Escolar Documentos
Profissional Documentos
Cultura Documentos
1. Introduction 2-5
Salient features, internal & general appearance of Drawout ACB
6. Type of Mounting 20
Fixed, metal clad type, lifter, accessories for draw-out, safety shutter, position switch,
S/C contacts, test jumper, mal-insertion/ prevention device
8. Power Consumption 25
Internal resistance, reactance & special environmental specifications
9. Clearance 26
Clearance above Arc chute, maintenance space
1.0 Introduction
“C & S” Air Circuit Breakers are available in the current range of 630A to 6300A with
wide choice of options & Accessories
! 2, 3 or 4 Pole version available in all current ! Wide options of front panel fittings.
ratings, in fixed & drawout execution.
! 8 type of Accessories for Drawout types, Safety
! Motor charging or manual charging, facilitating Shutter, Position Switch, Test Jumper, Lifter, Mal
local or remote control. Insertion Prevention Device, Door Interlock with
defeat facility, Short Circuiting Contacts &
! 5 types of protection & trip devices: Drawout position Padlock.
a) Micro processor based RMS sensing over- ! Vertical or horizontal bus bar connection
current relay for industrial & generator arrangement.
protection.
4
Introduction
! Lightest and most compact for a given capacity. ! Due to use of tungsten-silver sintered metal
contacts, high speed opening mechanism &
! Most simple to operate & maintain. Only a electromagnetic instantaneous trip device, most
screw driver a spanner required for replacing suitable for capacitor switching & DC
the arcing contacts. application.
! Only 4 frame sizes for entire range (630A ! High dielectric strength even in hot and humid
to 6300A), resulting in maximum interchangeability, conditions due to use of class ‘B’ and ‘F’
commonality of parts and minimum inventory insulating materials.
of spares.
! Comply with utilisation category B & pollution
! High breaking capacity, 50KA to 120KA and degree 3 Group I of IEC 947-Part I.
making capacity from 105KA to 264KA with
line or load connected to upper or lower ! Can withstand impulse voltage of 8KV (peak),
terminals. 1.2/50 micro sec. wave as per case ‘A’ in
homogeneous field condition of
! High speed operating Mechanism ensures a IEC 947-Part-I.
total opening time of 30ms (including arcing
time of less than 10ms) and a total closing ! D-series Breaker fitted in Panel with door cut
time of 40m sec. out meets IP42 protection.
! Neutral pole of 4 pole ACB is of same current ! Designed to provide continuous duty even in
rating as of 3 pole. adverse environmental conditions.
! Highest degree of system protection &
coordination due to use of microprocessor
based protection release.
Internal Structure
Model: AH-6D, Draw-out, Motor Charging Type
"
#
$
%
12
& '
11
( +
15
)
* 13
14
16
% D/O PPosition
osition Indicator
Indicator.. 12 Draw
Draw-- out PPosition
osition PPadlock
adlock (Optional).
( Open PPosition
osition PPadlock
adlock (Optional). 15 D/O Operation Instruction nameplate.
The front panel indicator provides Breaker The Panel Cutout Rubber Gasket
position indication: The shutter prevents erroneous insertion of
provides complete dust-proof
the handle. This can be opened by lowering
protection.
the position stop release lever only when the
"CONNECTED", "TEST" or Breaker is open.
"ISOLATED"
When the Breaker is closed, the release lever
can not be lowered. Thus, the shutter can not
be opened.
6
Introduction
All the poles are completely isolated from each other as well as
from operating mechanism by high grade insulating materials. A
robust design of Arc Chute in a temperature resistant moulded
body and fitted with scientifically shaped Deion-Grids, totally
encompasses the poles.
The high short circuit arc gases thus escape through arc chute
only which clears and cools the highest short circuit arc energy
in less than 10ms. This isolation thus helps in providing highest
insulation properties as well as breaking capacity.
The light and compact ACBs in 4 frame sizes not only help in T T
T T T T
standardising the Switchboard design but also reduce the size of
load centre. T T T
2300
T T T T
Four Breakers upto 1600A frame and 3 Breakers above 1600A T T
upto 4000A frame can be arranged vertically in standard height
of 2300mm. T T T T T T T
8
Ratings & Specifications
800 ≤ In ≤ 1000
1600<In ≤ 2000
In ≤ 4000
In ≤ 6300
In ≤ 2500
In ≤ 5000
In ≤ 1250
10 10 10 10 10 10 10 10
40 40 40 40 40 40 40 40
% Values when fitted with magnetic type instantaneous trip.
0.05 seconds for solid state instantaneous trip.
& AH-16C suitable for 50 KA breaking capacity at 600V AC also available on request.
' Rated service breaking capacity & rated ultimate breaking capacity are same at all other voltages except at 415V.
9
Ratings & Specifications
The thermal current ratings “Ith” of Circuit Breakers c) Cross sectional area of the bus bars connected
shown in ratings & specifications table on to the Breaker terminals.
page No. 8 are free air ratings i.e. in open
d) Ambient temperature other than 40oC
execution at 40 oC ambient. The thermal ratings of
the Circuit Breaker when mounted inside an enclo- For ease of selection of our Breaker, keeping above
sure depend upon: factors into consideration, the thermal current ratings
a) The dimensions of the cubical in which the (I th ) in an enclosure having ventilation &
Breaker is mounted. recommended ambient temperature are shown in
b) Ventilation area provided by way of louvers in the table below:
the Breaker cubicle.
1. The above enclosed thermal current ratings (Ith) have 2. C & S may be consulted, for thermal current ratings
been based when the Breaker Terminals are connected in Enclosure with less ventilation area other than
with copper or aluminium bus bars of cross sectional shown in the above Table or at different ambient
area as indicated in Table XI of IEC 947-2 & IS temperatures.
13947-2.
2.2 Application
2.2.1 AC System
! 3 pole ACB for Industrial & Generator ! 3 pole ACB with 2 poles connected in series
application. can be used in DC system where the short
circuit breaking capacity requirement is
! 4 Pole ACB for complete safety in 3 phase 4
comparatively high.
wire distribution system as the neutral pole of
4 pole ACB closes earlier & opens later than ! A 4 pole ACB with 2 poles connected in parallel
other phase poles, thus effectively preventing can be used where the short circuit breaking
transient overvoltages on loads connected capacity requirement is low but the thermal
between live & neutral lines. current rating is high. (For this application, the
neutral pole closes alongwith the phase poles).
2.2.2 DC System
Please clearly specify 4 pole ACB for DC
! 2 pole ACB can be used on DC system where application.
the short circuit breaking capacity requirement
is not very high.
10
Ratings & Specifications
Various specification are available for wide selection to suit any particular application as well as local regulations
and requirements.
ITEM SELECTION AT Y
AT OUR OPTION
YOUR
▼ ▼ ▼
2 Types of Draw-out type Metalclad
Mounting Fixed type
(standard) construction
▼ ▼
Accessories for , Safety shutter , Position switch , Short-circuiting contact
3
draw-out type , Mal-insertion prevention device , Lifter , Test jumper
▼ ▼
4 Types of closing
Manual charging type Motor charging type
operation
Power transformer
Accessories for Spring charged switch
5
closing operation
▼ ▼
Micro processor based Thermal Magnetic type
6 Overcurrent
trip ▼ ▼ ▼
for General for generator for General
Devices Industrial Plant
Industrial Plant Protection
Adjustable L.T.D. Adjustable L.T.D. Adjustable L.T.D.
Adjustable S.T.D. Adjustable S.T.D. Non adjustable INST.
or
* L.T.D. means Long Adjustable INST. Non adjustable INST.
Making current release
Time Delay Adjustable or
Making current release
* S.T.D. means Short Ground-fault
Time Delay Non adjustable INST.
or
Making current release
▼ ▼
OCR Alarm switch OCR Alarm switch
Accessories for DC24V power supply
7
overcurrent OCR checker
trip device CT for Neutral line
▼ ▼ ▼
Shunt trip Capacitor trip Undervoltage trip
With or without T.D.
8 Other trips
▼
Trip indication switch
9 Other
▼
accessories
Close-open cycle counter
▼ ▼
Key lock / Castle lock Key interlock system
▼ ▼
C - Series D - Series
10 Types &
series of Air Circuit Breaker is assembled to comply with your specifications
Breaker
Note : Tropicalisation, cold climate treatment available on request at extra cost.
11
Multi-Function Protection Devices
Salient Features
Note : µIT-G is similar to µ IT-100 in construction and function but differs in current and time settings
of LTD & STD.
12
Multi-Function Protection Devices
13
Multi-Function Protection Devices
CAUTION : In normal running condition all the Test Mode b = 0.05 1.25 = 1.0+(0.05+0.1+0.1)
When X - min. value
DIP switches should be in OFF position (Normal position) c = 0.10
abcd - settings
d = 0.10
14
Multi-Function Protection Device
3.2 Economical Thermal Magnetic type 3.2.1 Base Current (In) (for Microproces-
sor & Thermal Magnetic Types)
! A direct acting electromagnetic instantaneous ! M i c r o p r o c e s s o r TTyy p e a n d T h e r m a l
trip device with fixed current setting for short Magnetic TType ype both have a single base
circuit protection. current that corresponds to one of the rated
currents available. When ordering, specify the
! CT actuated thermal O/L Relay used along with
base current (I n) that is higher than and closest
Shunt Trip or Undervoltage Trip Device for
to the rated load current passing through the
O/L protection
Air Circuit Breaker.
! Hall sensor actuated over load protection for
DC application can also be provided.
of Thermal of Thermal
Microprocessor Magnetic Microprocessor Magnetic
ACB Type Type ACB Type Type
1000 1000
AH-6D 400 400
1600 1600
600 600
AH-20D 800 800
AH-8D 600 600
1000 1000
800 800 1600 1600
15
Multi-Function Protection Devices
10 " 15 20 20 25 25 25
* Select and specify one of the 15 " 20 30 30 30 30 30
pick-up currents from the 20 " 25 40 40 40 40
table 50 50 50
* Tolerance is + 20% 60
Note : " : Applicable where the rated current of overcurrent trip devices is not less than 250A.
# : Applicable to AH-10D and AH-12D.
MCR instantaneously trips the Breaker without any A short time delay tripping ACB fitted with MCR can
intentional time delay during closing operation, if the thus utilise its full particular time capacity by forming
making current exceeds a predetermined value and a selective tripping system with the other Breaker
which is rendered inoperative when the Circuit and can rapidly clear the faulty circuit without any
Breaker is in closed condition. When the Breaker time delay when the Operator attempts to close it.
is closed on to a normal circuit condition, MCR
becomes inoperative affecting normal coordinated
system protection, thus most suitable for incomer
Breaker.
Closing Stroke
16
Multi-Function Protection Devices
3.3.2 2 4 V DC Power Supply , “Inductive” is a load whose power factor is 0.4 or more (AC)
or time constant is 7 ms or less (DC)
(To be fitted in the PPanel)
(To anel) , “Motor” assumes starting current of 6 times the specified value.
Type : RCU - 2
Power : 500VA, 50/60Hz 240V
Consumption
Dimension Drawing of 24V DC Power Supply Unit
Test : i) Calibration of current Functions
& time settings of
LTD, STD, Instantenous &
Ground Fault
ii) Function Check
by 24V DC.
iii)Closing Opening
time of ACB
Dimensions : 545W x 420D x 345H
Weight : 28 kg
OCR Checker
3.3.4 Phase & Neutral CTs
Polyester resin cast 5A secondary, 5VA, class 5P10 precision CTs are rigidly mounted on the lower terminals
of the Breaker. The CTs thus provide most reliable and accurate current signals to the protection devices
even in adverse environmental conditions.
