New features Internal timer for TEST mode New function was added to the controller. It is timer which allows to test gen-set function with the defined period. Controller is behaving according to TEST mode description in the manual (see IL-AMF-2.5.pdf) when the TEST duty is active.
Two parameters related to the new function were added:
Test period Period of the test repetition Range: 0-240 days Step: 1 day Test duration Duration of the Test mode duty (starts after expiration of the Test period) Range: 0-240 minutes Step: 1 minute If both parameters (Test period and Test duration) are set to zero, the timer is disabled. If a controller is switched off, the timer is reset and new counting starts after switching the controller on. If the engine is started, the timer is reset, too. Automatic Test may be carried out only if the controller is in AUT mode. If the Test period time elapses and the controller is in OFF or MAN mode, controller waits for switching over to AUT mode and starts automatic test then.