VA TECH Transmission & Distribution

Overcurrent and Earth Fault Protection


Cc/Hydro_Prs/Interne RS.ppt

PEEBLES

REYROLLE

VA TECH Transmission & Distribution

ARGUS 1-6 - Protection Functions

Cc/Hydro_Prs/Interne RS.ppt

PEEBLES

REYROLLE

VA TECH Transmission & Distribution


Phase and Earth Fault Characteristics
TIME

4 Independent Stages
1 x transient free LOWSET, 0.1 - 52.5 In, 0 - 20 sec
1 x SHAPED, 0.1 - 2.5In, T.M. 0.025 - 1.6
NI, EI, VI, LTI, DTL
2 x transient free HIGHSET , 0.1 - 52.5 In, 0 - 20 sec
SHAPED

HS1

24ms

LS

HS2
CURRENT

Cc/Hydro_Prs/Interne RS.ppt

PEEBLES

REYROLLE

VA TECH Transmission & Distribution


Grading with Electro-Mechanical Relays
R3

R2

Argus (Inst. Reset)


TRIP

% of Algorithm

Disc Travel

Electro-mechanical Relay

FAULT
R1 Clashing conductors or re-sealing cable

Time

Argus (DTL Reset)


TRIP

Time

Loss of grading /discrimination may occur:


If R2 Electromechanical & R1 Inst. reset or if R2 DTL reset and R1 electromechanical
Some compromise may be necessary where more than two relay points are in series

Cc/Hydro_Prs/Interne RS.ppt

PEEBLES

REYROLLE

VA TECH Transmission & Distribution


C.B. Failure Protection

F a u lt tr ig g e r
o u tp u t re la y
o p e ra te d

T im e D e la y > C B O p e r a tin g T im e +
S a fe ty M a r g in

&

DTL 1
0 - 20s

DTL 2
0 - 20s

P r o te c tio n
a lg o r ith m
o p e ra te d
R L1

O u tp u t re la y s a rra n g e d to trip
u p s tr e a m c ir c u it b r e a k e r

RL1

RL11

R L11

Cc/Hydro_Prs/Interne RS.ppt

PEEBLES

REYROLLE

VA TECH Transmission & Distribution


Trip circuit supervision - H6 Scheme
E x te r n a l re s is to r = 2 K 7 O h m s
1 1 0 V s y s t e m 5 0 V S t a t u s In p u t

Recom m ended
S .I. S e t t in g s :

ARG US
+

Fuse

52a

2 0 m s p .u .
4 0 0 m s d .o .
O /P 1 - 3 (N C c o n ta c t)

L in k

T R IP
T R IP C C T F A IL

C .B .

If t r ip c ir c u it n o t h e a lt h y r e la y
d is p la y s " T R IP C C T F A IL "

T C S c a n b e s e t fo r e a c h s ta tu s in p u t a n d
th e re fo re c a n b e u s e d to m o n ito r:
1 s t a n d 2 n d trip c o ils o r ,
a ll p h a s e s o f p h a s e s e g re g a te d C B

52a

52b

2K7

T R IP
C O IL

R L1

R L11

R e m o te A la r m

Cc/Hydro_Prs/Interne RS.ppt

PEEBLES

REYROLLE

VA TECH Transmission & Distribution


Status Inputs
Initiate output relays
Time delayed pick-up
Time delayed drop-off
Inhibit characteristic (except starters)
Change settings groups
Reset LEDs and Output Contacts
Trigger Waveform Storage

Opto-isolated inputs

Synchronise Clock

Cc/Hydro_Prs/Interne RS.ppt

PEEBLES

REYROLLE

VA TECH Transmission & Distribution


Argus protection summary
Wide range of IDMTL curves and DTL
Three independent high set/low set characteristics
Sensitive/restricted earth fault
Circuit breaker fail protection
Delayed or instantaneous reset
Low AC and DC burdens
True RMS measurement
Cc/Hydro_Prs/Interne RS.ppt

