Você está na página 1de 20

YCA (A Series)

AIR-COOLED SCROLL CHILLER


(R22/R407C)

THIS PAGE IS INTENTIONALLY LEFT BLANK

INTRODUCTION

GENERAL DESCRIPTION
YORK Millennium Air-Cooled Scroll Chillers provide chilled water for all air conditioning applications using central station air
handling units or terminal units. They are completely self-contained and are designed for outdoor (roof or ground level)
installation. Each unit includes hermetic scroll compressors, a liquid evaporator, air cooled condenser, and a weather proof
microprocessor control center, all mounted on a formed steel base.

UNIT NOMENCLATURE
UNIT
The model number denotes the following characteristics of the unit :

YORK

050

Generation

Chiller

Air-Cooled

Model 020 025 030


040 050 060
070 080 095
115

INTRODUCTION

GENERAL
The 20-115 Ton (70-400kW) YCA Models are shipped complete from the factory ready for installation and use.
The unit is pressure-tested, evacuated, and fully charged with R22 or optional R-407C and includes an initial oil charge. After assembly,
a complete operational test is performed to ensure that the refrigeration circuit operates correctly.

COMPRESSORS
Single speed winding, scroll compressor of fully sealed hermetic type, equipped with suction vapor cooled
windings, crankcase heater and internal line break motor protection. Besides that, the integration of a set of high
and low pressure switches in the unit provides better protection to the compressor, prolonging the compressor
life span.

EVAPORATOR
Direct expansion type with refrigerant inside high efficiency copper tubes, chilled liquid forced over
the tubes by galvanized steel baffles. Constructed and tested for maximum 225 PSIG (15.5 bar)
refrigerant side design working pressure and 150 PSIG (10 bar) water side design working pressure.

CONDENSER COILS
The air-cooled condenser coils shall consists of 3/8 OD, inner-grooved seamless copper tubes arranged in staggered rows. They
are mechanically expanded into die-formed aluminium condenser fin coil to provide optimum heat exchange capability. All coils are
pressure tested to withstand 450psig during production stage.

FANS
The condenser fans are designed for maximum efficiency and are statically and dynamically balanced
for vibration-free operation. They are directly driven by independent motors, and positioned for vertical
air discharge.

FAN MOTORS
The fan motors shall be of TEFC Squirrel-cage type. They feature ball bearings that are double-sealed
and permanently lubricated.

POWER PANEL
Rain tight, powder coated steel cabinets with hinged, latched and gasket sealed outer doors. Provide main power connection(s), control
power connections, compressor and fan motor start contactors, current overloads, and factory wiring.

INTRODUCTION

a) Remote water temperature reset.


b) Programmable Set-points (within Manufacturer limits)
c) Forty character liquid crystal display, descriptions in English, numeric data in English
(or Metric) units.
d) Display Data.
e) System Safety.
f ) Unit Safety.
g) Alarm Contacts.
h) Automatic control of compressor start/stop, anti-coincidence and anti-recycle timers,
automatic pump-down shut-down, condenser fans, evaporator pump, unit alarm contacts,
and chiller operation from 0F to 125F ambient. Automatic reset to normal chiller operation
after power failure.

OPTIONS AND ACCESSORIES


1) Single Point Power Supply - Single point Terminal Block for field connection and interconnecting wiring to the compressors.
2) Single Point Circuit Breaker - Single point Terminal Block with Circuit Breaker can be supplied to isolate power voltage for servicing.
3) Low Temperature Process Brine - Leaving chilled liquid setpoint range 20F to 55F.
4) Pressure Tranducers and Readout Capability - Discharge Pressure Tranducers : Permits unit to sense and display discharge pressure.
5) Heresite / Epoxy Coating Condenser Coil.
6) Copper Fin / Hydrophilic Fin Condenser Coil.
7) Protective Grille for condenser coil.
8) 1 inch or 2 inches Deflection Spring Isolators.
9) Power Factor Correction Capacitors - Provided to correct unit compressor factor to a 0.90 - 0.95.
10) Hot-Gas Bypass.
11) Flange Kits.
12) Flow Switch.

PHYSICAL DATA
YCA Physical Data R22 (50Hz)

MODEL
NOMINAL COOLING CAPACITY
Refrigerant Type
No of Refrigerant Circuit
Unit Capacity Control
Nominal Refrigerant Charge / Circuit
COMPRESSOR
Type
Power Supply
Quantity
RLA (each)
LRA (each)
Maximum Operating Current
(each)
Oil Charge (each)
EVAPORATOR
Type
Construction
Max Water Side Pressure
Max Ref Side Pressure
Water Connection Spec
Water Connection Size
Nominal Water Flow Rate
Pressure Drop
CONDENSER COIL
Tube Type
Tube Size / Thickness
Fin Type / Thickness
Number of coil
No of Row
Fins per Inch
Surface Area
CONDENSER FAN
Type / Drive
Size
Qty / Unit
Design Motor Size
Nominal Airflow / Fan
Nominal RLA / Each
UNIT DIMENSION
Width
Depth
Height
ESTIMATED UNIT WEIGHT
ESTIMATED OPERATING WEIGHT

YCA
ton
MBH
kWr

20
19.1
229.2
67.2

25
22.3
267.6
78.4

30
30.0
360.0
105.5

40
38.2
458.4
134.3

50
44.5
534.0
156.5

Steps
kg

1
2
10

1
2
14

1
2
20

2
4
16

2
4
16

70
66.8
801.6
234.9

80
76.4
916.8
268.7

95
89.9
1078.8
316.1

115
114.6
1375.2
403.0

2
6
17

2
6
23

2
4
24

2
6
30

2
6
36

6
23.2
175

4
37.2
270

6
29.3
215

6
37.2
270

R22

V/Ph/Hz

Welded Hermetic (Scroll)


380-415V / 3PH / 50Hz
4
6
23.2
19.6
175
145

A
A

2
19.6
145

2
23.2
175

2
29.3
215

4
19.6
145

32.0

35.0

50.0

32.0

35.0

32.0

35.0

69.0

50.0

69.0

Litre

3.31

6.21

7.98

3.31

6.21

3.31

6.21

7.98

7.98

7.98

3"
91.7 (5.8)
8.4 (57.7)

DX
Shell & Tube
150 (1034)
225 (1551)
BS 10 Table E
3"
3"
106.8 (6.7)
137.3 (8.7)
4.9 (34.1)
7.4 (51.1)

