Você está na página 1de 70

Line Constants

Sector Energy
D SE PTI NC
Steffen Schmidt

Copyright Siemens AG 2008. All rights reserved.

Introduction

Page 2

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Overhead Lines and Cables

Page 3

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Overhead Lines
Tower Outlines

L1, L2, L3 System 1


M1, M2, M3 System 2
G
Ground wire

Page 4

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Overhead Lines
Conductor Types
Aluminium conductor steel reinforced
(ACSR, Al/St, AL1/ST1A)

Aluminium alloy conductor


(AAAC, Ald, AL2 AL5)
Galvanized steel conductor (only for earth wires)
(St, ST1A)
Aluminium clad steel conductor (only for earth wires)
(ACS, St-Al-um, A20SA)

Page 5

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Single Core Cable


Principle Construction
Conductor
Aluminium
Copper

Insulation
XLPE
PVC
Paper, mass-impregnated
Oil
Cable screen, armour
Copper screen
Aluminium sheath
Lead sheath
Steel tape armour

Outer protection
Page 6

28.06.2008

Steffen Schmidt

Copyright
Copyright Siemens AG 2008.
2007. All rights
reserved.
E D SE
PTI NC

Importance of Line Characteristics

Line Characteristics are necessary for

Network planning (load flow, short circuit)

Design of equipment

Fault clearing

Protection setting (especially distance protection)

Page 7

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Overhead Lines and Cables


Equivalent Circuits
positive sequence system ( = negative sequence system)
A
U(1)A

R(1)

I(1)A

X(1)

I(1)E

G (1)

C(1)

C(1)

G (1)

E
U(1)E

01

zero sequence system


A
U(0)A

R(0)

I(0)A

X(0)

I(0)E

G ( 0)

C( 0 )

C( 0 )

G ( 0)

E
U(0)E

00
Page 8

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Calculation by Hand / Pocket Calculator


Formulas and Examples

Page 9

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Conductor with ground return

Conductor
Current

Infinite ground plane

Current

Page 10

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Self Impedance of Line-Earth Loop

Z S Rint R ext j Xint X ext


Rint

q
R ext

1
0
8
Xint L i

1
n

X ext 0 f ln

Page 11

28.06.2008

Steffen Schmidt

DE
r

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Data
Internal Inductance

1
Li 0 r
8

DE 660

0 = 1,26 10-3 H/km

r= 1
Li = 0,05 mH/km

Equivalent depth of return path of


earth current

E
f

E = 100 m

f = 50 Hz
DE = 930 m

r n rt n
2 sin 180

Page 12

28.06.2008

n 1

Equivalent radius of bundle


conductor
r t = 16 mm

s = 400 mm n = 2
r = 81 mm

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Input Data

dab

2rt

DE

Page 13

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Two conductors with ground return

Conductor
Current

Infinite ground plane

Current

Page 14

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Mutual Impedance between Line-Earth Loops

Z M R M j XM

1
RM 0
8

XM 0 f ln

Page 15

28.06.2008

Steffen Schmidt

DE
dab

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Positive Sequence Impedance


UR IR Z S IS ZM IT ZM
UR IR Z S IS IT ZM
IR IS IT 0

for positive
sequence:

UR IR Z S ZM

1
ZS ZS R ZS S ZS T
3

UR
Z S ZM
IR

1
ZM ZM RS ZM ST ZM TR
3

Page 16

28.06.2008

Steffen Schmidt

Z1 Z S Z M

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Positive Sequence Impedance


Z1 Z S Z M
Z1 R1 j X1
R1 Rint R ext RM
R1

X1 Xint X ext XM

1
1
0 0
q 8
8

1
De
De
0 f ln
0 f ln
n
r
dm

X1 L i

dm 3 dR,S dS,T dT,R


1 1
d
X1 2 f 0 r 0 f ln m
8

n
r

R1

Page 17

28.06.2008

d
r
ln m
r
4 n

X1 f 0

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Positive Sequence Impedance


Example Overhead line Given Data
Conductor:

70 mm Al

Cross-Section:q = 70 mm
Diameter:

d = 10.5 mm

Resistivity Al: Al = 29 mm/km


r = 1

Permeability Al:

Frequency:

f = 50 Hz

Soil resistivity: E = 100 m


0 = 4

Magnetic constant:
10-4 H/km
s/km

=0.00126

Positive Sequence
Impedance ??

