Você está na página 1de 1

ZERO SPEED SWITCH DATA SHEET

1 of 1

Sheet No
TAG NO.

To sense and transmit Zero speed condition of


RAV/screw coveyor

Service

NO:ELAC020002
Preliminary

Prepared by

VC

MSK

SRH

For Inquiry

Approved by

PS

PS

MSK

For Order

Date

21/02/07 14/06/08 12/8/2008

Revision Index
SUPPLY VOLTAGE

APPLICATION DETAILS
230/110 V AC. +/-10 % , 50 Hz. +/- 5 %

SENSING SPEED

5 TO 50 RPM

SENSING DISTANCE

14 mm. +/- 10 % NOMINAL 7 mm. +/- 10 % effective

ENCLOSURE

CAST ALUMINIUM

ELECTRICAL DETAILS
MAKE

KANA ELECTROMECH

MODEL

ESS 102-C-TD

POWER CONSUMPTION

5 VA. MAX.

VISUAL INDICATION

a) MAIN ON INDICATION LED


b ) RELAY ON INDICATION LED
c ) SENSOR PROBE ACTUATION LED

SPEED SETTING ACCURACY

WITHIN +/- 5 % OF DESIRED VALUE

REPEAT ACCURACY

WITHIN +/- 1 %

ACTUATION DIFFFERENTIAL

LESS THAN 5 % OF SET VALUE

OUTPUT CONTACT RATING

6A RESISTIVE AT 240 V AC

OUTPUT CONTACTS

2 NO + 2NC POTENTIAL FREE CONTACT, 2 C/O RELAY CONTACT

TIME DELAY
a ) SPEED SETTING POTENTIOMETER

CONTROLS

b ) INITIAL TIME DELAY SETTING POTENTIOMETER ( 1 TO 30 SEC. ADJ.)


c) NUISANCE TIME DELAY SETTING POTENTIOMETER (1 TO 30 SEC. ADJ.)
PROBE SIZE

M30 X 1.5P X 80 MM. LONG

NO. OF FLAGS

4 NOS.

AMBIENT TEMP.

55 DEG. C MAX.

PROTECTION CATEGORY

IP 65 ( SUITABLE FOR OUTDOOR INSTALLATION )

PROBE TYPE

NON CONTACT INDUCTIVE PROXIMITY TYPE 3 WIRE

PROBE MATERIAL

NICKEL CROME PLATED,THREADED BRASS TUBE WITH TWO CLAMPING NUTS

CALIBRATION

THE SWITCHES TO BE TESTED FOR CALIBRATION AT 25 % ,50 % , 75 %, 100 %OF FULL SPEED

CABLE

3 CORE , 2MTR. LONG INTRGRAL

MOUNTING

WALL MOUNTED

PAINTING

POWDER COATED LIGHT GREY

INSPECTION & TESTING REQUIREMENTS


INSPECTION

BY THERMAX,CLIENT,CONSULTANT

DOCUMENTS SUBMITTED ALONG WITH SUPPLY


06 set of O & M Manual.

GUARANTEE
18 MONTFHS FROM DATE OF SUPPLY OR 12 MONTHS FROM DATE OF COMMISSIONING WHICHEVER EARLIER
REV NO
1
2

REVISION DETAILS
REVISED AS PER SUPPLIERS FEEDBACK.
PART. NO. REVISED FOR ERP

REV BY
MSK
SRH

NOTE :
The serial number should be mentioned on the unit and also on all inspection reports.
Thermax spcification sheet number should be mentioned on all inspection reports
Supplier to confirm specification as mentioned above devation/ discrepancy if any should be informed before suppling the material .

DATE
15/04/08
12/8/2008