125.00
125.00
13.80
0.90
33.50
25 C
1.20 m
120.00 C - cm/W
MVA
0.20 sg
Kw
kVA
kV
35 mm2
190 Amp
N2XSY
20.00
m
25.00
80.00
frecuencia de la red
C
Hz
Enterrado SI o NO
SI
Datos del Transformador aprox.( 2 Un 1000 KV )
Alto
230.00
Ancho
230.00
Profundidad
125.00
Peso
2,250.00
cm
cm
cm
kg
1.09 fr
0.90 ft
Profundidad de Instalacin:
0.90 fp
fr x f t x fp
Feq =
Feq =
0.88
Inominal =
P
3 x VxCos
5.81
In =
Icable/Feq
215.20
7.26
Pgina 1
CALCULO
CALCULO POR CAIDA DE TENSION
V =
V =
V % =
3 x L x In x (rCos +xSen)
1,000.00
0.09
V
0.001%
MVA
kV
1.40
kA
0,143xS
tact
Ikm =
kA
11.19
kA
>
Icc
11.19
>
1.40
CUMPLE LA CONDICION
12 x n-transformador
0,1 Seg.
,,,,,,, (a)
20 x n-transformador
2 Seg.
In-t=
Tenemos que:
,,,,,,, (b)
Pt
3 x V
Para un transformador. =
Vn (tensin de servicio)=
200.00
13.80
kVA
KV
Trafo de:
200.00
160.00
160.00
De (b) tenemos:
20 *In-t =
20 *In-t =
12*In-t
100.41
80.32
80.32
20*In-t
167.34
133.87
133.87
167.34
133.87
A
A
Dimensionamiento Fusible
( Para el transformador)
( Para el transformador)
(Seccionador)
Para el Transformador
Para el Seccionador
Con estos datos vamos al Grfico y escogemos In del fusible. (FUSIBLES MESA )
16 A
PARA EL TRANSFORMADOR DE 160 kVA
16 A
PARA EL TRANSFORMADOR DE 160 kVA
40 A
PARA EL TRANSFORMADOR DE 200 KVA
Pgina 2
CALCULO
12.55
40.00
Iccp=
Icc =
S=
Para el Seccionador :
Pot S.E.
f=
In = P/(V3 x 10.0KV)
Ise =
If =
If =
200.00 kVA
1.50 xIn-t
8.37
8.37
1,5*In-t
K
Icc
t
dt
12.55
40.00
A
800.00 kVA
t+dt =
40.00
63.00
31.50
A
A
A
Pgina 3
BARRAS
NOMINAL
DIMENSIN AREA
(mm)
2X15
2X20
3X15
3X20
3X25
3X30
3X40
3X50
3X100
4X20
4X25
4X30
4X40
4X50
5X20
5X25
5X30
5X35
5X40
5X50
5X60
5X80
5X100
6X30
6X40
6X50
6X60
6X80
6X100
8X40
8X50
8X60
8X80
8X100
10X40
10X50
10X60
10X80
10X100
CAPACIDAD DE CARGA
MODULO RESISTENTE
y
Wy
AMP. CORRIENTE
Wx
ALTERNA
en x
x
en
PESO
BSQUEDA
2
2
3
3
3
3
3
3
3
4
4
4
4
4
5
5
5
5
5
5
5
5
5
6
6
6
6
6
6
8
8
8
8
8
10
10
10
10
10
15
20
15
20
25
30
40
50
100
20
25
30
40
50
20
25
30
35
40
50
60
80
100
30
40
50
60
80
100
40
50
60
80
100
40
50
60
80
100
(mm2)
30
40
45
60
75
90
120
150
300
80
100
120
160
200
100
125
150
175
200
250
300
400
500
180
240
300
360
480
600
320
400
480
640
800
400
500
600
800
1000
kg/m
Lb/m
0.267
0.356
0.401
0.534
0.668
0.801
1.068
1.335
2.670
0.712
0.890
1.068
1.424
1.780
0.890
1.113
1.335
1.558
1.780
2.225
2.670
