Você está na página 1de 1

TABLA DE CAPACIDADES DE DISTRIBUCION DE CONDUCTORES COMERCIALES.

PARA V LN
= 120 V, F = 60 HZ, TAMBIENTE = 30 C, V = 1.00 %.
Numero o MCM

IN

R (/m)

X (/m)

AISLAMIENTO TW (600 V, 60 C)

KVA-m

KVA-m

KVA-m

KVA-m

KVA-m

FP = 0.80

FP = 0.85

FP = 0.90

FP = 0.95

FP = 1.00

14 -TW

15

1.012E-02

2.091E-04

52.628

49.664

47.035

44.702

42.755

12 -TW

20

6.364E-03

1.939E-04

83.080

78.497

74.438

70.851

67.982

10 -TW

30

4.002E-03

1.804E-04

130.713

123.727

117.551

112.134

108.106

8 -TW

40

2.519E-03

1.683E-04

204.444

194.026

184.853

176.905

171.751

6 -TW

55

1.646E-03

1.653E-04

305.541

291.109

278.502

267.836

262.843

4 -TW

70

1.036E-03

1.555E-04

469.190

449.489

432.562

418.918

417.606

2 -TW

95

6.510E-04

1.460E-04

711.111

686.447

666.071

651.529

664.578

1/0 -TW

125

4.100E-04

1.460E-04

1041.001

1016.995

1000.000

994.372

1055.220

2/0 -TW

145

3.350E-04

1.427E-04

1223.460

1202.039

1189.547

1192.476

1291.463

3/0 -TW

165

2.670E-04

1.398E-04

1454.350

1439.282

1436.209

1455.218

1620.375

4/0 -TW

195

2.110E-04

1.361E-04

1727.382

1723.356

1735.944

1780.798

2050.427

250 MCM -TW

215

1.790E-04

1.388E-04

1910.279

1920.562

1952.333

2027.459

2416.983

300 MCM -TW

240

1.670E-04

1.352E-04

2014.903

2029.544

2067.749

2153.872

2590.659

350 MCM -TW

260

1.440E-04

1.332E-04

2217.302

2246.693

2305.439

2425.225

3004.444

400 MCM -TW

280

1.260E-04

1.329E-04

2396.366

2442.784

2525.189

2683.904

3433.651

500 MCM -TW

320

1.020E-04

1.302E-04

2708.740

2786.065

2912.364

3145.216

4241.569

AISLAMIENTO TTU (600 V, 75 C)

FP = 0.80

FP = 0.85

FP = 0.90

FP = 0.95

FP = 1.00

14 -TTU

15

1.063E-02

1.808E-04

50.257

47.405

44.874

42.624

12 -TTU

20

6.682E-03

1.700E-04

79.418

74.991

71.066

67.590

40.719
64.747

10 -TTU

30

4.202E-03

1.580E-04

125.171

118.372

112.354

107.056

102.960

8 -TTU

45

2.643E-03

1.580E-04

195.836

185.700

176.763

168.988

163.693

6 -TTU

65

1.662E-03

1.410E-04

305.926

290.953

277.821

266.580

260.313

4 -TTU

85

1.046E-03

1.320E-04

472.314

451.308

433.100

418.043

413.614

2 -TTU

115

6.570E-04

1.240E-04

721.067

693.588

670.396

652.678

658.508

1/0 -TTU

150

4.140E-04

1.280E-04

1060.392

1031.746

1009.912

998.551

1045.024

2/0 -TTU

175

3.280E-04

1.230E-04

1286.853

1259.160

1240.316

1236.090

1319.024

3/0 -TTU

200

2.600E-04

1.207E-04

1542.829

1520.261

1509.498

1519.696

1664.000

4/0 -TTU

230

2.060E-04

1.170E-04

1841.021

1827.540

1830.125

1862.955

2100.194

250 MCM -TTU

255

1.750E-04

1.150E-04

2070.048

2066.784

2083.733

2140.100

2472.229

300 MCM -TTU

285

1.460E-04

1.109E-04

2359.769

2370.368

2407.030

2496.069

2963.288

350 MCM -TTU

310

1.260E-04

1.109E-04

2585.395

2613.820

2674.907

2803.370

3433.651

400 MCM -TTU

335

1.100E-04

1.102E-04

2807.163

2854.740

2942.427

3114.536

3933.091

500 MCM -TTU

380

8.900E-05

1.119E-04

3127.367

3214.337

3357.023

3620.698

4861.124

TABLAS CALCULADAS EN BASE A LA FORMULA:

KVA L

10 V% KV 2
(R cos() X sin())

DONDE:
KV = 0.208
V% = 1.000

EQUIVALENCIAS
FP
0.80
0.85
0.90
0.95
1.00

0.64
0.55
0.45
0.32
0.00

V
%

COS
0.80
0.85
0.90
0.95
1.00

NOTA: EN ESTE CASO KVA - M.

SEN
0.60
0.53
0.44
0.31
0.00

NOTA: EL CONDUCTOR CON


AISLAMIENTO TTU TAMBIEN ES
LLAMADO XLPE AISLADO A 600V