAY
14 .1
DELAY
.1 .1
DELAY
.1

the circuit breaker. Electronic trip circuit break-


SEC. AT SEC. AT SEC. AT
% of Rating 0 20 40 60 80 100
6xP 12 x P 1xS
FLASH=90%
ON = OVERLOAD

ers are limited to ac systems because the


FULL-FUNCTION
SERIES B

Full-function Trip Unit electronic trip system uses current transform-


ers to sense the current.

The MICROLOGIC trip system samples the


MICROLOGIC trip systems use a set of current current waveform 33 times per cycle on a 60 Hz
transformers (called CTs or sensors) to sense system. It then uses this data to calculate the
current, either a standard-function or full-func- true rms current.
tion trip unit to evaluate the current, and a
tripping solenoid to trip the circuit breaker. Figure 4 – Trip System Current Sensing

Figure 3 – Trip System


Current
Load Current (in amperes)

Trip Unit

Trip
Coil
Microprocessor Sample Time
Interval
Communications
Link
Trip Unit
ZSI Link
Switches Time (in seconds)
Current Sensor
(one per pole) Trip
Indicator

5
True rms sensing accurately measures the mag- Each MICROLOGIC circuit breaker is shipped
nitude of a non-sinusoidal waveform. Therefore, with a rating plug factory installed. The label on
the heating effects of harmonically distorted wave- the circuit breaker marked "Configuration as
forms are accurately evaluated. Shipped" gives the circuit breaker configuration
as it left the factory. Field-installable rating plug
Electronic trip circuit breakers with MICROLOGIC kits are also available.
trip systems can be used on 50/60 Hz systems
with alternating current (ac) to direct current (dc), Ground-fault pickup values are based on the
dc to ac, and ac to ac converters. This includes sensor size of the circuit breaker and are not
applications that use silicon-controlled rectifiers affected by changing the rating plug.
(SCRs) and adjustable frequency controls.
AMMETER/TRIP INDICATOR
RATING PLUGS
The ammeter/trip indicator is used to identify
Rating plugs are used to determine the circuit the type of overcurrent if the circuit breaker
breaker ampere rating (P) according to the fol- trips, to monitor operating current, and to iden-
lowing equation: tify potential overcurrent situations.

Ampere (P) = Sensor (S) x Rating Figure 6 – Ammeter/Trip Indicator


Rating Size Plug %

PHASE AMMETER / TRIP INDICATOR


The ampere rating and the long-time pickup SELECT

P
switch are then combined to determine the circuit INDICATOR
RESET
H
A
GROUND FAULT

S
breaker continuous current rating. For example: E
Press and Hold
for Ammeter Reset

% of Rating
-----
0 20 40 60 80 100

Continuous = Sensor (S) x Rating x Long-time


Current Rating Size Plug % Setting

225 = 600 x 0.75 x 0.5


The ammeter/trip indicator displays current in
Rating plugs are available with multiplier values phases A, B and C, and the ground-fault current
ranging from 0.40 to 1.00. If the rating plug is not associated with the circuit. Each value can be
installed, the circuit breaker will operate safely, viewed one at a time using the phase select/
but the trip unit will default to a rating plug indicator reset button. (Phase values are dis-
multiplier of 0.40. played in true rms. Ground-fault current values
are displayed in calculated rms based on mea-
Figure 5 – Rating Plug sured peak current.) A bar graph is provided
Multiplier indicating the level of operating current as a
Value percentage of the continuous current rating
RATING PLUG (P x long-time setting) of the circuit breaker.
CAT NO. : ARP100
Max. Ampere Rating (P) = Sensor (S) x 100%
The ammeter may not display if the load is less
than 20% of the CT rating.

The ammeter/trip indicator window displays


Rating plugs and ammeter/trip indicators are "OVERLOAD," "SHORT CIRCUIT," or "GROUND
subject to damage from static charge. Internal FAULT" when the circuit breaker trips from an
damage can result if these devices are handled overcurrent. The indicator must be manually
by their contacts. If either device is removed from reset by pushing the phase select/indicator reset
the trip unit, it must be held against grounded button.
metal, such as the metal circuit breaker enclo-
sure, for at least two seconds before reinstalling.

