Você está na página 1de 1

PAGE 1 / 1

NAME:
PLACE AND DATE OF
INSPECTION:

CONTRA INCENDIO (COINCA) C.A

CERTIFICATE N LAB0115-15

COMPRESSOR DESCRIPTION

BAUER HIGH PRESSURE BREATHING AIR COMPRESSOR

MODEL / SERIAL N

K42-F3/460 V / 79273

AIR GRADE

D (OSHA BREATHING AIR)

SAMPLE PRESSURE

2000 PSI

PUNTA CARDON, MARZO 30, 2015

ANALISYS METHOD
o MSA BREATHING AIR TEST KIT PN 491932 / SN 025570 USING MSA AUER OIL-HP TUBES, CO2-HP TUBES 10-2000
PPM, CO TUBES 10-200 PPM, AND H2O-HP TUBES 5-70 PPM EXPIRING ON 04/2016
o OXYGEN ANALYSIS WITH RKI EAGLE MULTIGAS MONITOR SN E068031 / LAST CAL: 02/2015

COMPOUND

STANDARD

RESULTS

TOTAL HYDROCARBONS

< 25 PPM

0 PPM

OXYGEN

(19.5 23.5) %

20,9 % VOL +/- 0,5 % MOL

CARBON MONOXIDE

< 10 PPM

0 PPM

CARBON DIOXIDE

< 1000 PPM

200 PPM

< 0.5 mg / m

OIL

< 5 mg / m

HUMIDITY (H2O VAPORS)

< 67 PPM

40 +/- 0,5 PPM

NITROGEN

NONE

BALANCE

ODOR

NONE

NONE

REMARKS:

EXPANDED UNCERTAINTY FOR K=2

STANDARD FOR UNCERTAINTY IS NOT CONSIDERED FOR CARBON MONOXIDE ANALYSIS.


RECOMMENDATIONS:

TO AVOID EXCESSIVE HUMIDITY ON BREATHING AIR FLOW, DRAIN THE COMPRESSOR MANUALLY BY THE
INTER-STAGE OIL AND WATER SEPARATOR VALVES EVERY TEN MINUTES WHILE REFILLING.

REPLACE THE PURIFICATION CARTRIDGE EVERY 24-HOUR MAX. IN TROPICAL CLIMATE.

THIS CERTIFICATED IS VALID FOR SIX MONTHS SINCE THE ISSUANCE DATE

________________________________

SIGNATURE AND STAMP

Você também pode gostar