4"
160.3 (10.1)
5.2 (36.2)

2
4
12
54.2 (5.0)

Copper Tube
3/8" OD / 0.33mm
Aluminium Fin / 0.115mm
2
4
4
3
14
12
54.2 (5.0)
99.0 (9.2)

4
4
12
99.0 (9.2)

PSIG (kPa)
PSIG (kPa)
in
USgpm (l/s)
PSIG (kPa)

2 - 1/2"
45.8 (2.9)
5.1 (35.0)

2 - 1/2"
53.5 (3.4)
7.8 (53.5)

3"
72.0 (4.5)
4.3 (29.9)

in / mm
Qty

ft (m)

1
3
12
23.6 (2.2)

1
4
12
23.6 (2.2)

2
3
12
54.2 (5.0)

4"
4"
183.4 (11.6) 215.8 (13.6)
7.3 (50.2)
7.9 (54.7)

4
4
14
99.0 (9.2)

4
3
12
134.4 (12.5)

4"
275.0 (17.4)
6.5 (45.1)

4
4
14
137.5 (12.8)

Axial / Direct
35.4 (900)

in (mm)

3
3
2
2
2
4
4
4
6
6
HP (kW)
0.63 (0.47)
0.63 (0.47)
2 (1.5)
3 (2.3)
4 (3.0)
2 (1.5)
2 (1.5)
3 (2.3)
2 (1.5)
3 (2.3)
CFM (m/h) 12700 (21590) 12700 (21590) 26000 (44200) 26000 (44200) 32600 (55420) 52000 (88400) 49500 (84150) 54400 (92480) 74000 (125800) 75600 (128520)
A
1.8
1.8
4.2
5.6
7.4
4.2
4.2
5.6
4.2
5.6
in (mm)
in (mm)
in (mm)
kg
kg

105.6 (2683) 105.6 (2683)


60.8 (1544) 60.8 (1544)
52.6 (1335) 52.6 (1335)
903
945
918
955

116.1 (2948)
75.4 (1914)
64.6 (1640)
1434
1454

116.1 (2948) 116.1 (2948)


75.4 (1914) 75.6 (1919)
64.6 (1640) 67.3 (1710)
1530
1608
1545
1645

Note:
(i) Nominal Info based on LCWT of 44oF (6.7oC) and 95oF (35.0oC) ambient temperature.
(ii) The rated load ampere (RLA) and locked rotor ampere (LRA) are rated at Power Supply 415V/3Ph/50Hz
(iii) Compressor runs on mineral oil.

60
57.2
686.4
201.1

86.2 (2190) 86.2 (2190) 86.2 (2190) 125.5 (3290)


100.2 (2546) 100.2 (2546) 100.2 (2546) 90.6 (2300)
81.3 (2066) 81.3 (2066) 81.3 (2066) 82.1 (2085)
2516
2717
2823
4147
2547
2780
2880
4240

125.5 (3290)
90.6 (2300)
82.1 (2085)
4598
4740

PHYSICAL DATA
YCA Physical Data R407C (50Hz)

MODEL
NOMINAL COOLING CAPACITY
Refrigerant Type
No of Refrigerant Circuit
Unit Capacity Control
Nominal Refrigerant Charge / Circuit
COMPRESSOR
Type
Power Supply
Quantity
RLA (each)
LRA (each)
Maximum Operating Current
(each)
Oil Charge (each)
EVAPORATOR
Type
Construction
Max Water Side Pressure
Max Ref Side Pressure
Water Connection Spec
Water Connection Size
Nominal Water Flow Rate
Pressure Drop
CONDENSER COIL
Tube Type
Tube Size / Thickness
Fin Type / Thickness
Number of coil
No of Row
Fins per Inch
Surface Area
CONDENSER FAN
Type / Drive
Size
Qty / Unit
Design Motor Size
Nominal Airflow / Fan
Nominal RLA / Each
UNIT DIMENSION
Width
Depth
Height
ESTIMATED UNIT WEIGHT
ESTIMATED OPERATING WEIGHT

YCA
ton
MBH
kWr

20
18.2
218.4
64.0

25
20.8
249.6
73.1

30
28.4
340.8
99.9

40
36.5
438.0
128.4

50
41.5
498.0
145.9

Steps
kg

1
2
10

1
2
14

1
2
20

2
4
16

2
4
16

60
54.7
656.4
192.4

70
62.3
747.6
219.1

80
70.1
841.2
246.5

95
85.1
1021.2
299.3

115
105.1
1261.2
369.6

2
6
17

2
6
23

2
4
24

2
6
30

2
6
36

6
23.0
175

4
36.3
270

6
29.6
215

6
36.3
270

R407C

V/Ph/Hz

Welded Hermetic (Scroll)


380-415V / 3PH / 50Hz
4
6
23.0
19.6
175
145

A
A

2
19.6
145

2
23.0
175

2
29.6
215

4
19.6
145

32.0

35.0

50.0

32.0

35.0

32.0

35.0

69.0

50.0

69.0

Litre

3.31

6.21

7.98

3.31

6.21

3.31

6.21

7.98

7.98

7.98

3"
87.6 (5.5)
7.4 (50.8)

DX
Shell & Tube
150 (1034)
225 (1551)
BS 10 Table E
3"
3"
99.6 (6.3)
131.2 (8.3)
5.1 (35.4)
6.0 (41.5)

4"
149.5 (9.4)
5.7 (39.5)

4"
168.2 (10.6)
6.4 (44.2)

4"
204.2 (12.9)
6.9 (47.9)

4"
252.2 (15.9)
6.5 (44.7)

2
4
12
54.2 (5.0)

Copper Tube
3/8" OD / 0.33mm
Aluminium Fin / 0.115mm
2
4
4
3
14
12
54.2 (5.0)
99.0 (9.2)

4
4
12
99.0 (9.2)

4
4
14
99.0 (9.2)

4
3
12
134.4 (12.5)

4
4
14
137.5 (12.8)

PSIG (kPa)
PSIG (kPa)
in
USgpm (l/s)
PSIG (kPa)

2 - 1/2"
43.7 (2.8)
2.0 (14.0)

2 - 1/2"
50.0 (3.2)
7.9 (54.6)

3"
68.2 (4.3)
2.1 (14.7)

in / mm
Qty

ft (m)

1
3
12
23.6 (2.2)

1
4
12
23.6 (2.2)