6
The phase select/indicator reset button can be tor the flow of ground-fault current and signal an
pressed at any time to test the ammeter/trip alarm condition through the POWERLOGIC ®
indicator battery condition. The window will system. This feature meets NEC Sections 700-
display a battery symbol. If this does not occur, 7(d) and 700-26 for emergency systems. Circuit
contact Square D for a replacement ammeter/ breakers with the ground-fault alarm trip system
trip indicator. DO NOT trip if a ground-fault occurs.

Figure 7 – Reset Button Ground-fault protection (trip) trip units include


Reset Button
both ground-fault pickup and delay adjustments.
PHASE
SELECT
AMMETER / TRIP INDICATOR
Ground-fault alarm (no trip) trip units include
+ -

P
H
OK

only ground-fault pickup adjustments.


INDICATOR
A
RESET S
E
Press and Hold
for Ammeter Reset ----- Circuit breakers with either ground-fault pro-
% of Rating 0 20 40 60 80 100
tection (trip) or alarm (no trip) trip systems are
equipped with an internal ground-fault push-to-
test feature. The ground-fault push-to-test fea-
The ammeter/trip indicator is factory installed ture is built into the circuit breaker and elimi-
on the full-function circuit breaker and is avail- nates the need for any additional test equip-
able as a field-installable option on the stan- ment, such as monitor panels. The push-to-
dard-function circuit breaker. test feature requires 120 Vac control power.

MEMORY FEATURE TRIP CHARACTERISTICS

MICROLOGIC trip systems feature a memory MICROLOGIC trip units provide a full range of
circuit for intermittent overload or ground-fault adjustable tripping characteristics using a pro-
conditions. This enables the circuit breaker to grammable microcomputer that constantly
respond to a series of ON and OFF overload or monitors the line currents.
ground-fault conditions which could cause con-
ductor overheating. Table 1 – Adjustable Tripping Characteristics
for Electronic Trip Circuit Breakers
If the circuit breaker trips due to an overcurrent Standard-function Full-function
condition, wait at least one minute before re- Trip Unit Trip Unit
setting the circuit breaker. This allows the Long-time pickup Long-time pickup
memory to clear itself sufficiently for the circuit Long-time delay Long-time delay
breaker to be turned ON. If checking trip times, Short-time pickup Short-time pickup
Short-time delay Short-time delay
wait fifteen minutes after the circuit breaker (I2t IN only) (I2t IN and I2t OUT)
trips before resetting to allow memory to reset Instantaneous pickup Instantaneous pickup
completely to zero (or use a memory reset Ground-fault pickup Instantaneous OFF
module, Cat. No. MTMB). Ground-fault delay Ground-fault pickup
(I2t OUT only) Ground-fault delay
GROUND-FAULT DETECTION (I2t IN and I2t OUT)
Ground-fault alarm

Both standard-function and full-function circuit


breakers are available with integral ground- The overcurrent or ground-fault current pickup
fault protection for equipment. This feature will and delay levels are set using adjustable rotary
trip the circuit breaker if a ground-fault occurs. switches on the face of the trip unit. If the line
current exceeds the trip settings longer than
Full-function circuit breakers are also available the delay settings, the microcomputer signals
with integral ground-fault alarm (no trip) to moni- the circuit breaker to trip.