Combined 1A and 5A current inputs

PEEBLES

REYROLLE

VA TECH Transmission & Distribution

Argus Applications

Cc/Hydro_Prs/Interne RS.ppt

PEEBLES

REYROLLE

VA TECH Transmission & Distribution


Blocking scheme
logic

HS1
50ms
DTL

Power Flow

HS1
50ms
DTL

Block

Inst. LS

Block

Inst. LS

Metallic connection required between relaying points


IDMT characteristic of relays toward source have a supplementary HS1 tripping
characteristic with a DTL of 50ms
Inst. LS output of downstream relay arranged to block upstream HS1 characteristic
If metallic link is lost graded IDMT protection is not affected
Cc/Hydro_Prs/Interne RS.ppt

10

PEEBLES

REYROLLE

VA TECH Transmission & Distribution


Busbar Protection
Settings
SI1

INHIBIT LS
FWD. P/F BLOCK SETTING

938A
250A

2400A, 0.15s
320A, 0.15s

190A
30A

938A
250A

SI1

2400A, 0.15s
320A, 0.15s

2400A, 0.15s
320A, 0.15s

BLOCK SIGNAL

780A

P/F LS TRIP SETTING


E/F LS TRIP SETTING

P/F BLOCK
E/F BLOCK

SI1

780A
120A

560A
80A

480A
80A

480A
80A

240A
40A

938A
250A

84A
12A

938A
250A

Output from RL1 P/F & E/F Starters, Instantaneous operation


CAPACITOR 2

GEMFACTOR 2

PAY OFF
REEL

STAND 1

STAND 2

STAND 3

STAND 4

STAND 5

TENSION
REEL

CAPACITOR 1

GEMFACTOR 1

Cc/Hydro_Prs/Interne RS.ppt

11

PEEBLES

REYROLLE

VA TECH Transmission & Distribution


Alternative setting groups

Start
generators
Trip non-essential loads
Local
Generation

Industrial system draws power from grid system during


normal operation

Select alternate settings group

Argus relays normally use settings group 1


On loss of mains:
Local generation switched in.
Non essential loads tripped
Argus relays on essential circuits switched to settings
group 2 to reflect new load and fault currents
RADIAL SUBSTATION

Non-essential
loads
Cc/Hydro_Prs/Interne RS.ppt

12

PEEBLES

REYROLLE

VA TECH Transmission & Distribution


Applications Summary
Blocking schemes for faster clearance

Busbar zone schemes for low cost busbar protection

Alternative protection setting groups

Status inputs can be time lagged for pick-up and/or drop-off and operate
output contact(s)

Cc/Hydro_Prs/Interne RS.ppt

13

PEEBLES

REYROLLE

VA TECH Transmission & Distribution


Argus family of relays
Argus 2 - directional overcurrent and earth fault with bi-directional elements
Argus 3/4 - integrated overcurrent, earth fault & autoreclose 4 shot
autoreclose fully programmable with different sequences for phase fault, earth
fault and from an external signal
Argus 5/6 - directional overcurrent and earth fault with autoreclose
Argus 7 - check synchronising relay with independent settings for check and
system synchronising, dead line/bus switching and manual close guard
feature
Argus 8 - Under/overvoltage Under/overfrequency relay

Cc/Hydro_Prs/Interne RS.ppt

14

PEEBLES

REYROLLE

VA TECH Transmission & Distribution


Argus 2
C .A .
+900

Dual Directional Elements


Independent FWD. And REV. Settings
Independent control for each characteristic
Separate outputs for FWD. And REV.
20ms operating time for directional detection

F o rw a rd z o n e
le a d in g b o u n d a ry
+ 8 7 .5 0

FW D.
ZO NE

REV.
ZO NE

Directional P/F
300 or 450 deg. (I w.r.t. V)

C h a r a c te ris tic
A n g le (C .A .)