Page 18

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Positive Sequence Impedance


Example Overhead line Result
R1

29 mm 2
R1
70mm 2 km

km

R1 0.41

d
r
ln m
r
4 n

X1 f 0

dm 3 dR,S dS,T dT,R


dm 3 1.4m 1.4m 2.8m 1.76m
50 0.00126 s 1
1.76m

ln

s km
0.00525m
4 1

X1 0.38
km
X1

Page 19

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Zero Sequence Impedance


UR IR Z S IS ZM IT ZM
UR IR Z S IS IT ZM
for zero sequence: IR IS IT

UR IR Z S 2 ZM

1
ZS ZS R ZS S ZS T
3

UR
Z S 2 ZM
IR

1
ZM ZM RS ZM ST ZM TR
3

Page 20

28.06.2008

Steffen Schmidt

Z 0 Z S 2 ZM

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Zero Sequence Impedance


Z 0 Z S 2 ZM

Z0 R 0 j X 0

R 0 Rint R ext 2 RM
R0

1
2
0 0
q 8
8

X0 Xint X ext 2 XM
X0 Li

1
De
De
0 f ln
2 0 f ln
n
r
dm

dm 3 dR,S dS,T dT,R

r
De3
X0 f 0
0 f ln
4 n
r dm2
R0

Page 21

3
0
q 8

28.06.2008

r
De3
X 0 f 0
ln
4

n
r d2m

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Zero Sequence Impedance


Example Overhead line Given Data
Conductor:

70 mm Al

Cross-Section:q = 70 mm
Diameter:

d = 10.5 mm

Resistivity Al: Al = 29 mm/km


Permeability Al:

Frequency:

r = 1

f = 50 Hz

Soil resistivity: E = 100 m


Magnetic constant:
10-4 H/km
s/km

0 = 4
=0.00126

Zero Sequence
Impedance ??

Page 22

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Zero Sequence Impedance


Example Overhead line Result
R0

3
0
q 8

29 mm 2 3 0.00126 s 50 2
R0

70mm 2 km 8
km
s
R 0 0.56

km

r
De3

X0 f 0
ln
2
r dm
4 n
De 660

E
930m
f

50 0.00126 s 1
930 3

X0
ln
2
s km
0.00525 1.76
4
X 0 1.57
Page 23

28.06.2008

km

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Positive and Zero Sequence Capacitances


of an Overhead Line
Positive Sequence
Capacitance:
2 r 0
C1
d
ln
r

S
dRS

dST
T

dTR

Zero Sequence
Capacitance:

hS
hT

hR

C0

Page 24

relative dielectric constant (in air: r = 1)

dielectric constant (8.854 nF/km)

conductor distance

conductor height

line sag

radius of conductor
28.06.2008

2 r 0
2h
3 ln
3
r d2
d 3 dRS dST dTR
h 3 hR hS hT 0.7 s

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Positive and Zero Sequence Capacitance


Example Overhead line Given Data
Conductor:

70 mm Al

Diameter:

d = 10.5 mm

Frequency:

f = 50 Hz

Max. line sag:

s=4m

Dielectric constant: 0 = 8.854


nF/km

Positive Sequence
Capacitance ??
Zero Sequence
Capacitance ??
Page 25

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Positive Sequence Capacitance


Example Overhead line Result
C1

2 r 0
d
ln
r
d 3 dRS dST dTR
d 3 1.4m 1.4m 2.8m 1.76m

C1

2 1 8.854nF / km
1.76m
ln
0.00525m

C1 9.57

Page 26

28.06.2008

nF
km

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Zero Sequence Capacitance


Example Overhead line Result
C0

2 r 0
2h
3 ln
3
r d2
d 3 dRS dST dTR
d 3 1.4m 1.4m 2.8m 1.76m
h 3 hR hS hT 0.7 s
h 12m 0.7 4m 9.2m

C0

2 1 8.854nF / km
2 9.2m
3 ln
2
3
0.00525m 1.76m

C0 4.33
Page 27

28.06.2008

nF
km

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Positive and Zero Sequence Capacitances


of Cables

belted cable

a:

C1 CE 3C

b, c:

C1 C0 CE

three-core cable

single-core cable

C0 0.6 C1

CE
C

capacitance conductor cable screen (ground)


capacitance conductor - conductor

C1
C0

positive sequence system capacitance


zero sequence system capacitance

Page 28

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Typical Line Parameters

Page 29

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Calculation by Software Programs