7
Trip settings are used to obtain a coordinated STANDARD-FUNCTION TRIP UNIT
system in which a downstream circuit breaker FUNCTIONS
will trip before an upstream circuit breaker.
The trip curve below illustrates how the adjust-
Properly adjusting the MICROLOGIC trip set- ments made to a standard-function trip unit will
tings will result in a circuit breaker trip curve affect the circuit breaker's trip characteristics.
that falls above and to the right of the down-
stream circuit breaker trip curve. Under Adjusting the trip unit switches will shift that
overcurrent conditions, the downstream circuit area of the trip curve.
breaker will trip first. Figure 8 – Standard-function Trip Unit Curve

Square D recommends that a system coordina-


tion study be done to find the proper trip unit
Long-time
settings to optimize coordination with other 1000 Pickup
devices.
Long-time
Delay
100

10 Short-time
TIME IN SECONDS

Pickup

Short-time
Delay (I 2 t IN)
1.0

Instantaneous

0.1

0.01

1 5 10 100
MULTIPLES OF AMPERE RATING*

*Ampere Rating (P) = Sensor Size (S) x Rating Plug (%).

8
Long-time Trip Function INDICATOR — the trip unit includes an indica-
tor that will flash when the current reaches 90%
LONG-TIME PICKUP Switch — switch value of the LONG-TIME PICKUP setting and will be
(multiplied by the ampere rating) sets the maxi- lit continuously when the current is above 100%
mum current level which the circuit breaker will of the pickup setting.
carry continuously. If the current exceeds this
value for longer than the set delay time, the Short-time Trip Function
circuit breaker will trip.
SHORT-TIME PICKUP Switch — switch value
Figure 9 – Long-time Pickup (multiplied by the ampere rating) sets the short-
circuit current level at which the circuit breaker
will trip after the set SHORT-TIME DELAY.
.75 .8
.7 .9
.6 .95
Figure 11 – Short-time Pickup
.5 1.0
PICKUP
x P
LONG TIME
4 5
7 11 3 6
4.5 16
2.5 8
3 20
2 10
2 24 PICKUP
DELAY x P
SEC. AT
6xP
SHORT TIME
FLASH=90% I 2 t IN
ON = OVERLOAD
.5
.32
.2
.5 .1
LONG-TIME DELAY Switch — sets length of DELAY
SEC. AT
time that the circuit breaker will carry a sus- 12 x P

tained overload before tripping. Delay bands


are labeled in seconds of overcurrent at six
times the ampere rating. For maximum coordi- SHORT-TIME DELAY Switch — sets length of
nation, eight delay bands are available. time the circuit breaker will carry a short circuit
within the short-time pickup range. Delay bands
Figure 10 – Long-time Delay are labeled in seconds of short-circuit current at
12 times the ampere rating, P. The short-time
.75 .8 delay can be set to one of four I2t ramp operation
.9
.7
.6 .95
positions (I2t IN).
.5 1.0
PICKUP
x P Figure 12 – Short-time Delay
LONG TIME

7 11
4.5 16 4 5
20 3 6
3
2.5 8
2 24
DELAY 2 10
SEC. AT PICKUP
6xP x P
FLASH=90%
ON = OVERLOAD SHORT TIME
I 2 t IN
.5
.32
.2
Indicator
.5 .1
DELAY
SEC. AT
12 x P

Long-time delay is an inverse time characteris-


tic in that the tripping time decreases as the
current increases.
I2t IN delay is an inverse time characteristic in that
the delay time decreases as the current increases.

9
Instantaneous Trip Function Ground-fault pickup values are based on the
circuit breaker sensor size only, not the rating
INSTANTANEOUS PICKUP Switch — switch plug multiplier. Changing the rating plug mul-
value (multiplied by the ampere rating) sets the tiplier has no effect on ground-fault pickup
short-circuit current level at which the circuit values.
breaker will trip with no intentional time delay.
GROUND-FAULT DELAY Switch — sets the
The instantaneous function will override the length of time the circuit breaker will carry
short-time function if the INSTANTANEOUS ground-fault current which exceeds the
PICKUP is adjusted at the same or lower set- GROUND-FAULT PICKUP level before trip-
ting than the SHORT-TIME PICKUP. ping. Delay bands are labeled in seconds of
ground-fault current at 1 times the sensor size,
Figure 13 – Instantaneous Pickup S. Ground-fault delay can be adjusted to one
of four fixed time delay positions (I 2t OUT).

