Você está na página 1de 5

EQPT: UNIT#1 DDCMIS

4001(K)
6PR#0.5 CU DG
SHLD

DESCP: UNIT#1 DDCMIS


COMPT:

S1

SPEC:

4002(K)
8PR#0.5 CU AN
SHLD

EQPT: 1BBA01

2001(C)
5C#2.5 CU, 1.1KV

DESCP: 11KV UNIT SWITCHGEAR#1CA


COMPT: 10F
SPEC:

EQPT: 1BBB01

2004(C)
14C#2.5 CU, 1.1KV

REFERENCE DRAWING/ DOCUMENT:


1. 6.6kV Switchgear GA & SLD, Dwg. No. DBP-L007-EL-00-SWY-OTH-004, Rev-C
2. Drive Control Philosophy, Doc. No. L609000-YL01-01-C-151030, Rev-D
3. DCS IO List, (as discussed with DBPL during meeting dtd 15-18 Jan 2013)
4. 11kV Oil Filler Transformer Scheme, Dwg. No. MVISL039SC44964A, Rev-5
5. 6.6kV Incomer Scheme, Dwg. No. MVISL039SC45045, Rev-6
6. Diagram of Cooler Control Gear (UAT), Dwg. No. 34566250932, Rev-00

2003(C)
3C#2.5 CU, 1.1KV

2002(C)
3C#2.5 CU, 1.1KV

DESCP: 6.6KV UNIT SWITCHGEAR#1DA


COMPT: 1F
SPEC:

EQPT: UAT#1A

DESCP: UNIT AUX TRAFORMER#1A


COMPT:
SPEC:

NOTE:
1. Jumpering of IO signals at DCS end shall be done by BHEL.

DRAWING RELEASE RECORD


REV

DATE

A
B
C

Contractor/Installer shall take all appropriate precautions to ensure the safety of all people located on the work
site, including Contractor's/Installer's personnel (or that of its subcontractor(s)) performing the WORK.

SCALE
PURPOSE

MASTER SCHEMATIC DIAGRAM

NONE

PREPARED

REVIEWED

APPROVED

12/30/2011

H PAREKH

B ANAND

A BISWAS

FOR INFORMATION

10/10/2012

D FERNANDES

B ANAND

A BISWAS

FOR INFORMATION

PROJECT
NUMBER

04/05/2013

N VAIDYA

B ANAND

A BISWAS

FOR CONSTRUCTION

L609000

NOTE: Drawing release record shown on Page 1.

CABLE BASE NO:1BBB

6.6KV UNIT SWGR#1DA


INCOMER#1
2 X 600MW DB SUPER THERMAL
POWER PROJECT
DB POWER LIMITED

L&T - SARGENT & LUNDY LTD.


BARODA.
SHEET: 01-BBB-000001
PAGE

OF

DWG CLASS: YS00


Product of PLADES

REV.

Filename: 01-BBB-000001.VSD

# SPECIAL NOTE:
Disconnect wire K57 from terminal 8 of Timer T1 & wire it at terminal 7 of Timer T1.

X4-5

X4-6

Y PHASE
T

X4-7

X4-8

B PHASE

JMPR/05

JMPR/04

JMPR/03

X4-14

X4-13
BUCHHOLZ
TRIP
51NS
CT
INPUT

PRESSURE
RELIEF VALVE
TRIP

OLTC
OIL SURGE
TRIP

WDG.
TEMP
TRIP

CB CLOSED
IN SERVICE

X03-4
33

32
S1

2001/4

X03-3
S

S
S1

2001/3

X03-2

X03-1
S

31

2001/1

2001/2

S
S1

OIL
TEMP
TRIP

30
S1

52
X3-20

2004/10

51
S
X3-19
T

S
T

2004/9

50
X3-18

2004/8

49
S
X3-17
T

S
T

2004/7

48
X3-16

47
S
2004/6
X3-15
T

S
T

2004/5

46
X3-14

45
S
2004/4
X3-13
T

S
T

2004/3

44

X3-11
T

T
JMPR/02

CB OPENED
86 OPTD

11kV UNIT SWGR#1CA

UAT#1A

X4-9

X4-10

NEUTRAL
T

JMPR/06

JMPR/01

X3-12

2004/2

43
S

S
2004/1

X01-10

NEUTRAL
T

R PHASE

2003/2

X01-9

2003/1

X01-6
S

2002/2

X01-7

2002/1

6.6kV UNIT SWITCHGEAR#1DA

X4-11

X4-12

64R
CT
INPUT

Contractor/Installer shall take all appropriate precautions to ensure the safety of all people located on the work
site, including Contractor's/Installer's personnel (or that of its subcontractor(s)) performing the WORK.

