not available. UPS Battery Charger/ or Battery Banks Failed & UPS By-PASS Supply is not available.
Consequences:
No control from DCS.
No Alarm will come in LVS, UCP & No control from UCP 220 V A.C UPS Supply Fail means 110V A.C Fail. 24V D.C Fail. 230V A.C Fail.
What will happen after Failure of UPS Power :
Boiler will trip through Loss of 24V D.C (i.e.
MFT WILL OCCUR THROUGH HARDWIRE) MFT All running Coal Feeder will trip due to FAIL SAFE Logic ( Loss of 110 V AC ) FEEDER HOTV/ LOTV will trip due to FAIL SAFE Logic. HORV will not change the state. TRIP VALVE Mill & PA FAN not tripped through Logic. To be tripped manually. PA FAN
Slide 3
FEEDER
DC HEALTHY 36,46,56 ENERGIZE 1&3 ARE CONNECTED
LOTV/HOT V
LOTV
OYV HOTV
PSS AB
110V AC RELAY PSF AB
SYSTE M POWE R 24 V DC
SADC will open fully.
SH/ RH Block Valve will not close. Burner Tilt to be minimum. All CV, Blade Pitch of Fans, IGV, and SCOOP will come down to Minimum.