Você está na página 1de 1

Unistrut Cable Tray

Cable Management Data Sheet


Load data
TYPE LIGHT DUTY CABLE TRAY (L)

2500
2000

N/m

0.5 L
0.75 L

0.4 L

1500

W= 300

1000

W= 50-225

500
0
Load test according to CEI/IEC 61537:2001
Q = UDL (uniformly distributed load)
Safety Factor = 1.7
L = intermediate span
F = deflection = 1/100 of the intermediate span (max.)
S = splice location

N/m

700

Stated loadings apply to mild steel products only.

W= 300-600

500

W= 50-225

300
200

1,0

3000

1,5
L (Span m)

2,0

TYPE HEAVY DUTY CABLE TRAY (H-50)

2500

N/m

COUPLERS: The loading and deflection tables for Unistrut Cable


Tray assume that the couplers are located at the most onerous
position within the span (i.e. mid span).
To maintain the load/deflection figures stated in the tables, the
couplers should not be located in end spans or over support
locations. Straight couplers were utilized for the testing of the
medium and heavy duty cable trays. Only one pair of couplers
should be installed per span.

2000

W= 450-600

1500
1000

W= 225-300

500
200

M EDI UM DUTY (M -2 5 )

Width
mm
50
75
100
150
225
300
450
600
750
900

600
400

ACCESSORIES: To ensure adequate support, accessories should


be supported locally.

Useful cross section


(cm2)
5.4
8.1
10.9
16.6
24.9
49.9
75.1
95.3
119.3
143.3

1,5

800

DEFLECTION: Unistruts load and deflection figures are in


accordance with CEI/IEC 61537:2001, with the characteristic
deflection of Unistrut Cable Tray limited to span/100. and load
figures inclusive of a safety factor of 1.7.

Width
mm
50
75
100
150
225
300
450
600
750
900

1
L (Span m)
TYPE MEDIUM DUTY CABLE TRAY (M-25)

900

Unistruts load testing is in accordance with CEI/IEC 61537:2001.


In practical terms this covers continuous/multi span installations,
evenly loaded along the length of, and across the full width of the
tray. The end spans in these installations should be reduced to
0.75 of the intermediate spans.

LI G H T DUTY (L)

0,5

Useful cross section


(cm2)
11.4
17.4
23.5
35.6
53.7
70.4
106.1
141.8
171.1
205.6

W= 75-150
1,5

2
L (Span m)

2,5

H EAV Y DUTY (H -5 0 )

Width
mm
75
100
150
225
300
450
600
750
900

Useful cross section


(cm2)
35.8
48.1
72.7
108.2
144.8
213.6
285.6
357.6
429.6

Você também pode gostar