Você está na página 1de 1

Amps CARAL MT (Nom. kV=20, Plot Ref.

kV=20)
.5

10

30

50

100

300

500

1K

3K

5K

1K

F0

T1
FLA

500

10K
1K

500

1757.153 Amps

100/5

I>

300

CB T1

300

R2 - CARAL

50/1

F0
CB 2

Chance
Fuse Link (K)
Fast 0 kV
80A

100

50

100

CARAL MT
20 kV

50

F1
30

30

F1

T1

10

10

Merlin Gerin
Sepam 1000
CT Ratio 100:5
Extremely Inverse
Pickup = 0.75 (0.3 - 2.4 xCT Sec)
Time Dial = 0.4
3x = 4.95 s, 5x = 1.65 s, 8x = 0.629 s
Inst = 4.1 (1 - 24 xCT Sec)
Time Delay = 0.05 s

5
3

CB T1

CARAL BT

0.44 kV

T1

.5

.5

.3

.3

T1
Inrush

.1

.1
F0 - 3P

.05

.05

R2 - CARAL - 3P
1.766kA @ 20kV
(Asym)

.03

.03

F1 - 3P
1.766kA @ 20kV
(Asym)

CB T1 - 3P
36.151kA @ 0.46kV
(Asym)

.01
.5

10

30

50

100

300

500

1K

Amps CARAL MT (Nom. kV=20, Plot Ref. kV=20)


BARENTS

5K

Date:
SN:
Rev:
Fault:

19-08-2013
ENERGIAING
Base
Phase

.01
10K

ETAP Star 11.0.0C

PESQUERA CARAL

SOBRECORRIENTE FASE T1

Project:
Location:
Contract:
Engineer:
Filename: C:\ETAP 1100\CARAL\CARAL.OTI

3K

Seconds

Seconds

R2 - CARAL - P

Você também pode gostar