Você está na página 1de 1

M&T MECHANICAL CALCULATIONS

Closed System Expansion Tank

Project:
Client:
Contractor:
Engineer:

Building:
Floor:
Axes:
Tank No.:
Tank Type: Closed
Pump Description:
Max. Temp. ( oC):

Pump on Return
30

System Volume Estimation


System Heating or Cooling Power

2296

( Kw )

Approx.Volume System Vs (12L/Kw)

27552

(L)

Input Data
Height From Exp. Tank To Highest Point (m)

20

Circulating Pump Head (m)

40

Maximum Safe Working Pressure (Bar)

10

Output Data
System
Water
Volume
(L)
27552

12/9/2013

Max. Allowable
Press. (Ppw)
Bar
5.73

Air Cushion
Min. Vessel Volume
Vessel
Press. (Pac)
Acceptance %
(L)
Bar
2.21

50

248

Page 1 of 1