Você está na página 1de 2

TURBINE FIRE PROTECTION LOGICS

TWO NUMBER OF FIRE PROTECTION PUSH BUTTONS IN RED COLOUR WERE PROVIDED IN
3 PLACES.
1. UCB CONTROL DESK - FROM TOP TO BOTTOM
1. FP.CHANNEL-I
2. FP.CHANNEL-II

2. NEAR LP TURBINE [PUSH BUTTON ARRANGEMENT FROM LEFT TO RIGHT]


RESPECTIVELY.

FP.CHANNEL-I

FP.CHANNEL-II

3. MAIN OIL TANK ROOM ENTRANCE [PUSH BUTTON ARRANGEMENT FROM LEFT TO
RIGHT] RESPECTIVELY.

FP.CHANNEL-I

FP.CHANNEL-II

FIRE PROTECTION CHANNEL-I OPERATES GATE VALVE-I NEAR MAIN OIL TANK.
FIRE PROTECTION CHANNEL-II OPERATES GATE VALVE-II NEAR GOVERNING RACK.
1. FP.CHANNEL-I (MINOR)
2. FP.CHANNEL-II (MAJOR)

FIRE PROTECTION CHANNEL-I


FIRE PROTECTION OPERATED.
FIRE PROTECTION CHANNEL-1 NOT COMPLETE.
TURBINE TRIPPED.
TURBINE TRIP GEAR OPERATED.

FIRE PROTECTION CHANNEL-II


FIRE PROTECTION OPERATED.
FIRE PROTECTION CHANNEL-2 NOT COMPLETE.
TURBINE TRIPPED.
TURBINE TRIP GEAR OPERATED.

IF FIRE PROTECTION CHANNEL-II OPERATES FOLLOWING THING HAPPENS:


1. TURBINE TRIPS.
2. GATE VALVE-II TRIPS (NEAR GOVERNOR RACK)-SHUT-OFF VALVE CLOSES.
3. VACUUM BREAKER PROTECTION OPENS.
4. STARTING EJECTOR STEAM VALVE - PROTECTION CLOSES.
5. STARTING EJECTOR AIR VALVE - PROTECTION OPENS.
6. FIRE PROTECTION SWITCH-II OPERATED ALARM.
7. SGC OIL SUPPLY IS MADE OFF.
8. SLC AUXILIARY OIL PUMP-A IS MADE OFF.
9. SLC AUXILIARY OIL PUMP -B IS MADE OFF.
10. SLC EMERGENCY OIL PUMP IS MADE ON.ON HP CASING.120C LOGIC EOP WILL START.
11. SLC JOCKING OIL PUMP-A IS MADE OFF.
12. SLC JOCKING OIL PUMP-B IS MADE OFF.
13. SLC TURNING GEAR IS MADE OFF.
14. AOP-A IS PROTECTION OFF.
15. AOP-B IS PROTECTION OFF.
16. JOP-A IS PROTECTION OFF. 17. JOP-B IS PROTECTION ON FOR HAND BEARING PURPOSE.

Você também pode gostar