Tabela de corrente nominal, em Ampéres, de um motor de indugdo padrao sob corrente
alternada de 60Hz.
6 48 22 : : :
4 58 2.9 = 5 .
413 72 36 - : -
42 98 49 2,0 42 1,0
34 38 69 2.8 16 14
1 16 5,0 35 2A 18
i 20 10,0 5,0 29 25
2 24,0 12,0 65 38 33
34,0 17,0 9,0 5,2 45
5 56,0 28,0 15,0 8,7 75
7 80,0 40,0 22,0 13,0 11,0
10 100,0 50,0 27,0 16,0 14,0
15 40,0 23,0 20,0
20 52,0 30,0 26,0
25 64,0 37,0 32,0
30 78,0 45,0 39,0
40 104,0 60,0 52,0
50 125,0 73,0 63,0
60 150,0 87,0 75,0
75 185,0 108,0 93,0
100 246,0 143,0 123,0
125 310,0 180,0 155,0
150 360,0 209,0 180,0
200 480,0 278,0 240,0
‘alors aca esto baseados nas tabla do National Bail Code (Elo de 1959)
Nota: A norme tase NBRSA10 etablee que
(0 eanautores do cata terminal para siento Ge un Unico motor deve ter uma capaciade de corte ual 2 125% a
‘erent nomin! do mess.
(Or constorer que aimertam dols ou mals motores devem ter uma capaci
‘ovenes ominas de oso os motores, mas 25% da carene do metor de moi poten
enugio oe corrnte igual 8 some as