3. Remove Memory Module ( 1747-M11 ) Skip step 3 if a Memory Module is not Installed
4. Disconnect Battery
5. Locate the GND & VBB points on the back side of the processor module.
6. Using a small flat blade screw driver short the GND & VBB points for 60 Seconds.
(Take care to make a good metal-to-metal connection)
IMPORTANT:
Once Factory Defaults have been restored the ladder logic program will be lost and all
communications channels will be reset to their default state, See Below:
SLC-5/04 CH1 - DH+ ( 57.6k baud )
SLC-5/03 CH1 - DH485 ( 19.2k baud )
SLC-5/05 CH0 - DF1 Full Duplex 19.2k Baud, N, 8, 1, CRC
SLC-5/04 CH0 - DF1 Full Duplex 1200 Baud, N, 8, 1, CRC
SLC-5/03 CH0 - DF1 Full Duplex 1200 Baud, N, 8, 1, CRC
Note: SLC 5/03 OS302 FRN 11 , SLC 5/04 OS401 FRN 8 or greater Channel 0 Defaults to
19.2KBaud
Reference(s):
16846- Lost or Forgotten passwords procedure for the Micrologix, SLC-500, PLC-5 Family of
controllers and RSLogix software. Processor is prompting for a password and password is either
lost or forgotten.