6 8 Figure 15 – Ground-fault Delay


5 10
4 12

3 12
PICKUP .35 .45
x P .3 .55
INSTANT. .25 .65

.2 .75
PICKUP
x S

GROUND FAULT
I 2 t OUT
.5
.32
.2
.1 .5
DELAY
SEC. AT
1xS

Ground-fault Trip Function

GROUND-FAULT PICKUP Switch — switch


value (multiplied by the sensor size) sets the I 2t OUT delay is a fixed time characteristic in
current level at which the circuit breaker will that the delay time does not change as the
trip after the set GROUND-FAULT DELAY. current increases.

Figure 14 – Ground-fault Pickup

.35 .45
.3 .55
.25 .65

.2 .75
PICKUP
x S

GROUND FAULT
I 2 t OUT
.5
.32
.2
.1 .5
DELAY
SEC. AT
1xS

10
FULL-FUNCTION TRIP UNIT FUNCTIONS Long-time Trip Function

The full-function trip unit trip curve drawing, LONG-TIME PICKUP Switch — switch value
below, shows the various parts of a typical trip (multiplied by the ampere rating) sets the maxi-
curve affected by the adjustments on a full- mum current level which the circuit breaker will
function trip unit. carry continuously. If the current exceeds this
value for longer than the set delay time, the
Adjusting the trip unit switches will shift that circuit breaker will trip.
area of the trip curve.
Figure 17 – Long-time Pickup
Figure 16 – Full-function Trip Unit Curve

.75 .8
.7 .9
Long-time .6 .95
1000 Pickup .5 1.0
PICKUP
x P
LONG TIME
Long-time
Delay 7 11
4.5 16
100
3 20

2 24
DELAY
SEC. AT
6xP
FLASH=90%
ON = OVERLOAD
10 Short-time
Pickup

Short-time LONG-TIME DELAY Switch — sets length of


Delay (I 2 t IN) time that the circuit breaker will carry a sustained
1.0
overload before tripping. Delay bands are la-
beled in seconds of overcurrent at six times the
Short-time
Delay (I 2 t OUT) Instantaneous ampere rating. For maximum coordination, there
0.1 are eight delay bands.

Figure 18 – Long-time Delay


0.01
.75 .8
.7 .9
1 5 10 100
.6 .95
MULTIPLES OF AMPERE RATING* .5 1.0
PICKUP
x P
*Ampere Rating (P) = Sensor Size (S) x Rating Plug (%).
LONG TIME

7 11
4.5 16
3 20

2 24
DELAY
SEC. AT
6xP
FLASH=90%
ON = OVERLOAD

Indicator

Long-time delay is an inverse time characteristic


in that the delay time decreases as the current
increases.

11
INDICATOR — the trip unit includes an indicator SHORT-TIME DELAY Switch — sets length of
that will flash when the current reaches 90% of time the circuit breaker will carry a short
the LONG-TIME PICKUP setting and will be lit circuit within the short-time pickup range.
continuously when the current is above 100% of Delay bands are labeled in seconds of short-
the pickup setting. circuit current at 12 times the ampere rating, P.
The delay can be adjusted to four positions
Short-time Trip Function of I 2t ramp operation (I 2t IN) or four positions
of fixed time delays (I 2t OUT).
SHORT-TIME PICKUP Switch — switch value
(multiplied by the ampere rating) sets the short- Figure 20 – Short-time Delay
circuit current level at which the circuit breaker
will trip after the set SHORT-TIME DELAY.

Figure 19 – Short-time Pickup

4 5
3 6
I 2t IN
4 5 2.5 8
3 6 2 10
PICKUP
2.5 8
x P
2 10 SHORT TIME
PICKUP
x P I2 t OUT I2 t IN
SHORT TIME .5 .5
.32 .32
I2 t OUT I2 t IN
.5 .2 .2
.5
.32 .32 .1 .1
.2 .2 DELAY
SEC. AT
.1 .1 12 x P
DELAY
SEC. AT
12 x P

I 2t OUT

I 2t IN delay is an inverse time characteristic in


that the delay time decreases as the current
increases.

