Escolar Documentos
Profissional Documentos
Cultura Documentos
Range
Settings
Remarks
0.5-1.00Un
0.9Un
342.0V
set(Umax)
Lower threshold voltage
0.10-0.8Un
0.8Un
304.0V
set(Umin)
Voltage difference Un
Phase Angle difference Phase
Frequency difference f
Operate Time of Circuit
0.02-0.60 Un
5-900
0.02-5.0 Hz
0.05-0.25s
0.16Un
100
0.15Hz
0.15
60V
100
60.15-59.85Hz
150ms
breaker
Parameter
Range
Settings
Low Stage 3U<Low Setting ( Under Voltage)
Start Voltage low set 0.02-1.20Un
0.90Un
Remarks
90% of Primary
Voltage =342V
Operation Mode
Definite
(3U<)
curves
Time
Def. time/IDMT
80ms
80ms
Operate time(Sec)
Drop-off/Pick-up
0.1-600
1.01-1.05
60s
1.03
ratio,D/P>
Reset Time
70-6000ms
100ms
High Stage -3U<< High Setting (Under Voltage)
Start Voltage low set 0.1-1.20Un
0.80Un
3% hysteresis
recommended
80% of Primary
Voltage
=304Vsetting
Operation Mode
Definite time
(3U<<)
curves
operation
Operate time(Sec)
Start time (Sec)
Drop-off/Pick-up
Def. time/IDMT.
0.1-2
80ms
1.01-1.05
6s
80ms
1.03
ratio,D/P>
Reset Time
3% hysteresis
recommended
70-6000ms
0.5In 40 In
100ms
1.3 In
Since the
ACB
setting is
at 1.2 x
In, so
this relay
is
0.04 300 s
0.6 s
0.1In-0.8In
0.2 x In
0.05s-300s
0.5 s
0.5In 40 In
1.3 In
slightly
higher
Since the
actual
time of
operatio
n of
ACB is
0.5s
thats
why we
will keep
time
setting
slightly
higher .
Same as
G
setting of
ACB
Since the
actual
time of
operatio
n of
ACB for
G
setting is
0.4s
thats
why we
will keep
time
setting
slightly
higher.
Since the
ACB
setting is
at 1.2 x
In, so
this relay
is
slightly
higher
Operating time to>>
0.05s-300s
0.3