ANNEXURE - F

SPAU 140C RELAY SETTINGS


Relay location: 380V Incomer
Protection Function: 25
Parameter
Low Stage Setting
Upper threshold voltage

Range

Settings

Remarks

0.5-1.00Un

0.9Un

342.0V

set(Umax)
Lower threshold voltage

0.10-0.8Un

0.8Un

304.0V

set(Umin)
Voltage difference Un
Phase Angle difference Phase
Frequency difference f
Operate Time of Circuit

0.02-0.60 Un
5-900
0.02-5.0 Hz
0.05-0.25s

0.16Un
100
0.15Hz
0.15

60V
100
60.15-59.85Hz
150ms

breaker

REU-610 RELAY SETTING:


Relay location: 380V Incomer

Protection Function: 27/59

Parameter
Range
Settings
Low Stage 3U<Low Setting ( Under Voltage)
Start Voltage low set 0.02-1.20Un
0.90Un

Remarks
90% of Primary
Voltage =342V

Operation Mode

IEC and IEEE

Definite

(3U<)

curves

Time

Start time (Sec)

Def. time/IDMT
80ms

80ms

Operate time(Sec)
Drop-off/Pick-up

0.1-600
1.01-1.05

60s
1.03

ratio,D/P>
Reset Time
70-6000ms
100ms
High Stage -3U<< High Setting (Under Voltage)
Start Voltage low set 0.1-1.20Un
0.80Un

3% hysteresis
recommended
80% of Primary
Voltage
=304Vsetting

Operation Mode

IEC and IEEE

Definite time

(3U<<)

curves

operation

Operate time(Sec)
Start time (Sec)
Drop-off/Pick-up

Def. time/IDMT.
0.1-2
80ms
1.01-1.05

6s
80ms
1.03

ratio,D/P>
Reset Time

High set Stage I>>


Start current I>>
(definite time)

3% hysteresis
recommended

70-6000ms

0.5In 40 In

100ms

1.3 In

Since the
ACB
setting is
at 1.2 x
In, so
this relay
is

Operating time t>>

0.04 300 s

0.6 s

0.1In-0.8In

0.2 x In

Operating time to>

0.05s-300s

0.5 s

High set Stage Io>>


Start current I>>
(definite time)

0.5In 40 In

1.3 In

Setting of E/F unit


Low set Stage Io>
Start current Io>
(definite time)

slightly
higher
Since the
actual
time of
operatio
n of
ACB is
0.5s
thats
why we
will keep
time
setting
slightly
higher .
Same as
G
setting of
ACB
Since the
actual
time of
operatio
n of
ACB for
G
setting is
0.4s
thats
why we
will keep
time
setting
slightly
higher.
Since the
ACB
setting is
at 1.2 x
In, so
this relay
is

slightly
higher
Operating time to>>

0.05s-300s

0.3