2
3
12
54.2 (5.0)

Axial / Direct
35.4 (900)

in (mm)

4
3
3
2
2
2
4
6
6
4
2 (1.5)
HP (kW)
0.63 (0.47)
0.63 (0.47)
2 (1.5)
3 (2.3)
4 (3.0)
3 (2.3)
2 (1.5)
3 (2.3)
2 (1.5)
CFM (m/h) 12700 (21590) 12700 (21590) 26000 (44200) 26000 (44200) 32600 (55420) 52000 (88400) 49500 (84150) 54400 (92480) 74000 (125800) 75600 (128520)
4.2
1.8
1.8
4.2
5.6
7.4
5.6
4.2
5.6
A
4.2
in (mm)
in (mm)
in (mm)
kg
kg

105.6 (2683)
60.8 (1544)
52.6 (1335)
903
918

105.6 (2683)
60.8 (1544)
52.6 (1335)
945
955

116.1 (2948)
75.4 (1914)
64.6 (1640)
1434
1454

116.1 (2948)
75.4 (1914)
64.6 (1640)
1530
1545

116.1 (2948)
75.6 (1919)
67.3 (1710)
1608
1645

86.2 (2190)
100.2 (2546)
81.3 (2066)
2516
2547

86.2 (2190)
100.2 (2546)
81.3 (2066)
2717
2780

86.2 (2190)
100.2 (2546)
81.3 (2066)
2823
2880

125.5 (3290)
90.6 (2300)
82.1 (2085)
4147
4240

125.5 (3290)
90.6 (2300)
82.1 (2085)
4598
4740

Note:
(i) Nominal Info based on LCWT of 44oF (6.7oC) and 95oF (35.0oC) ambient temperature.
(ii) The rated load ampere (RLA) and locked rotor ampere (LRA) are rated at Power Supply 415V/3Ph/50Hz
(iii) Compressor runs on P.O.E. oil.

PHYSICAL DATA
YCA Physical Data R22 (60Hz)

MODEL
NOMINAL COOLING CAPACITY

YCA
ton
MBH
kWr

20
18.5
222.0
65.1

Refrigerant Type
No of Refrigerant Circuit
1
Unit Capacity Control
2
Steps
kg
Nominal Refrigerant Charge / Circuit
10
COMPRESSOR
Type
Power Supply
V/Ph/Hz
Quantity
2
RLA (each)
17.3
A
LRA (each)
147
A
Maximum Operating Current
A
19.6
(each)
Oil Charge (each)
Litre
3.31
EVAPORATOR
Type
Construction
PSIG (kPa)
Max Water Side Pressure
PSIG (kPa)
Max Ref Side Pressure
Water Connection Spec
in
2 - 1/2"
Water Connection Size
USgpm (l/s) 44.4 (2.8)
Nominal Water Flow Rate
Pressure Drop
PSIG (kPa)
5.1 (35.0)
CONDENSER COIL
Tube Type
in / mm
Tube Size / Thickness
Fin Type / Thickness
Qty
1
Number of coil
3
No of Row
Fins per Inch
12
ft (m)
23.6 (2.2)
Surface Area
CONDENSER FAN
Type / Drive
in (mm)
Size
3
Qty / Unit
0.63 (0.47)
HP (kW)
Design Motor Size
Nominal Airflow / Fan
CFM (m/h) 12700 (21590)
1.8
A
Nominal RLA / Each
UNIT DIMENSION
in (mm)
105.6 (2683)
Width
60.8 (1544)
in (mm)
Depth
in (mm)
52.6 (1335)
Height
kg
861
ESTIMATED UNIT WEIGHT
kg
ESTIMATED OPERATING WEIGHT
876

25
23.3
279.6
81.9

30
26.7
320.4
93.9

40
36.3
435.6
127.6

50
46.6
559.2
163.9

1
2
14

1
2
20

1
2
16

2
4
16

70
69.9
838.8
245.8

80
72.6
871.2
255.3

95
92.6
1111.2
325.6

115
108.8
1305.6
382.6

2
4
17

2
6
23

2
4
24

2
4
30

2
6
36

6
19.6
145

4
29.4
215

4
37.1
270

6
29.4
215

R22

Welded Hermetic (Scroll)


460V / 3PH / 60Hz
4
4
19.6
22.6
145
175

2
19.6
145

2
22.6
175

2
29.4
215

32.0

35.0

50.0

32.0

35.0

32.0

50.0

69.0

50.0

3.31

6.21

7.98

3.31

6.21

3.31

6.21

7.98

7.98

3"
87.1 (5.5)
8.4 (57.7)

DX
Shell & Tube
150 (1034)
225 (1551)
BS 10 Table E
3"
3"
111.8 (7.1)
127.9 (8.1)
4.9 (34.1)
7.4 (51.1)

4"
167.8 (10.6)
5.2 (36.2)

4"
174.2 (11.0)
7.3 (50.2)

4"
222.2 (14.0)
7.9 (54.7)

4"
261.1 (16.5)
6.5 (45.1)

2
4
12
54.2 (5.0)

Copper Tube
3/8" OD / 0.33mm
Aluminium Fin / 0.115mm
2
4
4
3
14
12
54.2 (5.0)
99.0 (9.2)

4
4
12
99.0 (9.2)

4
4
14
99.0 (9.2)

4
3
12
134.4 (12.5)

4
4
14
137.5 (12.8)

2 - 1/2"
55.9 (3.5)
7.8 (53.5)

1
4
12
23.6 (2.2)

3"
64.1 (4.0)
4.3 (29.9)

2
3
12
54.2 (5.0)

Axial / Direct
35.4 (900)
3
2
2
2
4
4
6
6
4
0.63 (0.47)
3 (2.3)
3 (2.3)
5.5 (4.1)
3 (2.3)
3 (2.3)
2 (1.5)
3 (2.3)
3 (2.3)
12700 (21590) 26000 (44200) 26000 (44200) 32600 (55420) 52000 (88400) 49500 (84150) 54400 (92480) 74000 (125800)75600 (128520)
1.8
5.9
5.9
10.1
5.9
5.9
4.2
5.9
5.9
105.6 (2683)
60.8 (1544)
52.6 (1335)
911
921

116.1 (2948)
75.4 (1914)
64.6 (1640)
1319
1340

116.1 (2948)
75.4 (1914)
64.6 (1640)
1506
1521

116.1 (2948)
75.6 (1919)
67.3 (1710)
1541
1578

Note:
(i) Nominal Info based on LCWT of 44oF (6.7oC) and 95oF (35.0oC) ambient temperature.
(ii) The rated load ampere (RLA) and locked rotor ampere (LRA) are rated at Power Supply 460V/3Ph/60Hz
(iii) Compressor runs on mineral oil.