Further Influences

Page 30

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Further influences

Earthed conductors (overhead line earth wire; cable shield)


Length of conductor twist
Skin effect
Height above ground; Exact calculation of earth return path
Conductor temperature

Page 31

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Further influences
Influence of an Earth Wire
Conductors:
earth wire:
70
max line sag:

ACS
4m

Influence on
Positive Sequence
Impedance ??
Zero Sequence
Impedance ??
Positive Sequence
Capacitance ??
Page 32

28.06.2008

Steffen Schmidt

Zero
Sequence
Copyright Siemens AG 2008. All rights reserved.

E D SE PTI NC

Further influences
Influence of an Earth Wire - Results
without earth wire

with earth wire

_______________________________________________________________________
positive sequence resistance

R1

0.414 /km

0.414 /km

positive sequence reactance

X1

0.381 /km

0.381 /km

zero sequence resistance

R0

0.559 /km

0.631 /km

zero sequence reactance

X0

1.566 /km

1.419 /km

positive sequence capacitance C1

9.640 nF/km

9.641 nF/km

zero sequence capacitance

4.332 nF/km

4.999 nF/km

Page 33

28.06.2008

C0

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Further influences
Influence of Metallic Cable Sheath
Conductor:
Cross-Section:

630 mm

Material:

Copper

Outer Diameter:

31 mm

Insulation:
Material:

XLPE

Metallic sheath:

Arrangement:
trefoil
spec. Soil Resistivity:
50 m
Frequency:
50 Hz

Page 34

28.06.2008

Steffen Schmidt

Cross-Section:

50 mm

Material:

Copper

Inner Diameter:

69 mm

Outer Diameter:

73 mm

Cable Diameter:

84 mm

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Further influences
Influence of Metallic Cable Sheath Results

Arrangement

Page 35

28.06.2008

Sheath
Bonding

R1

X1

R0

X0

[/km]

[/km]

[/km]

[/km]

0.039

0.120

0.368

0.134

0.196

0.070

0.175

0.365

0.138

0.212

0.031

0.190

0.179

1.673

1.000

0.035

0.183

0.192

0.349

0.189

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Further influences
Influence of Metallic Cable Sheath Cross Bonding

Page 36

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Further influences
Conductor Twist
Conductor twist results in
higher length of outer wires (red wire) of
the conductor
increase of resistance

Increase of DC-resistance
acc. to EN 50182:
7wires
19 wires
37 wires
61 wires
127 wires

Page 37

28.06.2008

Steffen Schmidt

1 layer
2 layers
3 layers
4 layers
6 layers

1.11 %
1.68 %
2.03 %
2.36 %
2.75 %

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Further influences
Influence of Conductor Temperature
RDC,T RDC,20 1 * TC 20C
T 20 1 * TC 20C

Page 38

RDC,T

resistance at conductor temperature T

RDC,20

DC resistance at 20C

temperature coefficient of conductor material

TC

conductor temperature

resistivity at conductor temperature T

20

resistivity at 20C

Conductor material

Temperature coefficient

Aluminium

0.0040 1/C

Aluminium alloy

0.0036 1/C

Copper

0.0039 1/C

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Further influences
Skin Effect
without Skin effect
Current density:

with Skin effect


Current density:

Calculation:

Calculation:
with Bessel functions (depending on R_)

Page 39

28.06.2008

1
f 0 r
4
Steffen Schmidt

R~ R

X~ X

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Further influences
External self impedance of Line-Earth-Loop

Page 40

Basic approach:

Exact calculation:

Concentrated earth return path in


depth De

Series expression by Carson to


consider earth current distribution and
conductor height above ground

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Other Characteristic Values

Page 41

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Other Characteristic Values


Surge Impedance and Natural Load

Snat

UN2

ZW

ZW

R1 j X1
j C1

ZW
R1
X1

Surge impedance (complex)


Resistance in the positive phase-sequence system
Reactance in the positive phase-sequence system

C1
Snat

Angular frequency (2f)


Capacitance in the positive phase-sequence system
Natural load

Page 42

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Other Characteristic Values


Charging Power
100,00 %
0,00

-0,00 kW
51,70 kVAr

Q C UN2 C1
QC
UN

Charging power
Rated voltage

C1

Angular frequency (2f)