3.560
4.450
1.602
2.136
2.670
3.204
4.272
5.340
2.848
3.560
4.272
5.696
7.120
3.560
4.450
5.340
7.120
8.900
0.181
0.241
0.272
0.362
0.453
0.543
0.724
0.905
1.810
0.483
0.603
0.724
0.965
1.207
0.603
0.754
0.905
1.056
1.207
1.508
1.810
2.413
3.017
1.086
1.448
1.810
2.172
2.896
3.620
1.931
2.413
2.896
3.861
4.827
2.413
3.017
3.620
4.827
6.033
Desnudo
155
185
170
220
270
315
420
488
912
261
309
357
453
549
290
350
400
449
520
630
750
950
1,000
433
551
669
787
1,022
1,258
650
789
929
1,209
1,488
750
920
1,100
1,400
1,700
mm
6
8
10
12
14
16
18
20
22
PULGADAS
0.236 1/4"
0.315 5/16"
0.394 3/8"
0.472 1/2"
0.551 9/16"
0.630 5/6"
0.709 23/32"
0.787 3/4"
0.866 7/8"
kg/m
0.252
0.447
0.699
1.007
1.370
1.789
2.265
2.796
3.383
CAPACIDAD
(A)
125
160
250
300
440
480
600
670
750
Pgina 4
Pintado
178
205
185
245
300
350
480
564
1083
283
340
398
512
627
325
385
450
501
600
700
825
1,060
1,310
478
615
752
889
1,187
1,437
718
877
1,036
1,355
1,673
835
1,025
1,200
1,540
1,880
cm3
cm3
0.075
0.133
0.113
0.200
0.313
0.450
0.800
1.250
5.000
0.267
0.417
0.600
1.067
1.667
0.333
0.521
0.750
1.021
1.333
2.083
3.000
5.333
8.333
0.900
1.600
2.500
3.600
6.400
10.000
2.133
3.333
4.800
8.533
13.333
2.667
4.167
6.000
10.667
16.667
y
0.010
0.013
0.023
0.030
0.038
0.045
0.060
0.075
0.150
0.053
0.067
0.080
0.107
0.133
0.083
0.104
0.125
0.146
0.167
0.208
0.250
0.333
0.417
0.180
0.240
0.300
0.360
0.480
0.600
0.427
0.533
0.640
0.853
1.067
0.667
0.833
1.000
1.333
1.667
CABLES
V=
DE
8.7
15
kV
V=
PARMETROS FSICOS
SECCIN
NOMINAL
N DE HILOS
(mm2)
25
35
50
70
95
120
150
185
240
300
400
500
7
7
19
19
19
37
37
37
61
61
61
61
DIMETRO
CONDUCTOR
ESPESOR
DIAM. EXT.
PESO
SECCIN
NOMINAL
(mm)
(mm)
Kg/Km
(mm2)
6.30
7.40
8.70
10.50
12.30
13.90
15.40
17.20
19.80
22.20
25.10
28.20
4.50
4.50
4.50
4.50
4.50
4.50
4.50
4.50
4.50
4.50
4.50
4.50
1.80
1.80
1.80
1.80
1.80
2.00
2.00
2.00
2.20
2.20
2.40
2.40
21.40
22.60
23.90
25.60
27.50
29.50
31.00
32.80
35.80
38.10
41.40
44.50
687
810
962
1,207
1,503
1,804
2,100
2,497
3,135
3,772
4,672
5,695
18
30
N DE HILOS
kV
DIMETRO
CONDUCTOR
(mm)
50
70
95
120
150
185
240
300
400
500
19
19
19
37
37
37
61
61
61
61
237.780135
ESPESOR
AISL (mm) CHAQ.(mm)
8.70
10.50
12.30
13.90
15.40
17.20
19.80
22.20
25.10
28.20
8.00
8.00
8.00
8.00
8.00
8.00
8.00
8.00
8.00
8.00
1.80
1.80
1.80
2.00
2.00
2.00
2.20
2.20
2.40
2.40
DIAM. EXT.