60
53.3
639.6
187.4

86.2 (2190) 86.2 (2190)


100.2 (2546) 100.2 (2546)
81.3 (2066) 81.3 (2066)
2411
2616
2442
2679

86.2 (2190)
100.2 (2546)
81.3 (2066)
2823
2880

125.5 (3290)
90.6 (2300)
82.1 (2085)
3827
3920

125.5 (3290)
90.6 (2300)
82.1 (2085)
4598
4740

PHYSICAL DATA
YCA Physical Data R407C (60Hz)

MODEL
NOMINAL COOLING CAPACITY
Refrigerant Type
No of Refrigerant Circuit
Unit Capacity Control
Nominal Refrigerant Charge / Circuit
COMPRESSOR
Type
Power Supply
Quantity
RLA (each)
LRA (each)
Maximum Operating Current
(each)
Oil Charge (each)
EVAPORATOR
Type
Construction
Max Water Side Pressure
Max Ref Side Pressure
Water Connection Spec
Water Connection Size
Nominal Water Flow Rate
Pressure Drop
CONDENSER COIL
Tube Type
Tube Size / Thickness
Fin Type / Thickness
Number of coil
No of Row
Fins per Inch
Surface Area
CONDENSER FAN
Type / Drive
Size
Qty / Unit
Design Motor Size
Nominal Airflow / Fan
Nominal RLA / Each
UNIT DIMENSION
Width
Depth
Height
ESTIMATED UNIT WEIGHT
ESTIMATED OPERATING WEIGHT

YCA
ton
MBH
kWr

20
17.5
210.0
61.5

25
22.1
265.2
77.7

30
25.0
300.0
87.9

40
34.2
410.4
120.3

50
44.2
530.4
155.4

Steps
kg

1
2
10

1
2
14

1
2
20

1
2
16

2
4
16

60
50.0
600.0
175.8

70
66.3
795.6
233.1

80
68.4
820.8
240.5

95
84.4
1012.8
296.8

115
102.5
1230.0
360.4

2
4
17

2
6
23

2
4
24

2
4
30

2
6
36

6
19.5
145

4
29.8
215

4
36.6
270

6
29.8
215

R407C

V/Ph/Hz

Welded Hermetic (Scroll)


460V / 3PH / 60Hz
4
4
19.5
23.0
145
175

A
A

2
17.2
125

2
19.5
145

2
23.0
175

2
29.8
215

19.6

32.0

35.0

50.0

32.0

35.0

32.0

50.0

69.0

50.0

Litre

3.31

3.31

6.21

7.98

3.31

6.21

3.31

6.21

7.98

7.98

3"
82.1 (5.2)
7.4 (50.8)

DX
Shell & Tube
150 (1034)
225 (1551)
BS 10 Table E
3"
3"
106.1 (6.7)
120.0 (7.6)
5.1 (35.4)
6.0 (41.5)

4"
159.1 (10.0)
5.7 (39.5)

4"
164.2 (10.4)
6.4 (44.2)

4"
202.6 (12.8)
6.9 (47.9)

4"
246.0 (15.5)
6.5 (44.7)

2
4
12
54.2 (5.0)

Copper Tube
3/8" OD / 0.33mm
Aluminium Fin / 0.115mm
2
4
4
3
14
12
54.2 (5.0)
99.0 (9.2)

4
4
12
99.0 (9.2)

4
4
14
99.0 (9.2)

4
3
12
134.4 (12.5)

4
4
14
137.5 (12.8)

PSIG (kPa)
PSIG (kPa)
in
USgpm (l/s)
PSIG (kPa)

2 - 1/2"
42.0 (2.7)
2.0 (14.0)

2 - 1/2"
53.0 (3.3)
7.9 (54.6)

3"
60.0 (3.8)
2.1 (14.7)

in / mm
Qty

ft (m)

1
3
12
23.6 (2.2)

1
4
12
23.6 (2.2)

2
3
12
54.2 (5.0)

Axial / Direct
35.4 (900)

in (mm)

3
3
2
2
2
4
4
4
6
6
HP (kW)
0.63 (0.47)
0.63 (0.47)
3 (2.3)
3 (2.3)
5.5 (4.1)
3 (2.3)
3 (2.3)
3 (2.3)
2 (1.5)
3 (2.3)
CFM (m/h) 12700 (21590) 12700 (21590) 26000 (44200) 26000 (44200) 32600 (55420) 52000 (88400) 49500 (84150) 54400 (92480) 74000 (125800) 75600 (128520)
1.8
1.8
5.9
5.9
10.1
5.9
5.9
5.9
4.2
5.9
A
in (mm)
in (mm)
in (mm)
kg
kg

105.6 (2683)
60.8 (1544)
52.6 (1335)
861
876

105.6 (2683)
60.8 (1544)
52.6 (1335)
911
921

116.1 (2948)
75.4 (1914)
64.6 (1640)
1319
1340

116.1 (2948)
75.4 (1914)
64.6 (1640)
1506
1521

116.1 (2948)
75.6 (1919)
67.3 (1710)
1541
1578

86.2 (2190)
100.2 (2546)
81.3 (2066)
2411
2442

86.2 (2190)
100.2 (2546)
81.3 (2066)
2616
2679

86.2 (2190)
100.2 (2546)
81.3 (2066)
2823
2880

125.5 (3290)
90.6 (2300)
82.1 (2085)
3827
3920

125.5 (3290)
90.6 (2300)
82.1 (2085)
4598
4740

Note:
(i) Nominal Info based on LCWT of 44oF (6.7oC) and 95oF (35.0oC) ambient temperature.
(ii) The rated load ampere (RLA) and locked rotor ampere (LRA) are rated at Power Supply 460V/3Ph/60Hz
(iii) Compressor runs on P.O.E. oil.