I 2t OUT delay is a fixed time characteristic in


that the delay time does not change as the
current increases.

12
Instantaneous Trip Function Ground-fault Trip Function

INSTANTANEOUS PICKUP Switch — switch GROUND-FAULT PICKUP Switch — switch


value (multiplied by the ampere rating) sets the value (multiplied by the sensor size) sets the
short-circuit current level at which the circuit current level at which the circuit breaker will
breaker will trip with no intentional time delay. trip after the set GROUND-FAULT DELAY.

Figure 21 – Instantaneous Pickup Ground-fault pickup values are based on circuit


breaker sensor size only, not on the rating plug
multiplier. Changing the rating plug multiplier
6 8 has no effect on ground-fault pickup values.
5 10
4 12
3
Figure 23 – Ground-fault Pickup
OFF
PICKUP
x P
INSTANT.

.35 .45
.3 .55
.25 .65

.2 .75
PICKUP
x S

GROUND FAULT
I 2 t OUT I 2 t IN
.5 .5
.32 .32
.2 .2

The instantaneous function will override the .1


DELAY
.1

SEC. AT
short-time function if the INSTANTANEOUS 1xS

PICKUP is adjusted at the same or lower set-


ting than the SHORT-TIME PICKUP.

In full-function trip units with both adjustable


short-time and instantaneous trip functions, Figure 24 – Ground-fault Pickup
the adjustable instantaneous trip can be dis- (> 1600A Sensor)
abled by setting INSTANTANEOUS PICKUP to
OFF. Even when the instantaneous pickup is
turned OFF, an instantaneous override occurs 880 960
800 1040
above the circuit breaker short-time withstand
720 1120
rating. 640
PICKUP
1200

GROUND FAULT
Figure 22 – Instantaneous OFF gure 23 – Ground-fault Pick
I 2 t OUT I 2 t IN
.5 .5
.32 .32
.2 .2
.1 .1
6 8 DELAY
5 10 SEC. AT
1xS
4 12

3 OFF
PICKUP
x P
INSTANT.

13
GROUND-FAULT DELAY Switch — sets length I 2t IN delay is an inverse time characteristic in
of time the circuit breaker will carry ground-fault that the delay time decreases as the current
current which exceeds the GROUND-FAULT increases.
PICKUP level before tripping. Delay bands are
labeled in seconds of ground-fault current at 1 I 2t OUT delay is a constant time characteristic
times the sensor size, S. Delay can be adjusted in that the delay time does not change as the
to four positions of I2t ramp operation (I2t IN) or current increases.
four positions of fixed time delays ( I2t OUT).
For sensor sizes below 2000 amperes and I2t
Figure 25 – Ground-fault Delay IN ground-fault current levels less than 1 x S,
the actual time delay will be longer than the
delay setting. At ground-fault current levels
equal to or greater than 1 x S, the delay will be
equal to the delay setting.
.35 .45
.3 .55
.25 .65 For sensor sizes equal to or greater than 2000
.2
PICKUP
.75 amperes, the actual time delay will be equal to
x S

GROUND FAULT
the delay setting for ground-fault currents of
I 2 t OUT I 2 t IN
.5
2000 amperes and above.
.5
.32 .32
.2 .2
.1
DELAY
.1
Ground-fault Alarm Function
SEC. AT
1xS

GROUND-FAULT ALARM Switch — switch


value (multiplied by the sensor size) sets the
current level at which the circuit breaker will
signal the POWERLOGIC system that a ground
fault is present.

