Datos:
a) Lnea San Gabn Mazuco
Corriendo Flujo de Carga
= 0.06
Corriendo Falla Trifsica
1% 3 = 3.705
99% 3 = 1.426
Corriendo Falla Monofsica
1% 1 = 4.418
99% 1 = 1.183
b) Lnea Mazuco Pto Maldonado
Corriendo Flujo de Carga
= 0.05
Corriendo Falla Trifsica
1% 3 = 1.397
99% 3 = 0.584
1% 1 = 1.161
99% 1 = 0.762
Pregunta 1
a) Ajuste del Rel de Sobrecorriente de fases
50
Verificar:
1% 3
1.25
99% 3
3.705
= 2.598 1.25
1.426
50 = 1.299% 3
50 = 1.2(1.426) = 1.7112
51
i)
ii)
iii)
0.14
0.02
(99% 3 )
1
(
)
Curva Caracterstica
50N
Verificar:
1% 1
1.25
99% 1
4.418
= 3.734 1.25
1.183
50 = 1.299% 1
50 = 1.2(1.183) = 1.4196
51N
i)
Curva: IEC-Inverse (Transmisin)
ii)
= [0.1 0.2]1
= 0.2(0.5) = 0.1
iii)
= = 0.4 = (0.1 + )
Sabemos:
=
Reemplazando:
Dial = 0.144
Curva Caracterstica
0.14
0.02
(99% 1 )
1
(
)
Sabemos:
= 38.937 < 72.816
L = 68.85 Km
TC: 500 A/1 A
RTC = 500
TT: 138 KV/ 100V
RTT= 1380
=
1380
=
= 2.76
500
Zona 1
1 = 0.8 =
0.8(38.937)
= 11.286 .
2.76
1 = 0
Zona 2
2 = 1.2 =
1.2(38.937)
= 16.929 .
2.76
2 = 0.4
Zona 1
Zona 2
t2
Pregunta 2
51
iv)
v)
vi)
Curva Caracterstica
0.14
0.02
(99% 3 )
1
(
)
50N
Verificar:
1% 1
1.25
99% 1
1.161
= 1.5236 1.25
0.762
50 = 1.299% 1
50 = 1.2(0.762) = 0.9144
51N
iv)
Curva: IEC-Inverse (Transmisin)
v)
= [0.1 0.2]1
= 0.2(0.5) = 0.1
vi)
= = 0.4 = (0.1 + )
Sabemos:
=
Reemplazando:
Dial = 0.118
Curva Caracterstica
0.14
0.02
(99% 1 )
1
(
)
Sabemos:
= 89.3566 < 71.2668
L = 155.73 Km
TC: 500 A/1 A
RTC = 500
TT: 138 KV/ 100V
RTT= 1380
=
1380
=
= 2.76
500
Zona 1
1 = 0.8 =
0.8(89.3566)
= 25.9 .
2.76
1 = 0
Zona 2
2 = 1.2 =
1.2(89.3566)
= 38.85 .
2.76
2 = 0.4
Zona 1
Zona 2
t2
Observaciones:
a) Lnea San Gabn Mazuco
Como se puede observar a continuacin hemos utilizado la Base de Datos del COES del ao
pasado, debido a que la que actualmente se encuentra disponible para el escenario del
AVMAX2016 no nos permite realizar un flujo de carga.