RATED DATA (Imperial)


YCA Rated Data R22 (50Hz)

85F
Model

20

25

30

40

50

60

70

80

95

115

LCWT
(F)

Outdoor Air Temperature (Dry Bulb)


95F

Total
Capacity
(MBH)

Power
Input
(kW)

Total
Capacity
(MBH)

Power
Input
(kW)

Total
Capacity
(MBH)

Power
Input
(kW)

40
42
44
46
40
42
44
46

224
234
243
253
261
272
284
295

19.4
19.4
19.4
19.4
22.9
22.9
22.9
23.0

211
220
229
239
246
256
267
278

21.8
21.8
21.8
21.8
25.6
25.6
25.7
25.7

197
205
214
223
229
239
249
260

24.6
24.6
24.6
24.6
28.6
28.7
28.7
28.7

40
42
44
46
40
42
44
46
40
42
44
46
40
42
44
46
40
42
44
46
40
42

352
367
382
398
449
467
487
507
522
545
567
591
673
701
730
760
784
817
851
886
899
938

30.5
30.6
30.7
30.8
38.8
38.8
38.9
38.9
45.8
45.8
45.9
45.9
58.2
58.2
58.3
58.3
68.6
68.7
68.8
68.9
76.0
76.4

331
345
359
374
421
439
458
477
491
512
534
556
632
659
687
716
737
768
801
834
842
879

33.9
34.0
34.1
34.2
43.6
43.6
43.7
43.7
51.2
51.3
51.3
51.4
65.4
65.4
65.5
65.5
76.8
76.9
77.0
77.1
84.2
84.6

309
322
336
350
393
410
428
446
458
478
498
520
590
615
642
669
687
717
748
780
783
818

37.8
37.9
38.0
38.1
49.1
49.1
49.1
49.2
57.3
57.3
57.4
57.5
73.7
73.7
73.7
73.7
85.9
86.0
86.1
86.2
93.6
94.0

44
46
40
42
44
46
40
42
44
46

978
1019
1057
1101
1147
1194
1348
1406
1466
1528

76.9
77.3
91.5
91.8
92.1
92.5
114.0
114.6
115.3
116.0

916
956
993
1035
1078
1123
1263
1318
1375
1433

85.0
85.5
101.6
102.0
102.3
102.6
126.3
126.9
127.6
128.2

853
890
926
966
1007
1049
1175
1226
1280
1335

94.4
94.8
113.3
113.6
113.9
114.2
140.4
141.0
141.6
142.2

Note:
(i) The Power Input ratings listed above are compressor motor power input (kW).
(ii) LCWT = Leaving Chilled Water Temperature.
(iii) Direct interpolation is permissible but extrapolation is not recommended.
(iv) Ratings are based upon 2.4 USgpm cooler water per ton and 0.0001 ft.h F/Btu fouling factor.

105F

RATED DATA (Imperial)


YCA Rated Data R407C (50Hz)

Outdoor Air Temperature (Dry Bulb)


85F
Model

20

25

30

40

50

60

70

80

95

115

LCWT
(F)

95F

105F

Total
Capacity
(MBH)

Power
Input
(kW)

Total
Capacity
(MBH)

Power
Input
(kW)

Total
Capacity
(MBH)

Power
Input
(kW)

40

216

19.5

200

22.2

184

25.3

42
44
46
40
42
44
46

225
236
246
246
258
269
282

19.6
19.6
19.6
22.5
22.6
22.6
22.6

209
219
229
228
238
249
261

22.2
22.2
22.2
25.5
25.5
25.6
25.6

193
201
211
207
217
228
238

25.3
25.3
25.3
28.9
29.0
29.0
29.0

40
42
44
46
40
42
44
46

335
351
367
383
431
451
471
492

30.6
30.7
30.8
30.9
39.1
39.1
39.1
39.1

311
325
340
356
400
419
438
458

34.4
34.5
34.6
34.7
44.4
44.4
44.4
44.4

285
299
313
327
368
385
403
421

38.7
38.8
38.9
39.1
50.5
50.5
50.5
50.5

40
42
44
46
40
42
44
46
40
42
44
46

493
516
539
563
647
676
707
739
739
773
808
845

45.1
45.1
45.1
45.2
58.6
58.7
58.7
58.7
67.6
67.7
67.7
67.7

455
476
498
521
600
628
657
687
683
715
748
782

51.0
51.1
51.1
51.1
66.6
66.6
66.6
66.7
76.6
76.6
76.7
76.7

415
435
455
476
552
578
604
632
622
652
683
714

57.8
57.9
57.9
58.0
75.8
75.8
75.8
75.8
86.8
86.9
86.9
87.0

40
42

826
863

74.6
74.8

771
805

84.0
84.3

710
742

94.3
94.7

44
46
40
42
44
46
40
42
44
46

901
941
1005
1052
1100
1150
1240
1295
1352
1411

75.1
75.4
91.9
92.2
92.5
92.8
111.8
112.2
112.7
113.1

841
878
932
976
1021
1068
1156
1208
1262
1317

84.6
84.9
103.2
103.5
103.8
104.1
125.9
126.4
126.9
127.4

776
810
856
896
939
982
1065
1113
1164
1216

95.0
95.4
116.2
116.5
116.8
117.2
141.5
142.0
142.6
143.1

Note:
(i) The Power Input ratings listed above are compressor motor power input (kW).
(ii) LCWT = Leaving Chilled Water Temperature.
(iii) Direct interpolation is permissible but extrapolation is not recommended.
(iv) Ratings are based upon 2.4 USgpm cooler water per ton and 0.0001 ft.h F/Btu fouling factor.

10

RATED DATA (Imperial)


YCA Rated Data R22 (60Hz)

Outdoor Air Temperature (Dry Bulb)


85F
Model

LCWT
(F)

20

25

30

40

50

60

70

80

95

115

95F

105F

Total
Capacity
(MBH)

Power
Input
(kW)

Total
Capacity
(MBH)

Power
Input
(kW)

Total
Capacity
(MBH)

Power
Input
(kW)