Figure 27 – Ground-fault Alarm


Figure 26 – Ground-fault Pickup
(> 1600A Sensor)
.35 .45
.3 .55
.25 .65

.2 .75
PICKUP
x S

GROUND FAULT
ALARM
880 960
800 1040

720 1120
640 1200
PICKUP

GROUND FAULT
gure 23 – Ground-fault Pick
2 2
I t OUT I t IN
.5 .5
.32 .32
.2 .2
.1 .1
DELAY
SEC. AT
1xS

14
PART 3 – A LOOK AT COORDINATION

COORDINATION COORDINATION UNDER GROUND-FAULT


CONDITIONS
When designing an electrical distribution sys-
tem, coordination must be considered. The National Electrical Code (NEC) requires
that equipment ground-fault protection be pro-
Coordination is the process of localizing the vided at service entrance disconnecting means
protection against an overcurrent condition to rated for 1000 amperes or more on solidly
restrict an outage to only affected equipment. grounded wye systems between 150 volt-to-
Only the upstream device closest to the fault ground and 600 volts phase-to-phase
trips – leaving the rest of the system intact to (NEC 215-10 includes ground-fault protection
continue supplying power to unaffected areas. requirements for feeders). In order to meet the
Coordination does not exist when more than minimum requirements set forth in the NEC, it
one device opens simultaneously during an is acceptable to provide ground-fault protec-
overcurrent condition. tion only at a single point in the electrical
system – at the main.
The degree of coordination required is depen-
dent on the load. For less critical loads, such What happens if a ground fault occurs farther
as commercial lighting, lack of coordination down in the system, at the branch circuit level
may only be a nuisance. For hospital applica- for instance? If the only device capable of
tions, manufacturing processes and other criti- detecting a ground fault is the service entrance
cal loads, coordination may be required. main, a ground fault anywhere in the system
will trip the main device. Coordination is lost
In order to maximize coordination, downstream because the main tripped and shut down the
branch devices should operate very fast – with entire system!
little or no intentional delay – and main devices
should delay operation so that the downstream It is estimated that over 80% of all overcurrents
devices can clear the fault. are low-level overloads and ground faults. Odds
are very high that the situation described above
Coordination is limited by the instantaneous will happen in the real world. In order to
trip characteristics of the upstream device. prevent a blackout condition, multiple levels of
When the magnitude of the overcurrent ex- ground-fault protection are recommended. That
ceeds the instantaneous pickup point of the is, equipment ground-fault protection should
upstream device, it will trip with no intentional be provided at each level of distribution (main,
delay and coordination is lost. feeder, branch, etc.) to maximize system con-
tinuity. By supplying multiple levels of ground-
Electronic trip devices from Square D, such as fault protection, it is possible to isolate ground
MICROLOGIC ® circuit breakers and GC faults to feeders and branch circuits or to any
GROUND-CENSOR ® relays, have adjustable portion of the system with ground-fault protec-
pickup and delay settings to maximize coordi- tion.
nation with other overcurrent protective de-
vices in the system.

For more information on coordination, see Cir-


cuit Breaker Application Guide SD354R2, Cir-
cuit Breaker Characteristic Trip Curves and
Coordination.

15
ZONE-SELECTIVE INTERLOCKING

Coordination assures that continuity of service is


maximized during any type of overcurrent. How-
ever, coordination does not eliminate the stress
on the system caused by the energy generated
during a fault. Zone-selective interlocking (ZSI)
actually reduces the stress on the system result-
ing from a fault while maximizing continuity of
service.

Without ZSI, a coordinated system results in the


circuit breaker closest to the fault clearing the
fault, but with an intentional delay.

With ZSI, the device closest to the fault will


ignore its preset short-time and/or ground-fault
delays and clear the fault with no intentional
delay.

Eliminating intentional delay with ZSI results in


faster tripping times without sacrificing coordina-
tion. This limits fault stress by reducing the
amount of let-through energy the system is sub-
jected to during an overcurrent.

Circuit breakers that are not coordinated (due


to improper settings) will not be coordinated
simply by using ZSI.

For more information on ZSI, see Circuit


Breaker Application Guide 0600SC9102R6/
95, Reducing Fault Stress with Zone-selective
Interlocking.

16
SQUARE D, , MICROLOGIC, POWERLOGIC, I-LINE and GROUND-CENSOR
are Registered Trademarks of Square D Company.

Order No. 602SC9601 6/96


Replaces SD378 Printed In USA © 1996 Square D All rights reserved.

Você também pode gostar