Directional E/F
00, -150, -450,-650, -900 (I w.r.t. V)
Directional SEF
-900
C .A .
+900

2 out of 3 Gate Overcurrent Logic

F o rw a rd z o n e
le a d in g b o u n d a ry
+ 8 7 .5 0

Cc/Hydro_Prs/Interne RS.ppt

15

PEEBLES

REYROLLE

VA TECH Transmission & Distribution


Argus 4/6
4 pole relay with auto-reclose
1 to 4 shots (instantaneous or IDMT), 5th is Lockout IDMT
A.R. sequences for P/F, E/F, SEF, External
Supports sequence reclosing
Frequent operations counter
Trip and Lockout (Supervisory)
Hot line Working
CB Open/Closed Status Indication
9 Status Inputs, 7 Output Contacts
User Configurable Alarm Inputs
13 alphanumeric characters
R6 / R8 Case

Cc/Hydro_Prs/Interne RS.ppt

16

PEEBLES

REYROLLE

VA TECH Transmission & Distribution


Argus 4/6 - Sequence Co-ordinated Reclosing

Reduces supply interruption to local


customers on occurrence of remote fault

2 Inst +
Time Lag

Local
Consumers
Pole Mounted
Recloser

PMR

2 Inst + Graded
Time Lag

2 'Delayed' Inst +
Graded Time Lag

Argus

Reset
before trip

Argus
Count
Argus 4/6 configured for sequence co-ordination
Consumers
Cc/Hydro_Prs/Interne RS.ppt

17

PEEBLES

REYROLLE

VA TECH Transmission & Distribution


Argus 7 - Key Features
Check and system synchronising relay for 50Hz or 60Hz
systems
Independent phase angle (Line and Bus Voltages), slip
frequency (Line and Bus Freq) and slip timer settings
Independent undervoltage blocking and differential
voltage blocking (Line and Bus)
Split system detection with split timer (90-170 Deg)
Options for dead line and/or dead bus charging (Sync
bypass logic)
Integrated manual close guard function
Line & bus voltage trimming

Cc/Hydro_Prs/Interne RS.ppt

18

PEEBLES

REYROLLE

VA TECH Transmission & Distribution


Argus 7 - Close guard feature
Prevents an operator from initiating a manual circuit breaker close before the check
synchronising relay operates
Removes the need for additional relays e.g. B66

Cc/Hydro_Prs/Interne RS.ppt

19

PEEBLES

REYROLLE

VA TECH Transmission & Distribution


Argus 8 product variants
AG8 - 104-112
Three phase 4 stage under/overvoltage + negative sequence overvoltage
AG8 - 204-212
Three phase 4 stage under/overvoltage + negative sequence overvoltage + 4 stage
under/overfrequency
AG8 - 101-103
Single phase 4 stage under/overvoltage + neutral voltage displacement
AG8 - 201-203
Single phase 4 stage under/overvoltage + neutral voltage displacement + 4 stage
under/overfrequency

Cc/Hydro_Prs/Interne RS.ppt

20

PEEBLES

REYROLLE

VA TECH Transmission & Distribution

ARGUS Interface and Monitoring

Cc/Hydro_Prs/Interne RS.ppt

21

PEEBLES

REYROLLE

VA TECH Transmission & Distribution


Operator interface
Alpha Numeric LCD Display
2 rows, 16 characters
5 Pushbuttons
and
available with cover on:
View menu
Reset fault data display
Reset latched output relays
Reset TRIP LED
3 LEDs
Healthy
Trip
Start

Cc/Hydro_Prs/Interne RS.ppt

22

PEEBLES

REYROLLE

VA TECH Transmission & Distribution


Menu Structure

RELAY
ID E N T IF IE R

LED TEST

FAULT
IN D IC A T IO N S

S E T T IN G S
D IS P L A Y
M O DE

IN S T R U M E N T S
D IS P L A Y
M O DE

FAULT
DATA

SYSTEM
C O N F IG U R A T IO N
P R O T E C T IO N

D ir e c t io n

A u t o - R e c lo s e
R E Y D IS P
E V O L U T IO N

O UTPUT
RELAYS
STATUS
IN P U T S
CO M M S
IN T E R F A C E
DATA
STO RAG E
CB
M A IN T E N A N C E

Cc/Hydro_Prs/Interne RS.ppt

23

PEEBLES

REYROLLE

VA TECH Transmission & Distribution


Argus 1 - Instrumentation and Monitoring
P r im a r y C u r r e n ts
U s e r in p u t o f C T r a tio s r e q u ir e d