PESO
(mm)
Kg/Km
30.90
32.60
34.50
36.50
38.00
39.80
42.80
45.10
48.40
51.50
1,303
1,566
1,882
2,204
2,516
2,932
3,602
4,263
5,199
6,253
PARMETROS ELCTRICOS
RESISTENCIA
REACTANCIA
AC 90C
CAPACIDAD
CAPACIDAD
ENTERRADO (20 C)
AIRE (30 C)
SECCIN
RESIST. DC
NOMINAL
20 C
(A)
(B)
(A)
(B)
(A)
(B)
(A)
mm2
ohm/Km
ohm/Km
ohm/Km
ohm/Km
ohm/Km
Amp.
Amp.
Amp.
0.7125
0.5138
0.3794
0.2625
0.1893
0.1498
0.1219
0.0972
0.0740
0.0590
0.0461
0.0366
PARMETROS FSICOS
PARMETROS ELCTRICOS
25
35
50
70
95
120
150
185
240
300
400
500
DE
0.928
0.669
0.495
0.345
0.252
0.202
0.175
0.145
0.116
0.093
0.076
0.061
0.909
0.655
0.484
0.335
0.242
0.192
0.156
0.126
0.097
0.078
0.073
0.071
0.2930
0.2814
0.2667
0.2539
0.2427
0.2339
0.2270
0.2195
0.2104
0.2031
0.1956
0.1884
0.1689
0.1604
0.1491
0.1405
0.1335
0.1286
0.1246
0.1204
0.1160
0.1123
0.1092
0.1058
180
212
249
303
359
405
443
495
566
630
682
749
157
188
221
271
323
366
407
460
531
597
669
745
(A)
(B)
192
232
278
346
419
482
539
613
717
812
903
1008
RESISTENCIA
CD-7-013
CAPACIDAD
(B)
NOMINAL
20 C
(A)
(B)
(A)
(B)
(A)
(B)
(A)
(B)
Amp.
mm2
ohm/Km
ohm/Km
ohm/Km
ohm/Km
ohm/Km
Amp.
Amp.
Amp.
Amp.
164
197
236
294
356
410
463
529
624
712
817
924
50
70
95
120
150
185
240
300
400
500
0.3794
0.2625
0.1893
0.1498
0.1219
0.0972
0.074
0.059
0.0461
0.0366
AC 90C
CAPACIDAD
RESIST. DC
0.495
0.345
0.252
0.202
0.175
0.145
0.116
0.093
0.076
0.061
ENTERRADO (20 C)
0.484
0.335
0.242
0.192
0.156
0.126
0.097
0.078
0.073
0.071
0.2709
0.2580
0.2468
0.2378
0.2309
0.2233
0.2141
0.2067
0.1991
0.1918
3 CABLES UNIPOLARES EN FORMACIN TRIPOLAR, TENDIDOS PARALELOS CON UNA SEPARACIN >= 7 cm
3 CABLES UNIPOLARES EN FORMACIN TRIPOLAR, TENDIDOS, AGRUPADOS EN TRINGULO, EN CONTACTO
FACTORES DE CORRECCION
POR TEMPERATURA DEL SUELO
REACTANCIA
SECCIN
CD-9-012
Pgina 5
0.1684
0.1587
0.1505
0.1446
0.1399
0.1349
0.1294
0.1249
0.1209
0.1167
251
306
363
410
449
503
576
641
697
768
226
276
329
373
415
468
541
608
684
762
AIRE (30 C)
279
348
421
483
540
615
718
812
904
1011
241
299
362
416
469
536
630
717
823
929
CABLES
TEMP. ADMISIBLE
DEL CONDUCTOR C
90
10
1.11
15
1.08
20
1.04
SECCION DEL
CONDUCTOR DE mm2
25 a 240
30
0.96
35
0.91
40
0.87
45
0.83
CD-7-013
70
1.33
80
1.26
100
1.17
120
1.1
150
1
200
0.89
250
0.81
300
0.75
(INDECO)
PROF. (m)
50
0.50
0.60
0.70
0.80
1.00
1.10
1.20
1.50
25
1
1.01
1.00
0.99
0.97
0.95
0.94
0.93
----
300
1.02
1.01
1.00
0.98
0.96
0.96
0.95
0.94
>300
1.03
1.02
1.00
0.97
0.95
0.95
0.94
0.92
Pgina 6
CD-9-012
70
1.34
80
1.27
100
1.17
120
1.09
150
1
200
0.88
250
0.8
300
0.74