Você está na página 1de 3

IPN = 100 ..

1000 A

Coreless Coil Current Transducer


RH 100 .. 1000-P
For the electronic measurement of currents: AC, pulsed, mixed, with
a galvanic isolation between the primary circuit (high power) and the
secondary circuit (electronic circuit).

Electrical data
Primary nominal
r.m.s. current

Features

Type

IPN (A)
100
200
500
1000

VOUT
VC
Vd
IC
RIS
RL

RH 100-P
RH 200-P
RH 500-P
RH 1000-P

Output voltage(r.m.s)@ IPN, RL = 10 k, TA = 25C


Supply voltage ( 5 %)
R.m.s. voltage for AC isolation test, 50/60Hz, 1 mn
Current consumption
Isolation resistance@ 500 V DC
Load resistance

4
15
> 2.5
10
> 500
100

V
V
kV
mA
M
K

Accuracy-Dynamic performance data

VOE
VOT
TC G
tr
f

Linearity (0 .. IPN)
Electrical offset voltage, TA = 25C
Thermal drift of VOE
Thermal drift of the gain (% of reading)
Response time @ 90% of IP
Frequency bandwidth (3 dB)

0.5 % of IPN
5
mV
0.3
mV/K
0.03
%/K
1
s
20Hz .. 100KHz

General data
TA
TS
m

Ambient operating temperature


Ambient storage temperature
Mass
Min. internal creepage distance/clearance

-10 .. +75
C
-15 .. +80
C
20
g
110.5 m m

No magnetic core
Rogowski Coil principle
Highly accurate integration circuit
Voltage output

Advantages

Wide sensing range


Wide frequency range
Quick response
No hysteresis error
No insertion impedance
Small size and lightweight

Applications
Observing complicated current
waveforms

High speed and high current

sensing such as IGBT


Welding
Power unit
Electric power regulator
Discharge tube
Antenna
Monitoring for irruptive current

Notes :

040714/1

LEM Components

www.lem.com

RH 100 .. 1000-P (in mm)

30

0.5

M GND

-Vcc +Vcc

52

30

11

20

6.3
17.8

4- 0.7

2-2

4.2

11

6.3

0.5

Direction of Current

20.3

Specifications subject to change without notice.

2-5

This datasheet has been download from: