Você está na página 1de 43

1

Section Contents PAGES

1. Introduction 2-5
Salient features, internal & general appearance of Drawout ACB

2. Ratings & Specifications 6-9


Free air & enclosed thermal current ratings for AC & DC applications & selection
of specifications

3. Multi-Function Protecion Devices 10-15


Micro Processor Based over current trip device, Economical Thermal Magnetic &
their accessories

4. Spring Charging Operations 16-17


Manual & motor charging & accessories for closing operations

5. Electrical Tripping 18-19


Shunt Trip, Capacitor Trip, UVT & Control Devices

6. Type of Mounting 20
Fixed, metal clad type, lifter, accessories for draw-out, safety shutter, position switch,
S/C contacts, test jumper, mal-insertion/ prevention device

7. Other Accessories 21-24


Aux. Switch, Key lock, Mechanical Interlock, Door Interlock, Lifter, carrying handle

8. Power Consumption 25
Internal resistance, reactance & special environmental specifications

9. Clearance 26
Clearance above Arc chute, maintenance space

10. Outline Dimensions 27-36


Outline dimensions & Panel Mounting Details of D series ACBs of 630A to
4000A & C series ACBs of 5000 to 6300A

11. Electrical Connection Diagram 37-38


Interconnections between electrical accessories & tripping devices

12. ACB Order Form 39


ACB Order Form
Introduction

1.0 Introduction

“C & S” Air Circuit Breakers are available in the current range of 630A to 6300A with
wide choice of options & Accessories

! 2, 3 or 4 Pole version available in all current ! Wide options of front panel fittings.
ratings, in fixed & drawout execution.
! 8 type of Accessories for Drawout types, Safety
! Motor charging or manual charging, facilitating Shutter, Position Switch, Test Jumper, Lifter, Mal
local or remote control. Insertion Prevention Device, Door Interlock with
defeat facility, Short Circuiting Contacts &
! 5 types of protection & trip devices: Drawout position Padlock.
a) Micro processor based RMS sensing over- ! Vertical or horizontal bus bar connection
current relay for industrial & generator arrangement.
protection.

b) Electromagnetic instantaneous trip device with


thermal O/L Relay for S/C & O/L protection
for AC system & with Hall Sensor for DC
system.

c) Undervoltage trip with or without time delay


for under voltage.
d) Making current release for safeguarding
against closing of Breaker on S/C faults.
! 4 types of indication Switches, Auxiliary Switch,
Trip Indication Switch, OCR Alarm Switch,
Spring Charged Indication Switch.

General Appearance of Air Circuit Breaker

4
Introduction

1.1 Salient Features

! Lightest and most compact for a given capacity. ! Due to use of tungsten-silver sintered metal
contacts, high speed opening mechanism &
! Most simple to operate & maintain. Only a electromagnetic instantaneous trip device, most
screw driver a spanner required for replacing suitable for capacitor switching & DC
the arcing contacts. application.
! Only 4 frame sizes for entire range (630A ! High dielectric strength even in hot and humid
to 6300A), resulting in maximum interchangeability, conditions due to use of class ‘B’ and ‘F’
commonality of parts and minimum inventory insulating materials.
of spares.
! Comply with utilisation category B & pollution
! High breaking capacity, 50KA to 120KA and degree 3 Group I of IEC 947-Part I.
making capacity from 105KA to 264KA with
line or load connected to upper or lower ! Can withstand impulse voltage of 8KV (peak),
terminals. 1.2/50 micro sec. wave as per case ‘A’ in
homogeneous field condition of
! High speed operating Mechanism ensures a IEC 947-Part-I.
total opening time of 30ms (including arcing
time of less than 10ms) and a total closing ! D-series Breaker fitted in Panel with door cut
time of 40m sec. out meets IP42 protection.

! Neutral pole of 4 pole ACB is of same current ! Designed to provide continuous duty even in
rating as of 3 pole. adverse environmental conditions.
! Highest degree of system protection &
coordination due to use of microprocessor
based protection release.

Internal Structure
Model: AH-6D, Draw-out, Motor Charging Type

Stored energy type


1. Overcurrent trip device (Microprocessor based)
2. Arc chutes
3. Isolating contacts of control circuits
4. Main circuit Terminals
5. Draw out moulded base
6. Main circuit terminals
7. Isolating contacts of main circuits
8. Fixed arcing contacts
9. Moving arcing contacts
10. Fixed main contacts
11. Moving main contacts
12. Closing mechanism
13. Trip bar
14. Inst. trip devices
15. CT (for overcurrent trip device)
16. Charging motor
17. Closing latch release
18. Closing spring
19. Charging handle
20. Quick close Slow close selector lever
21. Auxiliary switches
5
Introduction

1.2 Front Panel designed for the new Millennium


Three Front Panel Cut-outs for entire range (630A to 6300A), help standardise your design

"
#
$
%
12

& '
11
( +
15
)
* 13

14

16

" Rating Name Plate. * Push to Open Button.

# Charging Handle. + Close PPosition


osition PPadlock
adlock (Optional).

$ Close Open Cycle Counter (Optional). 11 Draw-out insertion Hole.

% D/O PPosition
osition Indicator
Indicator.. 12 Draw
Draw-- out PPosition
osition PPadlock
adlock (Optional).

& Spring Charge Indicator


Indicator.. 13 Key Lock.

' Close Open Indicator


Indicator.. 14 Castle Lock.

( Open PPosition
osition PPadlock
adlock (Optional). 15 D/O Operation Instruction nameplate.

) Push to Close Button. 16 Panel Gasket.

The front panel indicator provides Breaker The Panel Cutout Rubber Gasket
position indication: The shutter prevents erroneous insertion of
provides complete dust-proof
the handle. This can be opened by lowering
protection.
the position stop release lever only when the
"CONNECTED", "TEST" or Breaker is open.
"ISOLATED"
When the Breaker is closed, the release lever
can not be lowered. Thus, the shutter can not
be opened.

6
Introduction

1.3 High Breaking capacity and large short


time current capacity

! By fully utilising electromagnetic repulsive force, a large short


time current and high breaking capacity is achieved in our
light and compact design.

! Light contact springs used to provide adequate contact pressure


to keep the contact temperature well within limits and also
to avoid contact bouncing.

! A large short circuit current causes an electromagnetic


repulsive force between the contact lead halves.
! This repulsive force works in a direction to turn the moving
contact clockwise about the contact shaft, giving it more contact
pressure proportional to the short circuit current.

! When interrupting a large current, the electromagnetic repulsive


force works in a direction to separate the moving contact from
the stationary contact.

! This electromagnetic repulsive force adds to the separating


force of trip spring, resulting in a high speed interruption.

1.3.1 Complete Isolation of Poles

All the poles are completely isolated from each other as well as
from operating mechanism by high grade insulating materials. A
robust design of Arc Chute in a temperature resistant moulded
body and fitted with scientifically shaped Deion-Grids, totally
encompasses the poles.

The high short circuit arc gases thus escape through arc chute
only which clears and cools the highest short circuit arc energy
in less than 10ms. This isolation thus helps in providing highest
insulation properties as well as breaking capacity.

1.3.2 High AC dielectric withstand voltage

Due to the use of non-hygroscopic, glass fibre based insulating


materials and corrugated shape employed for better creepage
distance, the AH series can withstand a dielectric voltage of 3.5KV
for a minute.

1.3.3 Space saving & standardisation of Switchboard


design

The light and compact ACBs in 4 frame sizes not only help in T T
T T T T
standardising the Switchboard design but also reduce the size of
load centre. T T T
2300

T T T T
Four Breakers upto 1600A frame and 3 Breakers above 1600A T T
upto 4000A frame can be arranged vertically in standard height
of 2300mm. T T T T T T T

1.3.4 Highly Resistant to Vibration upto 1600AF 2000AF 3200AF

Compact Breaker leads to space saving


Smallness of each component due to rational design ensures a low in Switchboards
response factor to vibration and high natural frequency. The design
is also highly resistant to vibrations as required in ships.
7
Ratings & Specifications

2.0 Ratings & Specifications


TYPE AH-6B/D AH-8B/D AH-10B/D
AMPERES FRAME IEC,BS,VDE,AS, IS 630 800 1000
Ith + (A) JIS 600 800 1000
" JEC 600 800 1000
NEMA, ANSI 600 800 1000
Marine 600 800 1000
number of poles 2, 3, 4 2, 3, 4 2, 3, 4
RATED CURRENT OF OVERCURRENT TRIP DEVICE In (A)
for general industrial plant application 250 600 400
400 800 600
600 800
1000

for generator protection

630 < In ≤ 1000


400 < In ≤ 600
250 < In ≤ 400

400 < In ≤ 630


600 < In ≤ 800
(In is generator rated current)

RATED INSULATION VOLTAGE (Ui) AC 690/1000 690/1000 690/1000


RATED ULTIMATE BREAKING/MAKING CAPACITY
(Icu/Icm) ' at Ue(AC) 415V 50/105 50/105 55/121
RATED SERVICE BREAKING/MAKING CAPACITY
(PEAK)(Ics/Icm)# at Ue(AC) 415V 45/94.5 45/94.5 50/105
IEC with INST AC 690 V 30 / 63 30 / 63 40 / 84
600 V 35 / 73.5 35 / 73.5 40 / 84
IS 500 V 40 / 84 40 / 84 45 / 94.5
380 V 50 / 105 50 / 105 60 / 126
BS 240, 220 V 50 / 105 50 / 105 65 / 143
without INST AC 690 V 30 / 63 30 / 63 40 / 84
VDE with MCR and STD 600 V 35 / 73.5 35 / 73.5 40 / 84
upto 500 V 40 / 84 40 / 84 45 / 94.5
AS
without INST AC 690 V 30 / 63 30 / 63 30 / 63
upto 600 V 30 / 63 30 / 63 30 / 63
NEMA with INST AC 690 V 35 / 80.5 35 / 80.5 40 / 84
ANSI 480 V 40 / 92 40 / 92 50 / 105
240 V 50 / 115 50 / 115 65 / 143
without INST AC 690V 35 / 80.5 35 / 80.5 40 / 84
with MCR and STD upto 480 V 40 / 92 40 / 92 45 / 94.5
without INST upto AC 600 V 30 / 63 30 / 63 30 / 63
JIS with INST AC 550 V 35 / 73.5 35 / 73.5 45 / 94.5
JEC 460 V 40 / 84 40 / 84 50 / 105
220 V 50 / 105 50 / 105 65 / 143
without INST AC 550 V 35 / 73.5 35 / 73.5 40 / 84
with MCR and STD upto 460 V 40 / 84 40 / 84 45 / 94.5
without INST upto 550 V 30 / 63 30 / 63 30 / 63
with INST DC 250 V $ 40 / 40 40 / 40 40 / 40
OTHER RA TINGS
RATINGS
short time current RMS (kA) 1 sec [3 sec.] Icw 45 / [25] 45 / [25] 50 / [25]
total breaking time % 30 30 30
RATED CLOSED TIME
stored energy spring charging time (sec.) max. 10 10 10
close time (m sec.) max. 40 40 40

" Rated thermal current in open Air.


# Higher breaking capacity ACBs available on request.
$ DC rating is of special application.

8
Ratings & Specifications

AH-12B/D AH-16B/D AH-20C/D AH-25C/D AH-30C/D AH-40C/D AH-50C AH-60C


1250 1600 2000 2500 3200 4000 5000 6300
1250 1600 2000 2500 3200 4000 5000 6150
- 1300 1850 2150 3100 3650 5000 5300
1200 1550 1950 2250 3200 4000 5000 6150
- 1600 2000 - 3000 4000 5000 6000
2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4

1250 400 800 2500 2000 4000 5000 6300


600 1000 2500
800 1600 3200
1000 2000
1600
1000< In ≤ 1600

2000 < I n ≤ 3200


400 ≤ In ≤ 1000

800 ≤ In ≤ 1000

1600<In ≤ 2000

In ≤ 4000

In ≤ 6300
In ≤ 2500

In ≤ 5000
In ≤ 1250

690/1000 690/1000 690/1000 690/1000 690/1000 690/1000 690/1000 690/1000

55/121 55/121 60/132 65/143 75/165 100/200 100/200 120/264

50/105 50/105 50/105 50/105 65/143 85/187 85/187 100/220


40 / 84 45 / 94.5 30 / 63 30 / 63 50 / 105 65 / 143 65 / 143 85 / 187
40 / 84 45 / 94.5& 45 / 94.5 45 / 94.5 65 / 143 75 / 165 75 / 165 85 / 187
45 / 94.5 50 / 105 50 / 105 50 / 105 65 / 143 85 / 187 85 / 187 100 / 220
60 / 126 65 / 143 65 / 143 65 / 143 65 / 143 100 / 220 100/220 120 / 264
65 / 143 65/ 143 65 / 143 65/ 143 75 / 165 120 / 264 120 / 264 120 / 264
40 / 84 45 / 94.5 45 / 94.5 45 / 94.5 50 / 105 65 / 143 65 / 143 85 / 187
40 / 84 45 / 94.5 45 / 94.5 45 / 94.5 65 / 143 75 / 165 75 / 165 85 / 187
45 / 94.5 50 / 105 50 / 105 50 / 105 65 / 143 85/ 187 85/ 187 100 / 220
30 / 63 30 / 63 30 / 63 30 / 63 42 / 88.2 60 / 132 60 / 132 70 / 154
30 / 63 30 / 63 35 / 73.5 35 / 73.5 42 / 88.2 60 / 132 60 / 132 70 / 154
40 / 84 45 / 103.5 45 / 103.5 45 / 103.5 65 / 149.5 75 / 165 75 / 165 100 / 230
50 / 105 50 / 115 50 / 115 50 / 115 65 / 149.5 85 / 187 85 / 187 120 / 230
65 / 143 65 / 149.5 65 / 149.5 65 / 149.5 75 / 172.5 100 / 220 100 / 230 120 / 276
40 / 84 45 / 103.5 45 / 103.5 45 / 103.5 65 / 149.5 75 / 165 75 / 165 85 / 187
45 / 94.5 50 / 115 50/ 115 50 / 115 65 / 149.5 85 / 187 85 / 187 100 / 230
30 / 63 30 / 63 35 / 80.5 35 / 80.5 42 / 96.6 60 / 138 60 /138 70 / 161
45 / 94.5 45 / 94.5 45 / 94.5 45 / 94.5 65 / 143 85 / 187 85 / 187 100 / 230
50 / 105 50 / 105 50 / 105 50 / 105 65 / 143 85 / 187 85 / 187 100 / 230
65 / 143 65 / 143 65 / 143 65 / 143 75 / 165 100 / 230 100 / 230 120 / 300
40 / 84 45 / 94.5 45 / 94.5 45 / 94.5 65 / 143 85 / 187 85 / 187 100 / 230
45 / 94.5 50 / 105 50 / 105 50 / 105 65 / 143 85 / 187 85 / 187 100 / 230
30 / 63 30 / 63 35 / 73.5 35 / 73.5 42 / 88.2 60 / 132 60 / 132 70 / 154
40 / 40 40 / 40 40 / 40 40 / 40 40 / 40 40 / 40 40 / 40 40 / 40

50 / [25] 50 [45] 50 [50] 50 [50] 65 [65] 85 [70] 85 [70] 100 [70]


30 30 30 30 30 30 30 30

10 10 10 10 10 10 10 10
40 40 40 40 40 40 40 40
% Values when fitted with magnetic type instantaneous trip.
0.05 seconds for solid state instantaneous trip.
& AH-16C suitable for 50 KA breaking capacity at 600V AC also available on request.
' Rated service breaking capacity & rated ultimate breaking capacity are same at all other voltages except at 415V.
9
Ratings & Specifications

2.1 Conventional free air and enclosed


current ratings

The thermal current ratings “Ith” of Circuit Breakers c) Cross sectional area of the bus bars connected
shown in ratings & specifications table on to the Breaker terminals.
page No. 8 are free air ratings i.e. in open
d) Ambient temperature other than 40oC
execution at 40 oC ambient. The thermal ratings of
the Circuit Breaker when mounted inside an enclo- For ease of selection of our Breaker, keeping above
sure depend upon: factors into consideration, the thermal current ratings
a) The dimensions of the cubical in which the (I th ) in an enclosure having ventilation &
Breaker is mounted. recommended ambient temperature are shown in
b) Ventilation area provided by way of louvers in the table below:
the Breaker cubicle.

S. Open Air With no Ventilation With Ventilation


Ventilation Min. enclosure dimensions (mm)
No. Rating
At 40 C At 50 C At 40 C At 50 C area cm sq. Width Depth
o o o o
Height

1. 630 930 850 950 880 600 575 575 550


2. 800 930 850 950 880 600 575 575 550
3. 1000 1100 1010 1140 1040 600 575 575 550
4. 1250 1300 1180 1350 1250 600 575 575 550
5. 1600 1530 1420 1600 1480 600 575 575 550
6. 2000 2030 1850 2200 2010 1000 700 766 620
7. 2500 2330 2130 2540 2320 1000 700 766 620
8. 3200 3280 3050 3620 3380 1250 800 766 700
9. 4000 3820 3480 4270 4000 1250 800 766 700
10. 5000 4370 3990 5280 5000 1600 1000 800 770
11. 6300 5150 4800 6150 5750 1600 1000 800 770
Note

1. The above enclosed thermal current ratings (Ith) have 2. C & S may be consulted, for thermal current ratings
been based when the Breaker Terminals are connected in Enclosure with less ventilation area other than
with copper or aluminium bus bars of cross sectional shown in the above Table or at different ambient
area as indicated in Table XI of IEC 947-2 & IS temperatures.
13947-2.

2.2 Application

2.2.1 AC System

! 3 pole ACB for Industrial & Generator ! 3 pole ACB with 2 poles connected in series
application. can be used in DC system where the short
circuit breaking capacity requirement is
! 4 Pole ACB for complete safety in 3 phase 4
comparatively high.
wire distribution system as the neutral pole of
4 pole ACB closes earlier & opens later than ! A 4 pole ACB with 2 poles connected in parallel
other phase poles, thus effectively preventing can be used where the short circuit breaking
transient overvoltages on loads connected capacity requirement is low but the thermal
between live & neutral lines. current rating is high. (For this application, the
neutral pole closes alongwith the phase poles).
2.2.2 DC System
Please clearly specify 4 pole ACB for DC
! 2 pole ACB can be used on DC system where application.
the short circuit breaking capacity requirement
is not very high.
10
Ratings & Specifications

2.3 A Wide Selection of Specifications

Various specification are available for wide selection to suit any particular application as well as local regulations
and requirements.

ITEM SELECTION AT Y
AT OUR OPTION
YOUR

1 Breaker 630 A 1000 A 2000 A 3200 A 5000 A


Rating 1250 A
800 A 1600 A 2500 A 4000 A 6300 A

▼ ▼ ▼
2 Types of Draw-out type Metalclad
Mounting Fixed type
(standard) construction
▼ ▼
Accessories for , Safety shutter , Position switch , Short-circuiting contact
3
draw-out type , Mal-insertion prevention device , Lifter , Test jumper

▼ ▼
4 Types of closing
Manual charging type Motor charging type
operation
Power transformer
Accessories for Spring charged switch
5
closing operation
▼ ▼
Micro processor based Thermal Magnetic type

6 Overcurrent
trip ▼ ▼ ▼
for General for generator for General
Devices Industrial Plant
Industrial Plant Protection
Adjustable L.T.D. Adjustable L.T.D. Adjustable L.T.D.
Adjustable S.T.D. Adjustable S.T.D. Non adjustable INST.
or
* L.T.D. means Long Adjustable INST. Non adjustable INST.
Making current release
Time Delay Adjustable or
Making current release
* S.T.D. means Short Ground-fault
Time Delay Non adjustable INST.
or
Making current release

▼ ▼
OCR Alarm switch OCR Alarm switch
Accessories for DC24V power supply
7
overcurrent OCR checker
trip device CT for Neutral line

▼ ▼ ▼
Shunt trip Capacitor trip Undervoltage trip
With or without T.D.
8 Other trips

Trip indication switch

9 Other

accessories
Close-open cycle counter

▼ ▼
Key lock / Castle lock Key interlock system

▼ ▼
C - Series D - Series

10 Types &
series of Air Circuit Breaker is assembled to comply with your specifications
Breaker
Note : Tropicalisation, cold climate treatment available on request at extra cost.

11
Multi-Function Protection Devices

3.0 Multi Function Protection Devices

3.1 Microprocessor Based Overcurrent Trip Device: “Type µIT”


µ IT is a true RMS sensing overcurrent trip device, requiring no external supply for its
basic function. It is available in two types, i.e., µ IT –100 for industrial application and
µ IT –G for generator protection.

Salient Features

! Error free and user friendly setting


" of current and time delay.
# ! Provides highest degree of system
protection coordination.
11 $ ! Self powered by the built in current
+ % transformer.

' & ! No mal-operation due to external


disturbances.
( ! Built in operation check function.
) ! Visual fault discrimination by LEDs.
*
! Three phase and earth fault in one
single compact unit.

! Self monitoring of trip unit with


blinking indication.
µ IT - 100
! Function Blocking facility provided.
" Overload (L.T.D.) current setting DIP switch. ! Certified by ERTL for
# Overload (L.T.D.) tripping time setting DIP switch. – Damp Heat Test IS 9000-PG4
$ Short circuit (S.T.D.) current setting DIP switch. – Dry Heat Test IS 9000-PG3
% Short circuit (S.T.D.) tripping time setting DIP switch. – Vibration Test IEC255-4

& Instantaneous short-circuit current setting DIP switch. – Radio Frequency


Interference (RFI) IEC801-3
' Earth fault tripping current setting DIP switch.
– Electrostatic Discharge
( Earth fault tripping time setting DIP switch. (ESD) IEC 801-2

) Built-in operation checking DIP switch. – Electrical Fast Transient


(EFT) IEC 801-4
* Function blocking DIP switch.
– Surge IEC 801-5
+ Reset switch.
– Impulse IEC 255-4
11 LED Indicators.

Note : µIT-G is similar to µ IT-100 in construction and function but differs in current and time settings
of LTD & STD.

12
Multi-Function Protection Devices

Characteristic Curves µIT-100 (For Industrial Applications)

3.1.1 Setting of Over Load Current 3.1.3 Setting of Instantaneous Current


(LTD)
Current ( I N S ) : Minimum setting 4xI n
L T D C u r r e n t : Minimum setting is 0.5 times I n
Setting Ranges: 4, 5, ... 11
Setting range: 0.5, 0.55 ...1.15
(in steps of 0.05) (in steps of 1)

3.1.4 Function Blocking


LT D T i m e : Minimum Setting - 2.5 sec.
Delay Setting range: 2.5, 5 ....... to 35 sec. In normal running operation of unit or in test
(in steps of 2.5 sec.) mode any of the four function can be blocked
by turning the DIP switches to ON position.

3.1.2 Setting of Short Circuit Current


(STD) 3.1.5 Ground Fault Setting (GFT)

STD C u r r e n t : Minimum setting 4 x In GFT Current: Minimum Setting 15% of I n


Setting range 4, 5 ... 10 (in steps of 1) Setting Range 15, 20, ... 50 %
(in steps of 5%)
STD Time: Minimum Setting 50 ms
GFT Time: Minimum Setting 50 ms
Delay Setting Range 50, 100, ... 550 ms.
Delay Setting Range 50, 100, ... 550 ms
(in steps of 50 ms)
(in steps of 50ms)

13
Multi-Function Protection Devices

Characteristic Curves µIT-G (For Generator Applications)

3.1.6 Setting of Over Load Current


(LTD)

L T D S e t t i n g s : a)Minimum setting is 1 times I n LED Indication


S e t t i n g R a n g e : 1 to 1.3 In (in steps of 0.05)
ON - LED : This will indicate normal operation of unit.
b) Time = 15 to 65 sec at 120% In
min. settings 15 sec (in steps of 5 sec.) - All the other three LEDs will glow on their respective faults.
- Reset switch is given to reset the LEDs.
S T D S e t t i n g s : a ) Current = 2 to 5.75In
(in steps of 0.25)
b) Time = 50msec. to 420msec. Setting Example LTD Time = 25 Sec.
(in steps of 50 msec.) X = 2.5
DIP Switch Position
a = 2.5
3.1.7 Test Mode OFF b = 5
by 24V DC for testing the trip unit without injecting current c = 10
Step 1: Put the DIP switch to TEST POSITION ON d = 15
Step 2: Put the LONG or SHORT switch to ON
t = X+(a+b+d)
position. LTD Current IO =1.25*In
25 Sec = 2.5+(2.5+5+15)
µIT will give trip command depending X = 1.0
upon the time set on respective LTD or STD
a = 0.05 I = X+(a+c+d)
time delay DIP switches. O

CAUTION : In normal running condition all the Test Mode b = 0.05 1.25 = 1.0+(0.05+0.1+0.1)
When X - min. value
DIP switches should be in OFF position (Normal position) c = 0.10
abcd - settings
d = 0.10

14
Multi-Function Protection Device

3.2 Economical Thermal Magnetic type 3.2.1 Base Current (In) (for Microproces-
sor & Thermal Magnetic Types)
! A direct acting electromagnetic instantaneous ! M i c r o p r o c e s s o r TTyy p e a n d T h e r m a l
trip device with fixed current setting for short Magnetic TType ype both have a single base
circuit protection. current that corresponds to one of the rated
currents available. When ordering, specify the
! CT actuated thermal O/L Relay used along with
base current (I n) that is higher than and closest
Shunt Trip or Undervoltage Trip Device for
to the rated load current passing through the
O/L protection
Air Circuit Breaker.
! Hall sensor actuated over load protection for
DC application can also be provided.

! Trip testing at CT secondary current levels.

Type Base Current (I n ) [A] Type Base Current (I n ) [A]

of Thermal of Thermal
Microprocessor Magnetic Microprocessor Magnetic
ACB Type Type ACB Type Type

250 250 800 800

1000 1000
AH-6D 400 400
1600 1600
600 600
AH-20D 800 800
AH-8D 600 600
1000 1000
800 800 1600 1600

400 400 2000 2000

AH-10D 600 600 AH-25D 2500 2500

AH-30D 2000 2000


800 800
2500 2500
1000 1000
3200 3200
AH-12D 1250 1250
AH-40D 4000 4000
400 400 AH-50C 5000 5000
AH-16D 600 600 AH-60C 6300 6300

15
Multi-Function Protection Devices

3.2.2 Current Setting of the nonadjustable magnetic instantaneous trip


and MCR
Applicable Breaker AH-6D AH-10D AH-20D AH25D AH-30D AH-40D AH-60C
AH-12D AH-50C
AH-16D

NI Instantaneous Trip Device 3 5 # 7.5 7.5 10 10 10


5 " 7.5 10 10 15 15 15
7.5 " 10 15 15 20 20 20
ELECTROMAGNETIC

10 " 15 20 20 25 25 25
* Select and specify one of the 15 " 20 30 30 30 30 30
pick-up currents from the 20 " 25 40 40 40 40
table 50 50 50
* Tolerance is + 20% 60

MCR Making Current Release 3 5 # 7.5 7.5 10 10 10


5 " 7.5 10 10 15 15 15
7.5 " 10 15 15 20 20 20
* Select and specify one of the 10 " 15 20 20 25 25 25
pick-up currents from the 15 " 20 25 25 30 30 30
table 20 " 25 40 40
* Tolerance is + 20% 50 50

Note : " : Applicable where the rated current of overcurrent trip devices is not less than 250A.
# : Applicable to AH-10D and AH-12D.

3.2.3 Making Current Release (MCR)

MCR instantaneously trips the Breaker without any A short time delay tripping ACB fitted with MCR can
intentional time delay during closing operation, if the thus utilise its full particular time capacity by forming
making current exceeds a predetermined value and a selective tripping system with the other Breaker
which is rendered inoperative when the Circuit and can rapidly clear the faulty circuit without any
Breaker is in closed condition. When the Breaker time delay when the Operator attempts to close it.
is closed on to a normal circuit condition, MCR
becomes inoperative affecting normal coordinated
system protection, thus most suitable for incomer
Breaker.

How MCR Operates


MCR
MCR Inoperative Operative MCR Inoperative

Short-circuit current may flow

Closing Process Closed Condition

Contacts Start to Arcing Contacts Main Contacts Latched in


move Close Close

Closing Stroke

16
Multi-Function Protection Devices

3.3 Accessories for Overcurrent Trip Devices

3.3.1 OCR Alarm Switch

This switch operates when the Air Circuit


Breaker is tripped by the overcurrent device. , Ratings
Any of LTD, STD, INST or earth-fault trip Number of contacts 1a
Circuitry Resistive L a m p Inductive Motor
causes operation of this OCR alarm switch.
Rated 480V 3 0.3 2 0.4
current (A) AC 250V 5 2 5 3
Its operation is as follows : normally OFF, 125V 5 3 5 4
ON for about 30 ms during ACB contact 250V 0.3 0.05 0.3 0.05
DC 125V 0.6 0.1 0.6 0.1
separation, then OFF again. Use a suitable
30V 7 4 6 4
self-hold circuit for continuous OCR trip
alarm indication. , “Lamp” is a resistive load of positive temperature coefficient with
inrush in excess of 10 times the normal current.

3.3.2 2 4 V DC Power Supply , “Inductive” is a load whose power factor is 0.4 or more (AC)
or time constant is 7 ms or less (DC)
(To be fitted in the PPanel)
(To anel) , “Motor” assumes starting current of 6 times the specified value.

! Supplies 24V DC power to the micro-


processor over-current trip device for :
- device function check purposes and
- for lighting the OCR trip indicators
(LEDs).

3.3.3 OCR checker (outside)

Type : RCU - 2
Power : 500VA, 50/60Hz 240V
Consumption
Dimension Drawing of 24V DC Power Supply Unit
Test : i) Calibration of current Functions
& time settings of
LTD, STD, Instantenous &
Ground Fault
ii) Function Check
by 24V DC.
iii)Closing Opening
time of ACB
Dimensions : 545W x 420D x 345H
Weight : 28 kg

OCR Checker
3.3.4 Phase & Neutral CTs

Polyester resin cast 5A secondary, 5VA, class 5P10 precision CTs are rigidly mounted on the lower terminals
of the Breaker. The CTs thus provide most reliable and accurate current signals to the protection devices
even in adverse environmental conditions.

The CT used for detecting a neutral line current in a 3 pole Breaker of a 3 phase four wire system,
is mounted outside on the neutral bus bar. This CT is necessary when over current trip device is having
a ground fault protection element.
However, in a 4 pole Breaker, the neutral CT is rigidly mounted on the neutral terminal of the Breaker.

17
Spring Charging Operations

4.0 Spring Charging Operations

4.1 Charging of Springs Manually

The closing springs are manually charged by pumping With the Breaker closed, the Motor automatically
the charging handle. When PUSH TO CLOSE button starts to charge the spring again for the next closing
is pressed, the charge of the closing springs is operation.
released, quickly closing the Breaker.
Manual charging is also possible in Motor charging
A closing coil (Latch Release Coil-LRC) can be type.
provided for remote closing operations, however,
the closing springs would have to be charged
manually before doing a remote close operation.

4.2 Charging of Springs by Motor

The closing Springs are charged by an Electric


Motor. A closing command from an external “Push
Button” energises the LRC (Latch Release Coil) which
releases the charge of the closing spring to quickly
close the Breaker.
Motor Charging type

4.3 Rating of Motor charging -Spring release type

Rated voltage (V) Min. And Max. Inrush current (A) Steady-state current Charging Closing Command
50/60 Hz Operating Voltage (peak value) (AC:RMS value) time (S) current (A) Max.

- Applicable Breakers : AH-6D, AH-10D, AH-12D, AH-16D

AC 200~230 170~255 9.6(220V) 1.0(220V) 4.0(220V) 2.7(220V)

100~115 85~130 4.7(110V) 0.8(110V) 6.0(110V) 4.0(110V)

D C 200~220 150~250 2.8(200V) 0.7(200V) 4.0(200V) 1.7(200V)

100~110 75~125 3.2(100V) 0.8(100V) 6.0(100V) 2.7(100V)

- Applicable Breakers : AH-20D, AH25D, AH-30D, AH-40D, AH-50C, AH-60C

AC 200~230 170~255 21(220V) 1.0(220V) 3.5(220V) 2.7(220V)

100~115 85~125 8.5(110V) 0.8(110V) 5.0(220V) 4.0(110V)

D C 200~220 150~250 9.6(200V) 0.6(200V) 4.0(200V) 2.7(200V)

100~110 75~125 8.0(100V) 0.5(100V) 6.0(100V) 2.7(100V)

Note :
. The charging motor is of short-time rating and the number of repeated open close cycles must
be limited to 15 cycles followed by a cooling period of at least 20 minutes for further operations.

18
Spring Charging Operations

4.4 Motor Charging And Closing Operation Circuit

4.4.1 Charging of Closing Springs

! When the closing springs are "DISCHARGED", ! With the release of Closing Spring charge, the
the “spring charged OFF” switch in series with “Spring Charged On Sw” opens and the supply
the motor, is closed. to the LRC is cut OFF through the Aux.Sw.B1
Contact which opens when the ACB gets closed.
! Control voltage is applied to terminals 1 and
2 and the motor starts to charge the springs.
4.4.3 Anti-Pumping Function
! When the closing springs are fully charged, the
“spring charged OFF” switch in series with the ! Once the closing spring have been released the
motor opens and cuts the supply to the motor. “ACB Reset OFF” switch is closed. If a closed
signal is continuously applied across the
4.4.2 Closing the ACB terminals 2 and 3, the holding relay (HC) is
energised and self holds when the HC/1 contact
! When the springs are charged, the "spring closes.
charged ON switch" in series with the LRC is
! The HC/2 contact opens, cutting the supply to
closed.
the LRC, ACB can not reclose without opening
! Apply voltages across terminals 3 and 4 the PB (Close).
through PB (close). The latch release coil (LRC)
is energised and the closing springs are
released to close the ACB.

Closing Operation Circuit


M Charging motor

LRC Closing Latch Release

HC Anti Pump Relay of ACB

B1 Aux. Switch of ACB

PB Control Switch

Isolation Contact

Circuit Diagram:- Closing Circuit

! The circuit may be separated into a ! When ACB is fitted with under voltage trip UVT
closing control and a motor circuit on and tripped by it (voltage below opening value).
request, so that they can be individually
energised. ACB will not reset until voltage above resettable
value is supplied to UVT.

! The diagram shows the condition when closing


springs are uncharged and ACB is tripped (not
reset yet).

19
Electrical Tripping

4.5 Accessories For Closing Operation

4.5.1 Power Transformer Outside 5.3 Undervoltage Trip

When the control supply voltage is higher than The undervoltage trip automatically opens the Air
230V AC, our special Step Down Transformer or Circuit Breaker when the voltage supplied to it drops
a 350VA Transformer with 220V secondary should below the opening voltage. It resets automatically
be used for electrical charging operation. on recovery of the supply voltage above the
resettable value, and allows for closing of the Air
4.5.2 Spring Charged Switch Circuit Breaker. The undervoltage trip consists of an
undervoltage trip device built-in the ACB and UVT
Provides a NO (1a) contact signal, which is closed Control Device installed external to the ACB .
when the closing springs are fully charged. Used
for indication at a remote place, from where
closing is made.

Ratings

250V AC - 15A, 250V DC - 0.25A


480V AC - 5A, 125V DC - 0.5A

5.0 Electrical Tripping Undervoltage Trip

5.1 Shunt Trip


Shunt Trip Rated Voltage (V) Min & Max. Excitation
Type 50/60 (Hz) Operating Voltages (V) Current Peak
The shunt trip device is used to electrically
open or trip the Air Circuit Breaker from AC 420-480 250-600 1.8 (415V)
a remote place. The tripping commands 380-420 220-530 1.9 (380V)
AVH-S 180-250 100-320 2.7 (220V)
to the shunt trip include those from an
100-150 60-190 4.0 (110V)
overcurrent relay, reverse power relay,
and similar protective relays. DC 150-230 90-290 2.2 (220V)
90-120 50-150 2.5 (110V)
24 14-30 8.1 (24V)
Note that the shunt trip uses one
48 28-60 5.1 (48V)
“a”-contact of the auxiliary switch.

5.2 Capacitor Trip , Rating : Capacitor Trip


Type
The shunt trip device will not work when power
supply (AC) of the trip equipment is disconnected Rated voltage (V) AC 110V/220V
or when the voltage drops due to some kind of Rated frequency (Hz) 50/60
short circuit accident. In such a case the capacitor Using type AVH-1
trip operates to trip the Air Circuit Breaker. For
capacitor tripping, the shunt trip device is necessary.

Even in case when capacitor tripping is used it is


possible to open the Air Circuit Breaker when the
overcurrent relay or low voltage relay operates.
Capacitor trip is installed external to the Air Circuit
Breaker but can be fitted inside the switchboard.

Capacitor Trip

20
Electrical Tripping

5.5 UVT Control Devices

Three Types of Control Devices are available

! Type AUH-V is without time-delay, and is used ! Type AUH-1SC is without time delay and is
for AC supply. It trips the ACB immediately on suitable for DC supply only.
dropping of the supply voltage below the ! The undervoltage trip, when in operation with
opening value. supply voltage below resettable value, keeps
! AUH-V-T is also for AC supply but with a time- the closing control circuit open and locks out
delay of 500 ms. It effectively prevents the the PUSH TO TRIP button.
overiding of the short time delay over current
trip function caused by short circuit fault &
simultaneous voltage drop.

AC - rated Undervoltage Trip Control Circuit DC - rated Undervoltage Trip Control Circuit

Under Rated Voltage (V) Opening [resettable] Excitation


Vo l t a g e Ty p e 50/60 (Hz) Vo l t a g e s ( V ) Current Peak

A C 401-429 165-205 (330) 0.1 (415V)


200-240 88-110 (170) 0.1 (220V)
AUH 100-120 44-55 (170) 0.1 (110V)

DC 200 80-100 (170) 0.1 (200V)


100 40-50 (85) 0.1 (100V)

21
Type of Mounting

6.0 Types Of Mounting


6.1 Fixed Type 6.4 Draw out type

This consists only of the Circuit Breaker fitted with This consists of a Circuit Breaker and a draw-out
brackets to enable it to be permanently mounted cradle. The Circuit Breaker can be withdrawn to any
inside the Panel and the bus bars are directly of the four draw out positions i.e. "CONNECTED",
connected to its terminals. "TEST", "DISCONNECTED" & "REMOVED".
The Circuit Breaker body is kept connected to earth
6.2 Metal Clad Type through earthing shoes to the draw out frame in
"CONNECT", "TEST" or in between to provide total
The metal clad type consists of a fixed or draw out safety to the Operator. The Panel door can be kept
Circuit Breaker housed in a steel enclosure. This closed in "CONNECTED", "TEST" & "DISCONNECTED"
can be used as a single pole mounted ACB or can position.
be readily constructed in a load centre by simply
placing them one upon another in a tier
arrangement.

6.3 Lifter

A Sleek Lifter with variable size loader to suite all


sizes of ACB or with a platform for safely handling
the Breaker in plant or for mounting or removing
them from the panel are available

Lifter

22
Type of Mounting

6.5 Accessories (Optional) for Draw-out Breaker

The following types of accessories are available for


draw-out type Air Circuit Breaker.

6.5.1 Safety Shutter

! When the Breaker is drawn out, it protects Safety Shuter


the operator from accidental contact with the
live parts by automatically concealing the
main circuit on the draw-out frame side with
insulating barrier.
! The shutter has a tamper proof lock
mechanism. As the Breaker is inserted into the
draw-out frame, it unlocks automatically to
free the shutter and the shutter opens.
! The shutter can be padlocked in the shut
position.
! Labels, "BUSBAR" and "CIRCUIT", are supplied
to indicate the line-side and load-side main
circuit terminals, respectively, and they are to 6.5.4 Test Jumper
be affixed by the user.
The test jumper allows checking of all functions on
6.5.2 Position Switch the removed Breaker on a Test Bench and can be
supplied on request.
There is 1NO contact to indicate the "TEST" position
and 1NC contact to indicate the "CONNECTED" 6.5.5 Mal-Insertion Prevention Device
position.
A good interchangeability exists in the C&S -Air
Ratings Circuit Breakers and because of this feature, there
is a possibility for a Breaker of a different rating
250V AC - 15A, 250V DC - 0.25A being placed into the cradle of other rating. This
480V AC - 5A, 125V DC - 0.5A is effectively prevented by the use of the Mal-
insertion Prevention Device.
6.5.3 Short-Circuiting Contacts

The short-circuiting contact shorts out the associated


auxiliary switch b-contact when the Breaker is in the
test position or further out position. Therefore, the
b-contact circuit with this short-circuiting contact
remains closed even when the Breaker is closed at
the test position.

This contact is useful when forming an interlock


circuit with another Breaker or Breakers or when
preventing the test operation at the test position from
causing any unwanted operation in the associated
circuit.

The short-circuiting contact is open when the Breaker


is in the connected position, and it can be fitted
in parallel with any of the auxiliary switch circuits,
B2, B3, B4 and B5.

23
Other Accessories

7.0 Other Accessories


7.1 Auxiliary Switch

The auxiliary switch is an assembly of auxiliary contacts , R at i n g s : Aux. Sw i t c h C on t ac t s


mechanically operated by the Air Circuit Breaker to
electrically indicate whether the Breaker is closed or open. Ty p e AXH-1
Numbers of contacts 5a 5b
Every Air Circuit Breaker is fitted with an auxiliary
switch. The Aux. Sw Contacts can be provided in Rated current (A) AC 450V 7

following combinations and out of which some contacts AC 220V 7


are utilised for various accessories fitted in Breaker AC 110V 7
as shown in the table. DC 250V 2.5
DC 125V 4
7.2 Combination of Aux. SW Contacts

Aux Sw Auxiliary Contacts Used

14 way 7-a-contact and 7-b-contacts (7a, 7b)


Accessory Fixed Draw-out
10 way 5-a-contact and 5-b-contact (5a, 5b)
Charging Motor 1b 1b
5 way 3-a-contacts and 2-b-contacts (3a, 2b)
Shunt Trip / UVT 1a 1a
or
Over Current Trip Device 1a 1a
2-a-contacts and 3-b-contact (2a, 3b)
Metal Clad - 1a, 1b
7.3 Trip Indication Switch

This switch closes (ON) when the Air Circuit Breaker is Cause of Operation Resetting Condition
tripped by overcurrent trip, shunt trip, undervoltage trip or
Overcurrent trip-shunt trip
manual operation of PUSH TO TRIP buttons. Turn OFF on completion of
Remote spring charging
opening
The table shown summarizes when the trip indication switch
Undervoltage Turn OFF on recovery of
operates (ON) and when it is reset (OFF). trip Undervoltage
voltage above resettable
below opening
value and on completion of
Use a suitable self hold circuit as necessary for continuous value
spring charging
trip alarm indication. PUSH TO TRIP Turn OFF on completion of
button pressed spring charging after release
of button
7.4 Key Lock & Castle Lock *Rating of TIS are same as of OCR Alarm SW

It locks the Breaker in CLOSED or OPEN position, and a


key is necessary to unlock so that only the authorised
operator can operate the Breaker and prevent it from being
operated by unauthorised persons.

Key Lock
! LOCK-IN-OPEN TYPE
Locks the Breaker in open position.
! LOCK-IN-CLOSED TYPE
Locks the Breaker in CLOSED position.
(Specify either type when ordering).

Castle Lock
! A device that is ready for use, when a Castle key
lock is fitted is also available (specify type of Castle Key Lock Castle Lock
lock when ordering).

24
Other Accessories

7.5 Key Interlock System

A system of key locks used to interlock a number of


Breakers.

The key is removable only when the Circuit Breaker


is locked open.

! Application Example

Breaker 3 cannot be closed


Incoming power Breakers 1 and 2 feed two bus
sections, which are connected by a bus-tie-Breaker-3.

When the bus-tie Breaker is closed, parallel feeding


with both Breaker 1 and 2 closed should not be
possible.

In this case, the same-numbered locks are fitted in


all the 3 Circuit Breakers and only two keys are used,
so that the bus-tie Breaker can be closed only when
Breaker 2 cannot be closed
either the Breaker 1 or 2 is locked in the open position
and that the Breakers 1 and 2 can be closed only
when the bus-tie Breaker is locked open.

A key lock device that is ready for use when a Castle


key lock (to be provided by the user) is fitted, is also
available.

7.6 Padlocking for user safety


Breaker 1 cannot be closed
Circuit Breakers are provided with Padlocking facility
on push to Trip & Push to Close button to avoid
accidental operation of breaking by unauthorised
persons.

The padlocking arrangement has also been provided


in drawout Breakers in all the 3 positions i.e.
"CONNECT", "TEST" & "DISCONNECT" positions. This
not only provides additional safety to the Operator
but also prevents the Breaker dislocation due to
vibration and shocks.

7.7 Operation Counter

A four digit mechanical counter can be fitted with


display window on the front panel to show the
number of operations and to facilitate routine
maintenance after specified number of operations.

Padlock Facility

25
Other Accessories

7.8 Mechanical Interlock

Two Breakers can be mechanically interlocked. The


Mechanical Interlock is available to any combination
i.e. in a vertical or horizontal arrangement between
any frame size in fixed or drawout version.

Horizontal Type Vertical Type

7.9 Door Interlock

The door interlock prevents the switchboard door


from being opened when the Breaker is CLOSED.

The door is operational only when the Breaker is


OPEN. It is also fitted with a lock release. Installation
of the door interlock requires a simple drilling of
the Switchboard Panel door.

7.10 Lifting Plate

For use with hooks, ropes etc. when lifting the


Breaker.
Carrying Handle

7.11 Carrying Handle

For the purpose of lifting by hand.

7.12 Door Flange

Provided with D-Series ACB‘s to cover the panel cut-


out of the board.

7.13 IP Cover

Mounted on the Switchboard Panel door to provide


IP55 degree of protection as defined in IEC529.
IP Cover

26
Power Consumption

8.0 Multivolt drop, power consumption, (per pole)

Multivolt frop Power consumption


Model No. & Type per phase (W) (Max)
(mv) (Max)

AH-6D fixed type 4.8 17.2


AH-8D
} draw-out type 8.04 28.2
AH-10D fixed type 3.0 30.0
AH-12D
} draw-out type 5.0 60.0
AH-16D fixed type 2.4 61.4
draw-out type 4.08 104.4
AH-20D fixed type 1.8 72.0
draw-out type 3.0 120.0
AH-25D fixed type 1.44 90
draw-out type 2.40 150
AH-30D fixed type 1.32 134.4
draw-out type 2.28 235.0
AH-40D fixed type 0.96 169.0
draw-out type 1.8 288.0
AH-50C draw-out type 1.6 350.0
AH-60C draw-out type 1.2 430.0

8.1 Special Environment Specs. 8.1.2 Anti-Corrosion Treatment

If the Breakers are to be used under abnormal This treatment is recommended when Breakers are
environmental conditions, specify the applicable to be used in highly saline atmosphere or in chemical
treatment given below : plants.

8.1.1 Moisture Treatment 8.1.3 Cold Climate Treatment

This treatment is recommended for Breakers which This treatment is provided when the Breaker is to
are to be used in areas where both temperature be used in very cold areas i.e. Storage - 40 oC, Use
& humidity are higher i.e. Ambient temperature -25 oC Provided no condensation or freezing.
60 oC or less & relative humidity 95% or less
provided no condensation.

27
Clearance

9.0 Clearance Above Arc Chute, Maintenance Space


Clearance above Arc chute, maintenance space

Arc gases expel out from the arc shown below in reference to the from the Breaker bottom level.
chutes when the Breaker interrupt Breaker bottom level. If the For fixed type air circuit Breakers,
a short circuit fault current. It is provision of such distance is also, provide a sufficient
therefore necessary to keep the impracticable, then provide a maintenance space around the
area above these arc chutes clear barrier of heat and flame resistant beaker.
of any metallic objects, including insulating material and of sufficient
If an arc barrier is provided within
electric devices and earthed size to cover all arc chutes at the
the recommended maintenance
structures, at least by the distance position indicated also as minimum
space, make the Breaker
removable.

12345678901
12345678901
12345678901 Metallic Structure / Electric Devices
Heat/Flame Resistant Insulating Plate

28
29
Outline Dimensions

10.0 Outline Dimensions and Panel Mounting Details (in mm)


For AH-6D to AH-16D

Note: N is neutral pole of 4-pole breaker.

DRAW-OUT TYPE

PANEL CUTOUT CL (3P) (4P)


HL

295 265

505
247

227

120
105
98

108

158(3P)
158 258(4P) Mounting holes 4-ø10
Projection of the mounting
215(3P) bolt into the draw-out cradle
215 332(4P) should be 13mm max.
(max.) (max.)

FIXED TYPE Note: N is neutral pole of 4-pole breaker.

PANEL CUTOUT
HL H
L (3P) (4P)

295 265

N
487

Terminal blocks for control


247

227

23.2 circuits (Left,Right)


Screw M4
135

120
80

105
90

15
12

184(3P) Mounting holes 2-ø10


184 284(4P)
199(3P)
199 299(4P)

30
Outline Dimensions

Dimensions of
Metalclad Construction
(3P)

WEIGHT (kg)

575
TYPE AH-6D/8D AH-10D AH-12D AH-16D
No.OF POLES 3 4 3 4 3 4 3 4
MOTOR CHARGING DRAW-OUT TYPE 80 100 82 102 82 102 85 110
TYPE FIXED TYPE 58 74 60 80 60 80 62 86

60
MANUAL CHARGINGDRAW-OUT TYPE 76 95 78 98 78 98 80 105

0
55
0
TYPE FIXED TYPE 54 70 56 76 56 76 58 82
DISCONNECTED

2-ø11 e Length availble for conductor connection


CONNECTED
DRAW-OUT

W
TYPE OF ACBS a b d e t w
25
TEST

AH-6D 46.8 107 20 30 8 45


d AH-10D AH-12D 46.8 107 20 30 12 50
190 25 AH-16D 46.8 115 20 35 20 55
35

N
t
505(max.)

482.5
b

mounting holes 2-ø10


W
205

100

100 100 100


65
90

Ø9 157(3P)
Earth terminal 257 (4P) 157
122 270 117 a
509 Mounting angle steel (not supplied)

2-ø11 30 Length for conductor connection


TYPE OF ACB b t
AH-6D 107 8
AH-10D,AH-12D 107 12
45

25
AH-16D 115 20
15

H
L
Lifting plate ø20 100 154(3P)
Mounting angle steel (not supplied)
254(4P) 154
20

113 N

37
t

334
487

b
397

384

45
100 100 100
187

15

Mounting holes 4-ø12

100
379 60

Mounting holes 2-ø10


Mounting angle steel (not supplied) Use when vibration is excessive.
Also make it removable for maintenance purpose.

31
Outline Dimensions

10.1 Outline Dimensions and Panel Mounting Details (in mm)


For AH-20D TO AH-25D

Note: N is neutral pole of 4-pole breaker.

DRAW-OUT TYPE

H
L (3P) (4P)

PANEL CUTOUT
HL

363
333

655
308

288
147
137

138 123

208(3P)
208 Mounting holes 4-ø12
338(4P)
Projection of the mounting
270(3P) bolt into the draw-out cradle
270 400(4P) should be 11mm max.
(max.) (max.)

FIXED TYPE

H
L (3P) (4P)
PANEL CUTOUT
HL

363
333
N
575

Terminal blocks
308

288

24 for control
circuits (Left, Right)
Screw M4
135

123
127
117

138
20

233(3P)
15 233 363(4P)
248(3P) 15 Mounting holes 2-ø12
248 378(4P)

32
Outline Dimensions

Dimensions of
Metalclad Construction
(3P)

WEIGHT (kg)

766
TYPE AH-20D AH-25D
No.OF POLES 3 4 3 4
MOTOR CHARGING DRAW-OUT TYPE 135 175 145 185
TYPE FIXED TYPE 90 115 95 120

70

0
62
MANUAL CHARGINGDRAW-OUT TYPE 130 170 140 180

0
TYPE FIXED TYPE 85 110 90 115
DISCONNECTED

50 conductor connection
3-ø12
CONNECTED

Mounting holes 3-ø 12


Terminal blocks
175 H

80
50
for control circuits L 175 (3P)
TEST

36-M4
25 65
Mounting angle steel (not supplied) 240 240 (4P)

15
20 35

48
Extension rail

15
N
595(max.)

117
630

553

80
289

130 130 130


232

150
213

163 270 137 60


425 570
Mounting holes 2-ø12 Mounting angle steel Earth terminal M8
(not supplied)

35 Length availble for


conductor connection
3-ø12
80
50

20 198(3P) H
L
Lifting plate ø20 328(4P) 198
20
25

N
15
117
575

480
505

80
269

130 130 130

100 296 80
15

Mounting holes 4-ø12


396
Mounting holes 2-ø12
Mounting angle steel (not supplied) Use when vibration is excessive.
Also make it removable for maintenance purpose.

33
Outline Dimensions

10.2 Outline Dimensions and Panel Mounting Details (in mm)


For AH-30D

Note: N is neutral pole of 4-pole breaker.


DRAW OUT TYPE

H
L (3P) (4P)
PANEL CUTOUT
H
L

N
363
333

655
290
308

147
137

93 78

249(3 P)
Mounting holes 4-ø14 249 409(4 P)
Projection of the mounting 311(3 P)
bolt into the draw-out cradle 311 471(4 P)
should be 11mm max. (max.) (max.)