REV

DATE

A
B
C

SCALE
PURPOSE

REVIEWED

APPROVED

12/30/2011

H PAREKH

B ANAND

A BISWAS

FOR INFORMATION

10/10/2012

D FERNANDES

B ANAND

A BISWAS

FOR INFORMATION

PROJECT
NUMBER

04/05/2013

N VAIDYA

B ANAND

A BISWAS

FOR CONSTRUCTION

L609000

NOTE: Drawing release record shown on Page 1.

MASTER SCHEMATIC DIAGRAM

NONE

PREPARED

6.6KV UNIT SWGR#1DA


INCOMER#1
2 X 600MW DB SUPER THERMAL
POWER PROJECT
DB POWER LIMITED

L&T - SARGENT & LUNDY LTD.


BARODA.
SHEET: 01-BBB-000001
PAGE

OF

DWG CLASS: YS00


Product of PLADES

REV.

Filename: 01-BBB-000001.VSD

DRAWING RELEASE RECORD

CABLE BASE NO:1BBB

6.6kV UNIT SWITCHGEAR#1DA

2DTBB1-62

CAB: 1CRE47
SET:
DESCP: 6.6KV SWGR#1DA
I/C#1 CL CMD

DO

DO

2DTBB1-63

X02-4

X02-8

X02-2

X02-10

X02-9

4001/5PR-2

4001/5PR-1

X02-6

4001/4PR-2

2DTBB1-60

POINT: 1BCA01GX201_XB91

CAB: 1CRE47
SET:
DESCP: 6.6KV SWGR#1DA
I/C#1 OPN CMD

X02-11

4001/4PR-1

4001/1PR-1
D

POINT: 1BCA01GX201_XB92

4001/3PR-2

X02-12

4001/3PR-1

4001/2PR-1

X02-13

4001/1PR-2

2DTBB1-61

2DTBB1-56

2DTBB1-55

2DTBB1-57

---

POINT: 1BCA01GX201_XB02

POINT: 1BCA01GX201_XB01

CAB: 1CRE47
SET:
DESCP: 6.6KV SWGR#1DA
I/C#1 OPND

CAB: 1CRE47
SET:
DESCP: 6.6KV SWGR#1DA
I/C#1 CLSD

DI

DI

2DTBB1-59

2DTBB1-58 D

POINT: 1BCA01GX201_XB03

2DTBB1-65

2DTBB1-64 D

POINT: 1BCA01GX201_XG48

CAB: 1CRE47
SET:
DESCP: 6.6KV SWGR#1DA
I/C#1 READY

CAB: 1CRE47
SET:
DESCP: 6.6KV SWGR#1DA
I/C#1 TRP

DI

2DTBB1-67

2DTBB1-66

POINT: 1BCA01GX201_XG53
CAB: 1CRE47
SET:
DESCP: 6.6KV SWGR#1DA
I/C#1 PT FUSE
FAIL

DI

DI

4001/OVERALL-S

"C"

X02-31

X02-30

X02-19

X02-18

X02-27

X02-26

6.6kV UNIT SWITCHGEAR#1DA

3DTBA2-51 D

3DTBA2-52

POINT: 1BCA01GX102_XQ05

4002/5PR-S

3DTBA2-49 D

3DTBA2-50

POINT: 1BCA01GX101_XQ05

CAB: 1CRE50
RANGE:
DESCP: 6.6KV SWGR#1DA
I/C#1 PWR

3DTBA2-57 D

3DTBA2-58

POINT: 1BCA01GX103_XQ05

CAB: 1CRE50
RANGE:
DESCP: 6.6KV SWGR#1DA
I/C#1 Y CURR

AI

4002/5PR-2

4002/5PR-1

4002/3PR-S

CAB: 1CRE50
RANGE:
DESCP: 6.6KV SWGR#1DA
I/C#1 RY VOLT

AI

AI

"C"

Contractor/Installer shall take all appropriate precautions to ensure the safety of all people located on the work
site, including Contractor's/Installer's personnel (or that of its subcontractor(s)) performing the WORK.

DRAWING RELEASE RECORD


REV

DATE

A
B
C

SCALE
PURPOSE

MASTER SCHEMATIC DIAGRAM

NONE

PREPARED

REVIEWED

APPROVED

12/30/2011

H PAREKH

B ANAND

A BISWAS

FOR INFORMATION

10/10/2012

D FERNANDES

B ANAND

A BISWAS

FOR INFORMATION

PROJECT
NUMBER

04/05/2013

N VAIDYA

B ANAND

A BISWAS

FOR CONSTRUCTION

L609000

NOTE: Drawing release record shown on Page 1.

CABLE BASE NO:1BBB

6.6KV UNIT SWGR#1DA


INCOMER#1
2 X 600MW DB SUPER THERMAL
POWER PROJECT
DB POWER LIMITED

L&T - SARGENT & LUNDY LTD.


BARODA.
SHEET: 01-BBB-000001
PAGE

OF

DWG CLASS: YS00


Product of PLADES

REV.

Filename: 01-BBB-000001.VSD

4002/1PR-S

4002/3PR-2

4002/3PR-1

4002/1PR-2

4002/1PR-1

4002/OVRALL-S

CIRCUIT TERMINATION LEGEND - PART 1


CONDUCTOR

NUMBER

LABEL

COLOR

1BBB2001
1BBB2001
1BBB2001
1BBB2001
1BBB2001

1
2
3
4
5

1BBB2002
1BBB2002
1BBB2002

FROM
TAG

TO

EQUIPMENT

COMPT

TERMN

EQUIPMENT

COMPT

TERMN

RED
YELLOW
BLUE
BLACK
GREY

1BBA01
1BBA01
1BBA01
1BBA01
1BBA01

10F
10F
10F
10F

30
31
32
33
SPARE

1BBB01
1BBB01
1BBB01
1BBB01
1BBB01

1F
1F
1F
1F

X03-1
X03-2
X03-3
X03-4
SPARE

1
2
3

RED
YELLOW
BLUE

1BBB01
1BBB01
1BBB01

1F
1F

X01-7
X01-6
SPARE

UAT#1A
UAT#1A
UAT#1A

X4-5
X4-6
SPARE

1BBB2003
1BBB2003
1BBB2003

1
2
3

RED
YELLOW
BLUE

1BBB01
1BBB01
1BBB01

1F
1F

X01-9
X01-10
SPARE

UAT#1A
UAT#1A
UAT#1A

X4-14
X4-13
SPARE

1BBB2004
1BBB2004
1BBB2004
1BBB2004
1BBB2004
1BBB2004
1BBB2004
1BBB2004
1BBB2004
1BBB2004
1BBB2004
1BBB2004
1BBB2004
1BBB2004

1
2
3
4
5
6
7
8
9
10
11
12
13
14

BLUE
YELLOW
GREY
GREY
GREY
GREY
GREY
GREY
GREY
GREY
BLUE
YELLOW
GREY
GREY

1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01

1F
1F
1F
1F
1F
1F
1F
1F
1F
1F

43
44
45
46
47
48
49
50
51
52
SPARE
SPARE
SPARE
SPARE

UAT#1A
UAT#1A
UAT#1A
UAT#1A
UAT#1A
UAT#1A
UAT#1A
UAT#1A
UAT#1A
UAT#1A
UAT#1A
UAT#1A
UAT#1A
UAT#1A

X3-11
X3-12
X3-13
X3-14
X3-15
X3-16
X3-17
X3-18
X3-19
X3-20
SPARE
SPARE
SPARE
SPARE

1BBB4001
1BBB4001
1BBB4001
1BBB4001
1BBB4001
1BBB4001
1BBB4001
1BBB4001
1BBB4001
1BBB4001
1BBB4001
1BBB4001
1BBB4001

1PR-1
1PR-2
2PR-1
2PR-2
3PR-1
3PR-2
4PR-1
4PR-2
5PR-1
5PR-2
6PR-1
6PR-2
OVERALL-S

BLUE-PK1
RED-PK1
GREY-PK1
YELOW-PK1
GREEN-PK1
BROWN-PK1
WHITE-PK1
BLACK-PK1
BLUE-PK2
RED-PK2
GREY-PK2
YELOW-PK2
SHIELD

1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01

1F
1F
1F

X02-13
X02-12
X02-11
SPARE
X02-6
X02-4
X02-8
X02-2
X02-10
X02-9
SPARE
SPARE

UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS

1CRE47
1CRE47
1CRE47

1BBB4002
1BBB4002
1BBB4002
1BBB4002

1PR-1
1PR-2
1PR-S
2PR-1

BLUE-PK1
RED-PK1
SHIELD
GREY-PK1

1BBB01
1BBB01
1BBB01
1BBB01

1F
1F
1F

UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS

1CRE50
1CRE50
1CRE50

1F
1F
1F
1F
1F
1F

1F
X02-26
X02-27
SPARE

1CRE47
1CRE47
1CRE47
1CRE47
1CRE47
1CRE47

1CRE47

Contractor/Installer shall take all appropriate precautions to ensure the safety of all people located on the work
site, including Contractor's/Installer's personnel (or that of its subcontractor(s)) performing the WORK.

DRAWING RELEASE RECORD


REV

DATE

A
B
C

SCALE
PURPOSE

3DTBA2-51
3DTBA2-52
S
SPARE

CABLE BASE NO:1BBB

MASTER SCHEMATIC DIAGRAM

NONE

PREPARED

REVIEWED

APPROVED

12/30/2011

H PAREKH

B ANAND

A BISWAS

FOR INFORMATION

10/10/2012

D FERNANDES

B ANAND

A BISWAS

FOR INFORMATION

PROJECT
NUMBER

04/05/2013

N VAIDYA

B ANAND

A BISWAS

FOR CONSTRUCTION

L609000

NOTE: Drawing release record shown on Page 1.

2DTBB1-62
2DTBB1-60
2DTBB1-61
SPARE
2DTBB1-56
2DTBB1-57
2DTBB1-59
2DTBB1-65
2DTBB1-67
2DTBB1-66
SPARE
SPARE
E

6.6KV UNIT SWGR#1DA


INCOMER#1
2 X 600MW DB SUPER THERMAL
POWER PROJECT
DB POWER LIMITED

L&T - SARGENT & LUNDY LTD.


BARODA.
SHEET: 01-BBB-000001
PAGE

OF

DWG CLASS: YS00


Product of PLADES

REV.

Filename: 01-BBB-000001.VSD

CABLE

CIRCUIT TERMINATION LEGEND - PART 2


CONDUCTOR

NUMBER

LABEL

COLOR

1BBB4002
1BBB4002
1BBB4002
1BBB4002
1BBB4002
1BBB4002
1BBB4002
1BBB4002
1BBB4002
1BBB4002
1BBB4002
1BBB4002
1BBB4002
1BBB4002
1BBB4002
1BBB4002
1BBB4002
1BBB4002
1BBB4002
1BBB4002
1BBB4002

2PR-2
2PR-S
3PR-1
3PR-2
3PR-S
4PR-1
4PR-2
4PR-S
5PR-1
5PR-2
5PR-S
6PR-1
6PR-2
6PR-S
7PR-1
7PR-2
7PR-S
8PR-1
8PR-2
8PR-S
OVRALL-S

YELOW-PK1
SHIELD
GREEN-PK1
BROWN-PK1
SHIELD
WHITE-PK1
BLACK-PK1
SHIELD
BLUE-PK2
RED-PK2
SHIELD
GREY-PK2
YELOW-PK2
SHIELD
GREEN-PK2
BROWN-PK2
SHIELD
WHITE-PK2
BLACK-PK2
SHIELD
SHIELD

JUMPER
JUMPER
JUMPER
JUMPER
JUMPER
JUMPER

01
02
03
04
05
06

FROM
TAG

EQUIPMENT
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01
1BBB01

COMPT

1F
1F
1F

1F
1F
1F

TO
TERMN

EQUIPMENT

SPARE
SPARE
X02-18
X02-19

UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS
UNIT#1 DDCMIS

SPARE
SPARE
SPARE
X02-30
X02-31
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE

1F

UAT#1A
UAT#1A
UAT#1A
UAT#1A
UAT#1A
UAT#1A

X4-5
X4-6
X4-7
X4-8
X4-9
X4-10

COMPT

REV

DATE

A
B
C

SCALE
PURPOSE

1CRE50
1CRE50
1CRE50

1CRE50

UAT#1A
UAT#1A
UAT#1A
UAT#1A
UAT#1A
UAT#1A

X4-7
X4-8
X4-9
X4-10
X4-11
X4-12

CABLE BASE NO:1BBB

MASTER SCHEMATIC DIAGRAM

NONE

PREPARED

REVIEWED

APPROVED

12/30/2011

H PAREKH

B ANAND

A BISWAS

FOR INFORMATION

10/10/2012

D FERNANDES

B ANAND

A BISWAS

FOR INFORMATION

PROJECT
NUMBER

04/05/2013

N VAIDYA

B ANAND

A BISWAS

FOR CONSTRUCTION

L609000

NOTE: Drawing release record shown on Page 1.

SPARE
SPARE
3DTBA2-49
3DTBA2-50
S
SPARE
SPARE
SPARE
3DTBA2-57
3DTBA2-58
S
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
E

1CRE50
1CRE50
1CRE50

Contractor/Installer shall take all appropriate precautions to ensure the safety of all people located on the work
site, including Contractor's/Installer's personnel (or that of its subcontractor(s)) performing the WORK.

DRAWING RELEASE RECORD

TERMN

6.6KV UNIT SWGR#1DA


INCOMER#1
2 X 600MW DB SUPER THERMAL
POWER PROJECT
DB POWER LIMITED

L&T - SARGENT & LUNDY LTD.


BARODA.
SHEET: 01-BBB-000001
PAGE

OF

DWG CLASS: YS00


Product of PLADES

REV.

Filename: 01-BBB-000001.VSD

CABLE