71-2 IEC: 1996

119

Table A.1

Correlation between standard lightning impulse withstand


voltages and minimum air clearances

Standard lightning impulse


withstand voltage

Minimum clearance
mm

kV
.9

wt

20

60

40

60

60

90

75

120

95

160

125

220

145

270

170

320

250

480

325

630

450

900

550

Rod-structure

Conductor-structure

1100

650

1300

750

1500

850

1700

1600

950

1900

1700

1050

2100

1900

1175

2350

2200

1300

2600

2400

1425

2850

2600

3100

2900

1675

1550

3350

3100

1800

3600

3300

1950

3900

3600

2100

4200

3900

NOTE
The standard lightning impulse is applicable phase-to-phase and
phase-to-earth.

For phase-to-earth, the minimum clearance for conductor-structure and rodstructure is applicable.
For phase-to-phase, the minimum clearance fQr rod-structure is applicable

121

71-2 IEC: 1996

Table A.2

Correlation between standard switching impulse withstand


voltages and minimum phase-to-earth air clearances
Minimum phase-to-earth
mm

Standard switching impulse


withstand voltage

Conductor-structure

Rod-structure

750

1600

1900

850

1800

2400

kV

Table A.3

950

2200

2900

1050

2600

3400

1175

3100

4100

1300

3600

4800

1425

4200

5600

1550

4900

6400

Correlation between standard switching impulse withstand


voltages and minimum phase-to-phase air clearances
Minimuni phase-to-phase clearance

Standard switching impulse


withstand voltage

Phase-toearth

Phase-to-phase
value

mm
Phase-tophase

Conductor-conductor
parallel

Rodconductor

2600

kV

Phase-to-earth
value

750

t,5

1125

2300

850

1,5

1275

2600

3100

850

1,6

1360

2900

3400

950

1,5

1425

3100

3600

950

1,7

1615

3700

4300

1050

1,5

1575

3600

4200
4600

<V

1050

1,6

1680

3900

1175

1,5

1763

4200

5000
7400

1300

1,7

2210

6100

1425

1,7

2423

7200

9000

1550

1,6

2480

7600

9400