Table1.ASHRAE/IES90.1lightingpowerallowancesusingtheBuildingAreaMethod.
BuildingType

MaximumLightingPowerDensity(W/sq.ft.)AllowedPer
VersionoftheASHRAE/IES90.1Standard
1989

1999/2001

2004/2007

2010

AutomotiveFacility

0.96

1.5

0.9

0.982

ConventionCenter

2.07

1.4

1.2

1.08

CourtHouse

1.44

1.4

1.2

1.05

Dining:Bar
Lounge/Leisure

1.37

1.5

1.3

0.99

Dining:Cafeteria/Fast
Food

1.37

1.8

1.4

0.90

Dining:Family

1.37

1.9

1.6

0.89

Dormitory

1.15

1.5

1.0

0.61

ExerciseCenter

2.07

1.4

1.0

0.88

Gymnasium

2.07

1.7

1.1

1.00

HealthcareClinic

1.44

1.6

1.0

0.87

Hospital

1.44

1.6

1.2

1.21

Hotel

1.15

1.7

1.0

1.00

Library

1.29

1.5

1.3

1.18

ManufacturingFacility

0.96

2.2

1.3

1.11

Motel

1.15

2.0

1.0

0.88

MotionPictureTheater

2.07

1.6

1.2

0.83

MultiFamily

1.15

1.0

0.7

0.60

Museum

2.07

1.6

1.1

1.06

Office

1.26

1.3

1.0

0.90

ParkingGarage

1.03

0.3

0.3

0.25

Penitentiary

1.44

1.2

1.0

0.97

PerformingArtsTheatre

2.07

1.5

1.6

1.39

Police/FireStation

1.44

1.3

1.0

0.96

PostOffice

1.44

1.6

1.1

0.87

ReligiousBuilding

2.07

2.2

1.3

1.05

Retail

2.25

1.9

1.5

1.40

data:text/htmlcharset=utf8,%3Cp%20style%3D%22margin%3A%201em%200px%3B%20padding%3A%200px%3B%20display%3A%20block%3B%20color%

1/2

12/2/2015

ASHRAEReleases90.12010Part1:Design,Scope,AdministrativeRequirements|LightingControlsAssociation

School/University

1.29

1.5

1.2

0.99

SportsArena

2.07

1.5

1.1

0.78

TownHall

1.44

1.4

1.1

0.92

Transportation

2.07

1.2

1.0

0.77

Warehouse

1.03

1.2

0.8

0.66

Workshop

0.96

1.7

1.4

1.20