CONTENTS:
Page
1- References
2- Design Basis
3- Design Parameter
Annexe1
THUWAL
SAUDI ARABIA
INDEX
PLANT NO.
DRAWING NUMBER
3-073205002
J215
WE-027979
SHEET NO.
of
REV. NO
02
1 - References:
12345678910-
( TES-P-119.25)
( WA - 027996 )
( WA - 028000 )
( WA - 028001 )
( WA - 028003 )
( WA - 028004 )
( WA - 028006 )
( WA - 027730 )
THUWAL
SAUDI ARABIA
INDEX
PLANT NO.
DRAWING NUMBER
3-073205002
J215
WE-027979
SHEET NO.
of
REV. NO
02
2 - Design Basis
Lighting calculation for indoor area is designed using Easy Plan Ver.2.4.1. of
Saudi Lighting company for all Indoor / Outdoor areas.
3 Design Parameter
3.1 Reference to SCECO standard no [TES.P.119.25], Rev(0), Clause [4.1.4],
Page no. 7, The reflectance factor for control building & 110kV GIS building and
13.8kV SWGR building.
3.1.1 Reflectance Factors
-Ceiling
0.3
-Wall
0.3
-Floor
0.2
3.1.2 Maintenance Factor
-Maintenance Factor will be 0.7 & 0.6 as per consultant requirement by
comments letter no.
(SCJ/SEC/20731025/D10595 DATED 29.03.08).
3.2 Work Plane height for normal indoor lighting system shall be considered
at zero level from finished level except Office as per consultant requirement by
comments letter no.
(SCJ/SEC/20731025/D10595 DATED 29.03.08).
3.3 Work Plane height for normal indoor lighting system shall be considered
at zero level from finished level except Office as per consultant requirement by
3.4 Work Plane height for emergency lighting system shall be at zero level
from finished floor level as per SCECO standard (TES-P-119.25), Rev(0),
Clause (5.4), and Page (12)
3.5 Recessed type fixture are considered for areas with false ceiling
Suspended type/surface type fixture are considered for areas without false ceiling.
- recessed
b) 2x40w
GIS room,basement,corridor
c) 2x36
Explosion proof
Battery room
THUWAL
SAUDI ARABIA
INDEX
PLANT NO.
DRAWING NUMBER
3-073205002
J215
WE-027979
SHEET NO.
of
REV. NO
02
d) 400w
e) 2x36w
f) 2x36
Mounting Heights
a) Battery room
b) Basement
c) Area with false ceiling
d) other areas in control building
e) GIS room
f) MVSWGR room
3.6
Portable type self contained emergency light fixture are proposed near the
main entrance. These will be connected to sockets outlet
3.7
8W wall mounted "EXIT" light fixtures with 3hrs emergency battery back up are
proposed at the exit.
3.8
DC emergency light
DC emergency lights with 60W incandescent lamps are proposed. These lights will be powered
by 125VDC substation batteries. Recessed down light type fixture propsed for false ceiling and
surface type is proposed for other areas.
A switch is also provide d in the rrom to control the lights.
THUWAL
SAUDI ARABIA
INDEX
PLANT NO.
DRAWING NUMBER
3-073205002
J215
WE-027979
SHEET NO.
of
REV. NO
02
S.N.
Lux Level
Control Room
400
300
300
AC/DC Room
300
Battery Room
200
Office
500
Kitchen
100
Toilet
100
Corridor
100
10 Basement - 1
100
100
100
100
14 FM 200 Room
200
THUWAL
SAUDI ARABIA
INDEX
PLANT NO.
DRAWING NUMBER
3-073205002
J215
WE-027979
SHEET NO.
of
REV. NO
02
P /
40
Product no.
Mounting System
No. of Lighting
Watt. Of Lighting
Voltage &
Ballast Type
P
S
B
B
:
:
:
:
Pendant Mounting
Surface Mounting
220VAC or 127VAC/60Hz
Switch Start Ballast
SAUDI ARABIA
INDEX
PLANT NO.
DRAWING NUMBER
3-073205002
J215
WE-027979
SHEET NO.
of
REV. NO
02
G Ellk 92/236.ADAF.PC
Pendant mounted luminaries suspended by rods, wires or chains, Body is made of
molded glass reinforce polyester in gray color & height resistance to chemical and
explosion protect Contain 2 x 36 W Lamps. Operate at 127 V, 60HZ. Clear translucent
molded, Polycarbonate below diffuser.