40
42
44
46

218
227
236
245

17.7
17.8
17.9
18.0

205
214
222
231

19.5
19.6
19.8
19.9

192
201
209
217

21.7
21.8
21.9
22.0

40
42
44
46
40
42
44
46
40

274
285
297
309
313
326
339
353
426

23.6
23.6
23.6
23.7
27.3
27.4
27.5
27.5
37.0

258
269
280
291
295
307
320
333
401

26.4
26.4
26.5
26.5
30.4
30.4
30.5
30.6
41.0

241
251
262
273
276
287
299
312
375

29.5
29.5
29.6
29.6
33.8
33.9
34.0
34.0
45.4

42
44
46
40
42
44
46
40
42
44
46
40
42

444
462
481
547
570
594
618
626
652
678
705
821
855

37.2
37.4
37.6
47.1
47.2
47.3
47.4
54.6
54.8
54.9
55.1
70.7
70.8

418
435
453
516
537
559
582
590
614
640
666
773
806

41.2
41.3
41.5
52.7
52.8
52.9
53.0
60.7
60.9
61.0
61.2
79.1
79.2

391
407
424
482
503
524
546
551
575
599
624
723
754

45.6
45.8
46.0
59.0
59.1
59.2
59.3
67.6
67.8
67.9
68.1
88.4
88.6

44
46
40
42
44
46
40
42
44
46
40
42
44
46

890
927
853
888
925
962
1090
1135
1181
1229
1279
1332
1387
1444

70.9
71.1
74.0
74.4
74.8
75.2
91.8
92.5
93.2
93.8
111.1
111.6
112.2
112.7

839
874
802
836
871
906
1024
1067
1111
1157
1203
1254
1306
1360

79.4
79.5
81.9
82.3
82.7
83.1
100.9
101.6
102.3
103.0
122.9
123.5
124.0
124.6

786
819
750
782
815
849
956
997
1039
1082
1125
1173
1222
1273

88.8
88.9
90.8
91.2
91.6
91.9
111.2
111.9
112.6
113.3
136.2
136.8
137.3
137.9

Note:
(i) The Power Input ratings listed above are compressor motor power input (kW).
(ii) LCWT = Leaving Chilled Water Temperature.
(iii) Direct interpolation is permissible but extrapolation is not recommended.
(iv) Ratings are based upon 2.4 USgpm cooler water per ton and 0.0001 ft.h F/Btu fouling factor.

11

RATED DATA (Imperial)


YCA Rated Data R407C (60Hz)

Outdoor Air Temperature (Dry Bulb)


85F
Model

LCWT
(F)

20

25

30

40

50

60

70

80

95

115

95F

105F

Total
Capacity
(MBH)

Power
Input
(kW)

Total
Capacity
(MBH)

Power
Input
(kW)

Total
Capacity
(MBH)

Power
Input
(kW)

40
42
44
46

206
216
225
235

18.0
18.1
18.1
18.2

192
201
210
219

20.4
20.5
20.5
20.5

178
186
195
203

23.1
23.2
23.2
23.2

40
42
44
46
40
42
44
46
40
42
44
46
40
42
44
46
40
42
44
46
40
42

261
273
285
298
297
310
324
339
403
422
441
461
522
546
570
595
594
621
648
677
783
818

23.7
23.8
23.8
23.8
27.2
27.3
27.3
27.4
37.8
37.9
38.1
38.2
47.4
47.5
47.6
47.7
54.4
54.5
54.6
54.7
71.2
71.3

243
254
265
277
275
287
300
314
375
392
410
429
486
508
531
554
549
574
600
627
728
762

26.8
26.8
26.8
26.9
30.6
30.7
30.8
30.8
42.1
42.2
42.4
42.5
53.5
53.6
53.7
53.8
61.3
61.4
61.5
61.6
80.3
80.4

224
234
245
256
251
262
274
287
346
362
379
396
448
468
490
512
501
525
549
574
671
702

30.2
30.3
30.3
30.4
34.5
34.6
34.7
34.7
47.0
47.2
47.3
47.5
60.5
60.5
60.6
60.7
69.1
69.2
69.3
69.5
90.7
90.8

44
46
40
42
44
46
40
42
44
46
40
42
44
46

855
893
807
844
882
922
999
1045
1090
1140
1210
1266
1323
1383

71.4
71.5
75.6
75.8
76.1
76.4
90.7
91.1
91.5
91.9
113.3
113.8
114.2
114.6

796
832
750
784
820
857
927
969
1013
1059
1125
1176
1230
1286

80.5
80.6
84.2
84.5
84.8
85.1
101.5
101.9
102.4
102.8
126.2
126.7
127.1
127.6

734
768
692
724
757
792
853
892
933
976
1038
1086
1136
1188

90.9
91.1
94.0
94.3
94.6
94.9
113.7
114.1
114.6
115.1
141.0
141.5
142.0
142.4

Note:
(i) The Power Input ratings listed above are compressor motor power input (kW).
(ii) LCWT = Leaving Chilled Water Temperature.
(iii) Direct interpolation is permissible but extrapolation is not recommended.
(iv) Ratings are based upon 2.4 USgpm cooler water per ton and 0.0001 ft.h F/Btu fouling factor.

12

RATED DATA (Metric)


YCA Rated Data R22 (50Hz)

Outdoor Air Temperature (Dry Bulb)


29.4C
Model

LCWT
(C)

20

25

30

40

50

60

70

80

95

115

35.0C

40.5C

Total
Capacity
(kWr)

Power
Input
(kW)

Total
Capacity
(kWr)

Power
Input
(kW)

Total
Capacity
(kWr)

Power
Input
(kW)

4.4
5.6
6.7
7.8

65.7
68.5
71.3
74.3

19.4
19.4
19.4
19.4

61.7
64.4
67.1
69.9

21.8
21.8
21.8
21.8

57.6
60.1
62.7
65.3

24.6
24.6
24.6
24.6

4.4
5.6
6.7
7.8
4.4
5.6
6.7
7.8
4.4
5.6
6.7
7.8
4.4
5.6
6.7

76.6
79.8
83.1
86.5
103.2
107.6
112.0
116.6
131.4
137.0
142.7
148.5
153.1
159.6
166.3

22.9
22.9
22.9
23.0
30.5
30.6
30.7
30.8
38.8
38.8
38.9
38.9
45.8
45.8
45.9

71.9
75.0
78.2
81.5
96.9
101.1
105.3
109.7
123.5
128.8
134.2
139.8
143.9
150.1
156.5

25.6
25.6
25.7
25.7
33.9
34.0
34.1
34.2
43.6
43.6
43.7
43.7
51.2
51.3
51.3

67.1
70.0
73.0
76.2
90.4
94.3
98.3
102.5
115.2
120.2
125.4
130.7
134.2
140.1
146.1

