FAILURE OF UPS POWER

UPS Invertors Failed & UPS By-PASS Supply is


not available.
UPS Battery Charger/ or Battery Banks Failed
& UPS By-PASS Supply is not available.

Consequences:

No control from DCS.


No Alarm will come in LVS, UCP &
No control from UCP
220 V A.C UPS Supply Fail means 110V A.C Fail.
24V D.C Fail.
230V A.C Fail.

What will happen after Failure of UPS Power :

Boiler will trip through Loss of 24V D.C (i.e.


MFT WILL OCCUR THROUGH HARDWIRE)
MFT
All running Coal Feeder will trip due to FAIL
SAFE Logic ( Loss of 110 V AC )
FEEDER
HOTV/ LOTV will trip due to FAIL SAFE Logic.
HORV will not change the state.
TRIP VALVE
Mill & PA FAN not tripped through Logic. To be
tripped manually.
PA FAN

Slide 3

FEEDER

DC HEALTHY
36,46,56
ENERGIZE 1&3
ARE
CONNECTED

LOTV/HOT
V

LOTV

OYV
HOTV

PSS
AB

110V AC RELAY
PSF AB

SYSTE
M
POWE
R
24 V
DC

SADC will open fully.


SH/ RH Block Valve will not close.
Burner Tilt to be minimum.
All CV, Blade Pitch of Fans, IGV, and SCOOP will
come down to Minimum.