H 5313ZP / 1-400AP.GL
Pendant mounted low bay indoor luminaire, 1 x 400-watt Mercury Vapor lamp,
127VAC/60Hz reactor type high power factor control gear, frame made of stamped
clear plain pattern flat tempered glass in frame body is made of spun aluminum,
brackets and glass frame are made of stamped galvanized steel sheet.
I 5771 / 11-60KB.GF
Reseed mounted luminaries used for false ceiling system. Contain 60 W incandescent
Lamps, Operate 125V dc, the lamp shall have efficacy more than 13 lum/W as per
specification (TES-P.119.25,Ro) clause no (4.3.2)
J 8513W/11-60K.GL
Base and frame are made from die casted aluminum wall mounted luminaries,, contain
60 W incandescent lamps. Operate at 125V dc. The lamp shall have efficacy more than
13 lum/W, as per specification (TES-P-119.25.R0) clause no (4.3.2).
K 8513S/11-60K.GL
Base and frame are made from die casted aluminum wall mounted luminaries,, contain
60 W incandescent lamps. Operate at 125V dc. The lamp shall have efficacy more than
13 lum/W, as per specification (TES-P-119.25.R0) clause no (4.3.2).
L AB50IXM/11-60K.GB.C110
Pendant mounted luminaries indirect entry. Contain 60W, incandescent lamp operate
125V dc.
THUWAL
SAUDI ARABIA
INDEX
PLANT NO.
DRAWING NUMBER
3-073205002
J215
WE-027979
SHEET NO.
of
REV. NO
02
Control Room
Normal
"SLC"
5313ZP/
1-400AP.GL
Recessed/Pendant
Switch Start
Emergency
"SLC"
5771/1160KB.GF
Recessed
-
Lighting Source
Fluores. 4x40W
Incandesce.1x60W
HPMV.1x400W
Supply
127VAC, 60Hz
125Vdc
2.9
2.9
Quantity
24
13
10
Required
400
10
300
10
403
14.9
349
13
Lighting Sys.
Manufacturer
5712A/440XB.2
Order No.
Mounting
Ballast Type
MH
Actual Lux
Room
Dimension(m)
Normal
"SLC"
72665/
240.XB.CL
Surface
Pendant
8513W/11-60K.GL
Wall
-
Switch Start
Fluores.2x40W
125Vdc
2
20
18
L = 14
L = 5.5
W = 49.6
H=3
21
Incandes.1x60W
127Vac. 60Hz
W = 20
43
IP Class no.
Emergency
"SLC"
54
H = 5.1
43
65
MH : Mounting Height
SAUDI ARABIA
THUWAL
JOB ORDER NO.
INDEX
PLANT NO.
DRAWING NUMBER
3-073205002
J215
WE-027979
SHEET NO.
of
REV. NO
02
Lighting Sys.
Manufacturer
Order No.
Mounting
Ballast Type
Fluores.2x40W
**
Indes.1x60W
5712A/440XB.2
5771/11.60SGC
Pendant
Switch Start
Recessed
-
Fluores 4x40W
Incandes. 1x60W
125Vdc
2.5
2.5
2.9
2.9
Quantity
Required Lux.
Actual lux
**
300
10
300
10
349
12.9
320
10
Room
Dimension (m)
Class of
protection (IP)
Emergency
"SLC"
6.5
Supply
MH
Normal
"SLC"
Emergency
"SLC"
5313ZP/
7266S/
1.400AP.GL
240XB.CL
Pendant
Surface
Switch Start
AC/DC Room
L=10
L = 5.4
W=20.1
W=6
H=8
H = 2.9
54
43
65
Order No
8513W/
11-60K.GL
85135/
11-60K.GL
Mounting
Wall
Surface
Quantity
43
21
THUWAL
SAUDI ARABIA
INDEX
PLANT NO.
DRAWING NUMBER
3-073205002
J215
WE-027979
SHEET NO.
of
REV. NO
02
Battery Room
Normal
"SLC"
Office
Emergency
"SLC"
AB501XM/
11-60K.GB
Pendant
Incandes.
1x60W
125Vdc
MH
2.9
Quantity
Required Lux.
200
10
500
10
Actual lux.
312
10
708
Lighting Sys.
Manufacturer
eLLK92/23ADAF.PC
Order No.