A = 2 3 3 .4 B = 2 3 5 .6
C = 2 3 4 .0 E = 0 0 0 .7

S e c o n d a ry C u rre n ts

a = 0 0 .5 3 b = 0 0 .5 3
c = 0 0 .5 3 e = 0 0 .0 0

O u tp u t R e la y s
1 = r e la y e n e r g is e d
S t a t u s In p u t s
1 = r e la y e n e r g is e d
T r ip C o u n te r
I2 S u m m a t io n
P o le w ith h ig h e s t lo a d

R e la y S ta tu s
11_1_1_
S ta tu s In p u ts
1_ _ _ _

C a n b e s e t a s d e fa u lt b y
s c r o llin g to d e s ir e d m e te r
s c r e e n a n d p r e s s in g E N T E R

T r ip C o u n t = 5

S u m o f I2
0 2 3 1 7 8 (M A )2

Cc/Hydro_Prs/Interne RS.ppt

24

PEEBLES

REYROLLE

VA TECH Transmission & Distribution


The Argus Fault Recorder

T r ip L E D

F iv e fa u lt r e c o r d s a v a ila b le fr o m r e la y fa c ia

0 2 /2 2 1 5 :2 7 :1 7
T r ip A

TEST/
R ESET

FAULT 1
F a u lt d a ta > > >

D a ta s to r a g e tr ig g e r e d b y :
FAULT 5
F a u lt d a ta > > >

O p e r a tio n o f p r o te c tio n
+
O u tp u t r e la y s
W a v e fo r m tr ig g e r
e n a b le d

F iv e w a v e fo r m r e c o r d s
a v a ila b le o v e r d a ta c o m m s lin k

1 0 0 E v e n t R e c o r d s a v a ila b le o v e r d a ta c o m m s lin k
1 5 :2 7 :1 7 .3 8 5 , 2 2 /0 2 /0 0

Rey

R a is e d

A -H S 2 S ta rte r

1 5 :2 7 :1 7 .5 0 7 , 2 2 /0 2 /0 0

Rey
IE C

R a is e d
R a is e d

A -H S 2 T r ip
A -g e n e r a l tr ip

1 5 :2 7 :1 7 .5 1 0 , 2 2 /0 2 /0 0

Rey

R a is e d

W a v e fo rm s to re d

1 5 :2 7 :1 7 .6 0 0 , 2 2 /0 2 /0 0

IE C

C le a r e d

A -H S 2 S ta rte r

Cc/Hydro_Prs/Interne RS.ppt

26

PEEBLES

REYROLLE

VA TECH Transmission & Distribution


Reydisp Evolution

Cc/Hydro_Prs/Interne RS.ppt

27

PEEBLES

REYROLLE

VA TECH Transmission & Distribution


Communications
Communications to IEC60870-5-103 protocol

Fibre optic with SMA connectors

May be connected in a loop with 254 relays

Fibre optic hub available for star configuration

Cc/Hydro_Prs/Interne RS.ppt

28

PEEBLES

REYROLLE

VA TECH Transmission & Distribution


Ring Connected Data Comms
Remote
PC

PCs to be equipped with Reydisp software


Up to 254 relays can be connected in single loop
Each relay to have unique address

Sigma
3
RX

RS232
TX

Local
PC
F.O Cables

TX

RX

RX

TX

RX

TX

RX

TX

Cc/Hydro_Prs/Interne RS.ppt

29

PEEBLES

REYROLLE

VA TECH Transmission & Distribution


Star Connected Data Comms

Star connected data comms


Increased Security

Remote
PC
Sigma
1
Local
PC

Sigma 1 F.O. Hub

F.O Cables

Cc/Hydro_Prs/Interne RS.ppt

30

PEEBLES

REYROLLE