28.6
28.7
28.7
28.7
37.8
37.9
38.0
38.1
49.1
49.1
49.1
49.2
57.3
57.3
57.4

7.8
4.4
5.6
6.7
7.8
4.4
5.6

173.1
197.2
205.5
214.0
222.8
229.7
239.4

45.9
58.2
58.2
58.3
58.3
68.6
68.7

163.0
185.2
193.2
201.3
209.7
215.8
225.1

51.4
65.4
65.4
65.5
65.5
76.8
76.9

152.3
172.9
180.3
188.0
196.0
201.3
210.1

57.5
73.7
73.7
73.7
73.7
85.9
86.0

6.7
7.8
4.4
5.6
6.7
7.8

249.4
259.6
263.4
274.7
286.5
298.5

68.8
68.9
76.0
76.4
76.9
77.3

234.7
244.5
246.7
257.5
268.6
280.0

77.0
77.1
84.2
84.6
85.0
85.5

219.1
228.5
229.5
239.6
250.0
260.8

86.1
86.2
93.6
94.0
94.4
94.8

4.4
5.6
6.7
7.8
4.4
5.6
6.7
7.8

309.7
322.7
336.1
349.9
395.1
412.1
429.7
447.8

91.5
91.8
92.1
92.5
114.0
114.6
115.3
116.0

290.8
303.2
316.0
329.0
370.1
386.2
402.8
420.0

101.6
102.0
102.3
102.6
126.3
126.9
127.6
128.2

271.2
282.9
295.0
307.4
344.2
359.4
375.0
391.2

113.3
113.6
113.9
114.2
140.4
141.0
141.6
142.2

Note:
(i) The Power Input ratings listed above are compressor motor power input (kW).
(ii) LCWT = Leaving Chilled Water Temperature.
(iii) Direct interpolation is permissible but extrapolation is not recommended.
(iv) Ratings are based upon 0.043 (l/s) cooler water per ton and 0.0176 m. K/kW fouling factor.

13

RATED DATA (Metric)


YCA Rated Data R407C (50Hz)

Outdoor Air Temperature (Dry Bulb)


29.4C
Model

20

25

30

40

50

60

70

80

95

115

LCWT
(C)

35.0C

40.5C

Total
Capacity
(kWr)

Power
Input
(kW)

Total
Capacity
(kWr)

Power
Input
(kW)

Total
Capacity
(kWr)

Power
Input
(kW)

4.4
5.6

63.2
66.0

19.5
19.6

58.6
61.3

22.2
22.2

53.9
56.4

25.3
25.3

6.7
7.8

69.0
72.2

19.6
19.6

64.1
67.1

22.2
22.2

59.0
61.7

25.3
25.3

4.4
5.6
6.7
7.8
4.4
5.6
6.7
7.8
4.4
5.6
6.7
7.8
4.4
5.6
6.7
7.8
4.4
5.6
6.7
7.8
4.4
5.6
6.7

72.2
75.5
78.9
82.5
98.2
102.8
107.5
112.3
126.3
132.1
138.1
144.3
144.4
151.1
157.9
165.0
189.5
198.1
207.1
216.5
216.6
226.6
236.8

22.5
22.6
22.6
22.6
30.6
30.7
30.8
30.9
39.1
39.1
39.1
39.1
45.1
45.1
45.1
45.2
58.6
58.7
58.7
58.7
67.6
67.7
67.7

66.7
69.8
73.0
76.3
91.0
95.3
99.7
104.3
117.2
122.7
128.3
134.1
133.4
139.6
146.1
152.7
175.9
184.0
192.4
201.2
200.1
209.4
219.1

25.5
25.5
25.6
25.6
34.4
34.5
34.6
34.7
44.4
44.4
44.4
44.4
51.0
51.1
51.1
51.1
66.6
66.6
66.6
66.7
76.6
76.6
76.7

60.8
63.7
66.7
69.7
83.6
87.6
91.7
96.0
107.7
112.9
118.1
123.5
121.5
127.4
133.3
139.5
161.6
169.3
177.1
185.2
182.3
191.1
200.0

28.9
29.0
29.0
29.0
38.7
38.8
38.9
39.1
50.5
50.5
50.5
50.5
57.8
57.9
57.9
58.0
75.8
75.8
75.8
75.8
86.8
86.9
86.9

7.8
4.4
5.6
6.7
7.8
4.4
5.6
6.7
7.8
4.4
5.6
6.7
7.8

247.5
242.2
253.0
264.1
275.6
294.5
308.3
322.4
336.9
363.3
379.5
396.2
413.4

67.7
74.6
74.8
75.1
75.4
91.9
92.2
92.5
92.8
111.8
112.2
112.7
113.1

229.0
225.8
236.0
246.5
257.4
273.0
285.9
299.2
312.9
338.7
353.9
369.7
386.1

76.7
84.0
84.3
84.6
84.9
103.2
103.5
103.8
104.1
125.9
126.4
126.9
127.4

209.2
208.0
217.5
227.3
237.5
250.8
262.7
275.0
287.9
312.0
326.2
341.0
356.3

87.0
94.3
94.7
95.0
95.4
116.2
116.5
116.8
117.2
141.5
142.0
142.6
143.1

Note:
(i) The Power Input ratings listed above are compressor motor power input (kW).
(ii) LCWT = Leaving Chilled Water Temperature.
(iii) Direct interpolation is permissible but extrapolation is not recommended.
(iv) Ratings are based upon 0.043 (l/s) cooler water per ton and 0.0176 m. K/kW fouling factor.

14

RATED DATA (Metric)


YCA Rated Data R22 (60Hz)

Outdoor Air Temperature (Dry Bulb)


29.4C

35.0C

40.5C

Model

LCWT
(C)

Total
Capacity
(kWr)

Power
Input
(kW)

Total
Capacity
(kWr)

Power
Input
(kW)

Total
Capacity
(kWr)

Power
Input
(kW)

20

4.4
5.6
6.7
7.8

63.8
66.5
69.1
71.9

17.7
17.8
17.9
18.0

60.1
62.6
65.2
67.8

19.5
19.6
19.8
19.9

56.4
58.8
61.2
63.6

21.7
21.8
21.9
22.0

4.4
5.6
6.7
7.8
4.4
5.6
6.7
7.8
4.4
5.6
6.7
7.8
4.4
5.6
6.7
7.8

80.2
83.6
87.0
90.5
91.7
95.5
99.4
103.3
125.0
130.1
135.5
141.0
160.4
167.1
173.9
181.0