Pendant
Switch Start
Mounting
Ballast Type
Lighting Source
Fluores. 2X36W
Aux. Supply
Room
Dimension (m)
Class of
Protection (IP)
Normal
"SLC"
Emergency
"SLC"
5712/440XB.2
5771/11-60KB.GF
Pendant
Switch Start
Recessed
-
Fluores. 4x40W
Incandes. 1x60W
127 Vac, 60 Hz
125Vdc
2.9
14.9
L = 5.5
L = 5.4
W=4
W=4
H = 4.9
H = 2.9
66
66
43
21
THUWAL
SAUDI ARABIA
INDEX
PLANT NO.
DRAWING NUMBER
3-073205002
J215
WE-027979
SHEET NO.
of
REV. NO
02
Kitchen
Normal
"SLC"
Lighting Sys.
Manufacturer
Toilet
Emergency
"SLC"
5771/1160KB.GF
Recessed
-
Normal
"SLC"
Emergency
"SLC"
5712A/440XB.2
5771/11-60KB.GF
Pendant
Order No.
5712A/440XB.2
Mounting
Ballast Type
Lighting Source
Pendant
Switch Start
Fluores. 4x40W
Incandes. 1x60W
Fluores. 4x40W
Recessed
Incandes.1x60W
127Vac. 60Hz
125Vdc
125Vdc
2.9
2.9
2.9
2.9
Aux. Supply
MH
Quantity
Switch Start
Required Lux.
100
10
100
10
Actual lux.
202
18.9
138
14.2
Room
Dimension (m)
Class of
Protection (IP)
L = 5.4
L = 5.4
W=3
W = 1.5
H = 2.9
H=3
43
21
21
43
THUWAL
SAUDI ARABIA
INDEX
PLANT NO.
DRAWING NUMBER
3-073205002
J215
WE-027979
SHEET NO.
of
REV. NO
02
Corridor
Normal
"SLC"
Lighting Sys.
Manufacturer
Basement - 1MVSWGR
Emergency
"SLC"
Emergency
"SLC"
8513W/
11-60K.GL
Wall
-
Normal
"SLC"
72665/240XB.CL
Incandex. 1x60W
Fluores. 2x40W
Incandes. 1x60W
125Vdc
Order No.
5712A/440XB.2
Mounting
Ballast Type
Lighting Source
Pendant
Switch Start
Fluores. 4x40W
Aux. Supply
125Vdc
MH
Quantity
11
22
Required Lux.
100
10
100
10
204
10
176
11.4
Actual lux.
Room
Dimension (m)
**
Surface
Switch Start
**
L = 18.6
W = 23.3
H=3
Class of
Protection (IP)
43
21
Order No
8513W/
11-60K.GL
85135/
11-60K.GL
Mounting
Wall
Surface
Mounting Height
2.2
Quantity
18
43
65
THUWAL
SAUDI ARABIA
INDEX
PLANT NO.
DRAWING NUMBER
3-073205002
J215
WE-027979
SHEET NO.
of
REV. NO
02
Basement -3GIS
Order No.
5712A/440XB.2
Mounting
Ballast Type
Lighting Source
Pendant
Switch Start
Fluores. 4x40W
Incandex. 1x60W
Fluores. 2x40W
Emergency
"SLC"
85135/
11-60K.GL
Surface
Incandes. 1x60W
Aux. Supply
125Vdc
125Vdc
MH
Quantity
14
18
Normal
"SLC"
Lighting Sys.
Manufacturer
Required Lux.
Actual lux.
Emergency
"SLC"
5770/1160KB.GF
Recessed
-
Normal
"SLC"
72665/240XB.CL
Surface
Switch Start
100
10
100
10
188
17.6
179
14
43
21
43
65
Room
Dimension (m)
Class of
Protection (IP)
Order No
8513W/
11-60K.GL
85135/
11-60K.GL
Mounting
Wall
Surface
Mounting Height
2.2
Quantity
18
THUWAL
SAUDI ARABIA
INDEX
PLANT NO.
DRAWING NUMBER
3-073205002
J215
WE-027979
SHEET NO.
of
REV. NO
02
Basement 4-Tunnel
Lighting Sys.
Manufacturer
Normal
"SLC"
Emergency
"SLC"
Order No.
5712A/440XB.2
8513w
Mounting
Ballast Type
Lighting Source
Pendant
Switch Start
Fluores. 4x40W
Wall
Incandex. 1x60W
Aux. Supply
125Vdc
MH
2.2
Quantity
14
Required Lux.
Actual lux.
100
10
100
10.8
43
65
Room
Dimension (m)
Class of
Protection (IP)
THUWAL
SAUDI ARABIA
INDEX
PLANT NO.
DRAWING NUMBER
3-073205002
J215
WE-027979
SHEET NO.
of
REV. NO
02