Capacitance in the positive phase-sequence system

Page 43

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Other Characteristic Values


Reduction Factor Calculation
Reduction factor of earthed conductors
e.g. overhead line earth wires, metallic cable sheaths

Definition and Calculation acc. to IEC 60909-3


rE

Z
IE
C,L E
3 I0
Z S,E

rE

Reduction factor

IE

Earth current (current flowing through earth)

3I0

Zero sequence current during a single phase fault

ZC,L-E

Coupling impedance between phase conductors and


earthed conductors

ZS,E

Self impedance of earthed conductors

Page 44

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Other Characteristic Values


Reduction Factor Importance

A low reduction factor results in


low earth, touch and step voltages
low inductive interference in case of earth faults
low magnetic fields in case of earth faults
Page 45

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Measurement of line impedances

Page 46

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Measurement of Positive Sequence Impedance


Power Cable

Page 47

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Measurement of Zero Sequence Impedance


Power Cable

Page 48

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Measurement of Zero Sequence Impedance


Overhead Line
earth wire

overhead line

current source

A
V

local earth grid

Page 49

28.06.2008

remote earth grid

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Measurement of Line Impedances


Test Equipment

Diesel-generator
Diesel-generatorset
set
200kVA
200kVA

Volt-Meter
Volt-Meter

Clamp-AmpereClamp-AmpereMeter
Meter

Page 50

28.06.2008

Active-PowerActive-PowerMeter
Meter

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Measurement of Line Impedances


Connection of test leads

Short
Shortcircuiting
circuitingof
oftest
testline
line

Connection
Connectionto
tocurrent
current
source
source
Page 51

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Measurement of Line Impedances


Safety rules
1. Switch off
2. Lock against reclosure
3. Verify that system is de-energized
4. Earthing and short circuiting
5. Cover of nearby live parts

1. Be aware of trapped charges


2. Be aware of induced or influenced voltages
3. Have a clear predefined switching procedure
4. Have a back up switch off strategy
5. Stop work in case of confusion
6. Stop work in case of thunder storm (which may be at the remote end!)

Page 52

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Impedance of 220 kV Overhead Line


Comparison of Measured and Calculated Values
Conductors:
phase wire:

Al/St 591/82
double

bundle
earth wire:

OPGW
57 mm

steel
41 mm ACS
length:

26 km

measuredcalculated
measuredcalculated
_______________________________
_______________________________
RR1
1.57
1.571.46
1.46
1
XX1
7.66
7.667.80
7.80
1
RR0
3.63
3.633.42
3.42
0
XX0
23.4
23.422.0
22.0
0

Page 53

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Double circuit Zero sequence mutual impedance

Page 54

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Double circuit Zero sequence mutual impedance

Z0M

Page 55

28.06.2008

Steffen Schmidt

Zero sequence
mutual
impedance

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Double circuit Zero sequence mutual impedance


Example
Conductors:
phase wire:
230/30

Al/St

2er bundle
earth wire:
95/55

Al/St

max. sag:15 m
spec. soil resistivity: 50 m
frequency :
50 Hz

Page 56

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Double circuit Zero sequence mutual impedance


Result Impedances in symmetrical components
Z 00 (I,I)
Z (I,I)
10
Z 20 (I,I)

Z 00 (II,I)

Z10 (II,I)

Z 20 (II,I)

Z 01(I,I)

Z 02 (I,I)

Z 00 (I,II)

Z 01(I,II)

Z11 (I,I)
Z 21(I,I)
Z 01(II,I)

Z12 (I,I)
Z 22 (I,I)
Z 02 (II,I)

Z10 (I,II) Z11 (I,II)


Z 20 (I,II) Z 21(I,II)
Z 00 (II,II) Z 01(II,II)

Z11 (II,I)
Z 21(II,I)

Z12 (II,I)
Z 22 (II,I)

Z 02 (I,II)
Z12 (I,II)
Z 22 (I,II)

Z 02 (II,II)

Z10 (II,II) Z11 (II,II) Z12 (II,II)

Z 20 (II,II) Z 21(II,II) Z 22 (II,II)

positive sequence impedance


/km + j 0.266 /km

Z11(I,I)

= Z11(II,II) =

0.063

negative sequence impedance


/km + j 0.266 /km

Z22(I,I)

= Z22(II,II) =

0.063

zero sequence impedance


/km + j 0.970 /km

Z00(I,I)

= Z00(II,II) =

0.223

zero sequence coupling imp.


