Você está na página 1de 1

GovernorHYGOV

Governor HYGOV
Hydro Turbine-Governor Model

Pref

db1

1 + sTn
1 + sTnp

G MAX
+

1
1+ sTf

1 + sTr
rTr s

1
1+ sTg

G MIN

PG V

rate limit - Velm

D turb

db2

GV

N GV
G Vg

PGV

q/PGV

+
Hdam=1

1
sTW

qNL

At

Pmech

States
1 - Filter Output
2 - Desired Gate
3 - Gate
4 - Turbine Flow

Model supported by PSSE and PSLF


Rperm shown as R, Rtemp shown as r
GV0, PGV0...GV5, PGV5 are the x,y coordinates of N GV block
Ttur, Tn, Tnp, db1, Eps, db2, Bgv0...Bgv5, Bmax, Tblade not implemented in Simulator