23.6
23.6
23.6
23.7
27.3
27.4
27.5
27.5
37.0
37.2
37.4
37.6
47.1
47.2
47.3
47.4

75.5
78.7
82.0
85.3
86.4
90.0
93.7
97.5
117.6
122.5
127.6
132.8
151.1
157.4
163.9
170.7

26.4
26.4
26.5
26.5
30.4
30.4
30.5
30.6
41.0
41.2
41.3
41.5
52.7
52.8
52.9
53.0

70.6
73.7
76.8
80.0
80.8
84.2
87.7
91.4
109.9
114.6
119.4
124.3
141.3
147.3
153.5
159.9

29.5
29.5
29.6
29.6
33.8
33.9
34.0
34.0
45.4
45.6
45.8
46.0
59.0
59.1
59.2
59.3

4.4
5.6
6.7
7.8

183.4
190.9
198.8
206.7

54.6
54.8
54.9
55.1

172.8
180.0
187.4
195.0

60.7
60.9
61.0
61.2

161.5
168.4
175.5
182.7

67.6
67.8
67.9
68.1

4.4
5.6

240.6
250.7

70.7
70.8

226.6
236.1

79.1
79.2

211.9
221.0

88.4
88.6

6.7
7.8
4.4
5.6
6.7
7.8

260.9
271.5
250.0
260.3
271.1
282.0

70.9
71.1
74.0
74.4
74.8
75.2

245.9
256.0
235.1
245.0
255.2
265.6

79.4
79.5
81.9
82.3
82.7
83.1

230.3
239.9
219.8
229.1
238.8
248.7

88.8
88.9
90.8
91.2
91.6
91.9

4.4
5.6
6.7
7.8
4.4
5.6
6.7
7.8

319.3
332.6
346.2
360.3
374.9
390.4
406.6
423.0

91.8
92.5
93.2
93.8
111.1
111.6
112.2
112.7

300.1
312.7
325.6
339.0
352.7
367.4
382.7
398.5

100.9
101.6
102.3
103.0
122.9
123.5
124.0
124.6

280.2
292.1
304.4
317.1
329.7
343.7
358.2
373.0

111.2
111.9
112.6
113.3
136.2
136.8
137.3
137.9

25

30

40

50

60

70

80

95

115

Note:
(i) The Power Input ratings listed above are compressor motor power input (kW).
(ii) LCWT = Leaving Chilled Water Temperature.
(iii) Direct interpolation is permissible but extrapolation is not recommended.
(iv) Ratings are based upon 0.043 (l/s) cooler water per ton and 0.0176 m. K/kW fouling factor.

15

RATED DATA (Metric)


YCA Rated Data R407C (60Hz)

Outdoor Air Temperature (Dry Bulb)


29.4C
Model

20

25

30

40

50

60

70

80

95

115

35.0C

40.5C

LCWT
(C)

Total
Capacity
(kWr)

Power
Input
(kW)

Total
Capacity
(kWr)

Power
Input
(kW)

Total
Capacity
(kWr)

Power
Input
(kW)

4.4
5.6
6.7
7.8

60.4
63.2
66.0
68.8

18.0
18.1
18.1
18.2

56.4
59.0
61.6
64.2

20.4
20.5
20.5
20.5

52.1
54.5
57.0
59.5

23.1
23.2
23.2
23.2

4.4
5.6
6.7
7.8
4.4
5.6
6.7
7.8
4.4
5.6
6.7
7.8
4.4
5.6
6.7
7.8

76.5
79.9
83.5
87.2
87.0
91.0
95.0
99.2
118.2
123.6
129.3
135.1
153.0
159.9
167.0
174.4

23.7
23.8
23.8
23.8
27.2
27.3
27.3
27.4
37.8
37.9
38.1
38.2
47.4
47.5
47.6
47.7

71.1
74.4
77.7
81.2
80.5
84.1
87.9
91.9
109.9
114.9
120.2
125.6
142.3
148.8
155.5
162.5

26.8
26.8
26.8
26.9
30.6
30.7
30.8
30.8
42.1
42.2
42.4
42.5
53.5
53.6
53.7
53.8

65.6
68.6
71.7
75.0
73.5
76.9
80.4
84.1
101.4
106.1
111.0
116.0
131.2
137.2
143.5
150.0

30.2
30.3
30.3
30.4
34.5
34.6
34.7
34.7
47.0
47.2
47.3
47.5
60.5
60.5
60.6
60.7

4.4
5.6
6.7
7.8
4.4
5.6

174.1
181.9
190.0
198.5
229.5
239.8

54.4
54.5
54.6
54.7
71.2
71.3

160.9
168.3
175.9
183.8
213.4
223.2

61.3
61.4
61.5
61.6
80.3
80.4

146.9
153.8
160.8
168.2
196.7
205.8

69.1
69.2
69.3
69.5
90.7
90.8

6.7
7.8
4.4
5.6
6.7
7.8

250.5
261.6
236.4
247.3
258.5
270.1

71.4
71.5
75.6
75.8
76.1
76.4

233.2
243.7
219.7
229.8
240.4
251.2

80.5
80.6
84.2
84.5
84.8
85.1

215.2
225.0
202.8
212.2
222.0
232.0

90.9
91.1
94.0
94.3
94.6
94.9

4.4
5.6

292.9
306.1

90.7
91.1

271.5
284.0

101.5
101.9

250.0
261.5

113.7
114.1

6.7
7.8
4.4
5.6
6.7
7.8

319.5
334.1
354.7
370.9
387.8
405.2

91.5
91.9
113.3
113.8
114.2
114.6

296.9
310.3
329.6
344.8
360.6
376.8

102.4
102.8
126.2
126.7
127.1
127.6

273.5
286.0
304.1
318.3
332.9
348.0

114.6
115.1
141.0
141.5
142.0
142.4

Note:
(i) The Power Input ratings listed above are compressor motor power input (kW).
(ii) LCWT = Leaving Chilled Water Temperature.
(iii) Direct interpolation is permissible but extrapolation is not recommended.
(iv) Ratings are based upon 0.043 (l/s) cooler water per ton and 0.0176 m. K/kW fouling factor.

16

THIS PAGE IS INTENTIONALLY LEFT BLANK

17

THIS PAGE IS INTENTIONALLY LEFT BLANK

18

YCA-A-CTL-032010
*Photo
used for illustration purposes only
15

While utmost care is taken in ensuring that all details in the publication are correct at the time of going to press,
we are constantly striving for improvement and therefore please confirm with your local distribution office
for the latest update on the product interested. All rights reserved.