/km + j 0.537 /km

Z00(I,II)

= Z00(II,I) =

0.165

all other impedances


/km

<

Page 57

28.06.2008

ZXX

Steffen Schmidt

0.020 /km + j 0.020


Copyright Siemens AG 2008. All rights
reserved.
E D SE
PTI NC

Double circuit Zero sequence mutual impedance


Influence of zero sequence coupling on s.c. results (I)
SINCAL calculation of single phase short circuit currents
Without consideration of zero sequence coupling impedance
0.00 kA

4.18 kA

0.00 kA

4.18 kA

21.68 kA

8.36 kA

wrong

With consideration of zero sequence coupling impedance

0.00 kA

3.42 kA

0.00 kA

3.42 kA

21.68 kA

Page 58

28.06.2008

Steffen Schmidt

6.83 kA

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Double circuit Zero sequence mutual impedance


Influence of zero sequence coupling on s.c. results (II)
SINCAL calculation of single phase short circuit currents
Without consideration of zero sequence coupling impedance
2.94 kA

0.00 kA
21.68 kA

wrong

0.00 kA

5.18 kA
5.18 kA

With consideration of zero sequence coupling impedance

4.28 kA

0.00 kA
21.68 kA

Page 59

28.06.2008

Steffen Schmidt

0.00 kA

5.18 kA
5.18 kA

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Zero Sequence Impedance of a Double Line

U0 I0,1 Z 0,1 I0,2 Z 0,M


Z 0,res

U0
I0,1

Z 0,res Z 0,1

I0,2
Z 0,M
I0,1

Z0,1

Zero sequence impedance line 1

Z0,2

Zero Sequence impedance line 2

Z0,M

Mutual zero sequence impedance

Z0,res
line 1

resultant (effective) zero sequence impedance of

Page 60

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Zero Sequence Impedance of a Double Line


Operation Modes
Z 0,res Z 0,1 Z 0,M

Z0,res Z 0,1

Z 0,res

Z
Z 0,1 0,M
Z 0,1

Z 0,res Z 0,1 Z 0,M

Page 61

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Coupling of zero sequence systems

Page 62

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Double Line
Measurement of Zero Sequence Impedance

Page 63

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Double Line
Measurement of Zero Sequence Coupling Impedance

Page 64

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Double Line
Measurement of Double Line Zero Sequence Imped.

Page 65

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Double Line
Measurement of Shortened Zero Sequence Imped.

Page 66

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Zero Sequence Impedance of 220 kV Double Line


Comparison of Measured and Calculated Values

2T 1T

2T

1T

Al/St 591/82
OPGW
57 mm

steel
41 mm ACS

1S

2R 1R

2R

1R

E1
5.400 m
5.800 m
7.100 m

1T
1R

measured
calculated
measured
calculated
_______________________________
_______________________________
RR0
0.23
0.20
0.23/km
/km
0.20/km
/km
0
XX0
1.01
1.02
1.01/km
/km
1.02/km
/km
0
RR0M 0.16
0.15
0.16/km
/km
0.15/km
/km
0M
XX0M 0.48
0.49
0.48/km
/km
0.49/km
/km
0M

m
m
m
m

m
m
m
m

40.007
30.650
23.850
17.050

0.000
-5.400
2T
2R -5.800
-7.100
2S

Page 67

2S 1S

2S

: 1:300

1
-OPGW.lei

Conductors:
phase wire:
earth wire:

E1

E1

1S

28.06.2008

Fig. 1
Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Break time!

Page 68

28.06.2008

Steffen Schmidt

Copyright
Copyright Siemens AG 2008. All rights
reserved.
E D SE
PTI NC

Contact
Steffen Schmidt
Senior Consultant
Siemens AG, Energy Sector
E D SE PTI NC
Freyeslebenstr. 1
91058 Erlangen
Phone: +49 9131 - 7 32764
Fax:
+49 9131 - 7 32525
E-mail: steffen.schmidt@siemens.com

Page 69

28.06.2008

Steffen Schmidt

Copyright Siemens AG 2008. All rights


reserved.
E D SE
PTI NC

Thank you for your attention!

Page 70

28.06.2008

Steffen Schmidt

Copyright
Copyright Siemens AG 2008. All rights
reserved.
E D SE
PTI NC

Você também pode gostar