FIXED TYPE

PANEL CUTOUT H (3P) (4P)


L
H
L

363
333 N
575
308

288

24
127

78
117

135

93

274(3P)
20

Terminal blocks for control circuits (Left, Right)


274 434(4P)
Screw M4 15 289(3P) 15
Mounting holes 2-ø12 289 449(4P)

34
Outline Dimensions

Dimensions of
Metalclad Construction
(3P)

WEIGHT (kg)
TYPE AH-30D

766
No.OF POLES 3 4
MOTOR CHARGING DRAW-OUT TYPE 215 275
TYPE FIXED TYPE 135 180
MANUAL CHARGINGDRAW-OUT TYPE 210 270

80

0
0
TYPE FIXED TYPE 130 175

70
DISCONNECTED
CONNECTED

Length available for Mounting holes 3-ø 14


conductor connection : 55 Terminal blocks
for control circuits 175 175 (3P)
36-M4
TEST

Mounting angle steel

25
(not supplied) 80
255 255 (4P)
20 35

48
N
112.5 112.5
140 54 45 45 25
Extension rail

620(max.)

25

578
630
232

15
149

40
160 160 160

30
3-15

163 270 166 81 25 Earth terminal M8

599 106
425
Mounting holes Mounting angle steel
4-ø14 (not supplied)

Length available for


conductor connection : 55
Mounting angle steel(not supplied) H
L
Lifting plate ø20 236(3P)
90 396(4P) 236
20

N
25
140 54 45 45
25
577

480
550
530

15
129

160 160 160


40

3-ø15
100 322 94 Mounting holes 4-ø14
25
422 119
Mounting holes 2-ø12
Mounting angle steel (not supplied) Use when vibration is excessive.
Also make it removable for maintenance purpose.

35
Outline Dimensions

10.3 Outline Dimensions and Panel Mounting Details (in mm)


For AH-40D

Note: N is neutral pole of 4-pole breaker.


DRAW OUT TYPE

H
L (3P) (4P)
PANEL CUTOUT
H
L

N
363
355

655
288
308

144
134

93 78

249(3 P)
Mounting holes 4-ø14 249 409(4 P)
Projection of the mounting 311(3 P)
bolt into the draw-out cradle 311 471(4 P)
should be 11mm max. (max.) (max.)

175 175 (3P)


Mounting holes 3-ø14 80
255 255 (4P)
48

Terminal blocks for control


112.5 112.5 circuits 36-M4

N
630

578

20
REAR VIEW

22
160 160 160
30
M8 tapped hole for
earth terminal
200

36
Outline Dimensions

CONNECTED

Length available for SIDE VIEW


ISOLATED

conductor connection : 55
Mounting angle steel
TEST

(not supplied)
20 35 25
Extension rail

17.5
620(max.)

35
35
35
17.5

630
54

140
232

149

4-ø15

163 270 166 81 25

599 106
425
Mounting holes Mounting angle steel
4-ø14 (not supplied)

WEIGHT (kg)
TYPE AH-40D
No.OF POLES 3 4
MOTOR CHARGING DRAW-OUT TYPE 240 280
TYPE FIXED TYPE - -
MANUAL CHARGINGDRAW-OUT TYPE 235 275
TYPE FIXED TYPE - -

37
Outline Dimensions

10.4 Outline Dimensions and Panel Mounting Details (in mm)


For AH-50C / AH-60C

Note: N is neutral pole of 4-pole breaker.

DRAW OUT TYPE


H
L (3P) (4P)

PANEL CUTOUT
HL
200 N
180 150

685
285

00
275
300

R2

Draw-out
handle

248
146
141

267(3P)
266(4P)

295(3P) 6-ø14 mounting holes


295 485(4P) Projection of the mounting
bolt into the draw-out cradle
should be 11 mm max.
373.5(3P)
373.5 563.5(4P)
(max.) (max.)

225 225
(3P)
320 320
(4P) Mounting holes 3-ø14
95
48

112.5 112.5 Terminal blocks for control


circuits 36-M4

N
660
619.5

REAR VIEW

16 62 16

30
M8 tapped hole for
190 190 190 earth terminal

246

38
Outline Dimensions

DISCONNECTED

CONNECTED SIDE VIEW


Length available for
conductor connection : 55
5 Mounting angle steel
TEST

(not supplied)
12.5

Dust plate
25
Front cover 25 35

25
Extension rail

45 45
25
660

70
660
140
231

166
(max) 28
50 125 268 191 121 25 3-ø15
160 5 146
584

Dust plate surface Mounting angle steel


Mounting holes
6-ø14 (Not supplied)
447

WEIGHT (kg)
TYPE AH-50C AH-60C
No.OF POLES 3 4 3 4
MOTOR CHARGING DRAW-OUT TYPE 350 450 360 460

MANUAL CHARGING DRAW-OUT TYPE 345 445 355 455

39
Electrical Connection Diagram

11.0 Connecting Diagram


! with motor stored energy operation

40
Electrical Connection Diagram

41
ACB Order Form

12.0 ACB Order Form


Please fill this sheet for each type and specification separately. Tick the Box in front of each appropriate item and fill the Blanks.
COMPANY’S NAME ORDER NO. & DATE REQUIRED DELIVERY DATE

RATING OF 630A 1000A 1600A 2500A 4000A 6300A QTY.


ACB
REQUIRED 800A 1250A 2000A 3200A 5000A

NO. OF
3 POLE 4 POLE AMBIENT TEMPERATURE 40OC 50OC
POLES

SAFETY SHUTTER
MOUNTING

12/24 WAY AUX. ISOLATING CONTACT ASSY. * Additionally reqd.


FIXED DRAWOUT
POSITION INDICATION SWITCH
SHORT CIRCUIT CONTACTS ______ NOS/ACB

CLOSING COIL ______ V AC/ ______ V DC


OPERATION

TRIPPING COIL ______ V AC/ ______ V DC


MANUAL ELECTRICAL

MOTOR 230V AC 220V DC


110V AC 110V DC

WITHOUT RELEASES

MICROPROCESSOR BASED TRIP MICROPROCESSOR BASED TRIP


UNIT : µ IT - 100 (FOR INDL. APPLICATION) UNIT : µ IT - G (FOR GENERATOR PROTECTION)
RELEASES

REQD. MAIN CT RATING _________ A NEUTRAL CT RATING _________ A


SETTINGS : OVERLOAD ______ A, SHORT CIRCUIT ______ A, GROUND FAULT ______ A
THERMAL
MAGNETIC
SHUNT TRIP ______ V AC/ ______ V DC
(230V AC SHUNT TRIP IS PROVIDED IN STANDARD ACB‘S)
REQUIRED MAIN CT RATING ________ A SETTING OF NON-ADJ. MAG. INST. TRIP _______ KA

AUX. SW. 3 NO + 2 NC AUX. SW. 5 NO + 5 NC AUX. SW. 7 NO + 7 NC

TRIP IND. SW. OCR ALARM SW. SPRING CHARGE IND. SW.
ACCESSORIES

KEY LOCK KEY INTERLOCK SHUNT TRIP ______ VOLTS


2 ACB‘s AC
UVT - AUH ______ Volts AC DC 3 ACB‘s DC
Type of Control Device Reqd. with UVT
ARO - 1B CLOSE-OPEN CYCLE COUNTER
AUH -V-T AUH -V AUH -1 SC Reqd. with AOJ-1LC-GBX

CAPACITOR TRIP ______ VAC DOOR INTERLOCK

SPECIAL REQUIREMENT
(IF ANY)

Notes : For further details of Microprocessor based Releases, Please refer Catalogue/Price-list
- NCT is provided alongwith releases having ground-Fault Protection. This has to be mounted on Earth/
Neutral Bus-bar of Panel.
- Where Under-Voltage Trip or No Volt Coil is provided Shunt Trip can be fitted.
* For Manual Drawout ACB 12 way Auxiliary Contacts assembly is standard fitting
* For Electrical Drawout ACB 24 way Auxiliary Contacts assembly is standard fitting.
Please mention the numbers of Auxiliary Contacts required in addition to the standard fittings.
Please mention if B & C type ACB is required. B & D is upto 630A~1600A, C & D is upto 2000A~4000A

Committed to Excellence in Quality


42
43

Você também pode gostar