The CT used for detecting a neutral line current in a 3 pole Breaker of a 3 phase four wire system,
is mounted outside on the neutral bus bar. This CT is necessary when over current trip device is having
a ground fault protection element.
However, in a 4 pole Breaker, the neutral CT is rigidly mounted on the neutral terminal of the Breaker.
17
Spring Charging Operations
The closing springs are manually charged by pumping With the Breaker closed, the Motor automatically
the charging handle. When PUSH TO CLOSE button starts to charge the spring again for the next closing
is pressed, the charge of the closing springs is operation.
released, quickly closing the Breaker.
Manual charging is also possible in Motor charging
A closing coil (Latch Release Coil-LRC) can be type.
provided for remote closing operations, however,
the closing springs would have to be charged
manually before doing a remote close operation.
Rated voltage (V) Min. And Max. Inrush current (A) Steady-state current Charging Closing Command
50/60 Hz Operating Voltage (peak value) (AC:RMS value) time (S) current (A) Max.
Note :
. The charging motor is of short-time rating and the number of repeated open close cycles must
be limited to 15 cycles followed by a cooling period of at least 20 minutes for further operations.
18
Spring Charging Operations
! When the closing springs are "DISCHARGED", ! With the release of Closing Spring charge, the
the “spring charged OFF” switch in series with “Spring Charged On Sw” opens and the supply
the motor, is closed. to the LRC is cut OFF through the Aux.Sw.B1
Contact which opens when the ACB gets closed.
! Control voltage is applied to terminals 1 and
2 and the motor starts to charge the springs.
4.4.3 Anti-Pumping Function
! When the closing springs are fully charged, the
“spring charged OFF” switch in series with the ! Once the closing spring have been released the
motor opens and cuts the supply to the motor. “ACB Reset OFF” switch is closed. If a closed
signal is continuously applied across the
4.4.2 Closing the ACB terminals 2 and 3, the holding relay (HC) is
energised and self holds when the HC/1 contact
! When the springs are charged, the "spring closes.
charged ON switch" in series with the LRC is
! The HC/2 contact opens, cutting the supply to
closed.
the LRC, ACB can not reclose without opening
! Apply voltages across terminals 3 and 4 the PB (Close).
through PB (close). The latch release coil (LRC)
is energised and the closing springs are
released to close the ACB.
PB Control Switch
Isolation Contact
! The circuit may be separated into a ! When ACB is fitted with under voltage trip UVT
closing control and a motor circuit on and tripped by it (voltage below opening value).
request, so that they can be individually
energised. ACB will not reset until voltage above resettable
value is supplied to UVT.
19
Electrical Tripping
When the control supply voltage is higher than The undervoltage trip automatically opens the Air
230V AC, our special Step Down Transformer or Circuit Breaker when the voltage supplied to it drops
a 350VA Transformer with 220V secondary should below the opening voltage. It resets automatically
be used for electrical charging operation. on recovery of the supply voltage above the
resettable value, and allows for closing of the Air
4.5.2 Spring Charged Switch Circuit Breaker. The undervoltage trip consists of an
undervoltage trip device built-in the ACB and UVT
Provides a NO (1a) contact signal, which is closed Control Device installed external to the ACB .
when the closing springs are fully charged. Used
for indication at a remote place, from where
closing is made.
Ratings
Capacitor Trip
20
Electrical Tripping
! Type AUH-V is without time-delay, and is used ! Type AUH-1SC is without time delay and is
for AC supply. It trips the ACB immediately on suitable for DC supply only.
dropping of the supply voltage below the ! The undervoltage trip, when in operation with
opening value. supply voltage below resettable value, keeps
! AUH-V-T is also for AC supply but with a time- the closing control circuit open and locks out
delay of 500 ms. It effectively prevents the the PUSH TO TRIP button.
overiding of the short time delay over current
trip function caused by short circuit fault &
simultaneous voltage drop.
AC - rated Undervoltage Trip Control Circuit DC - rated Undervoltage Trip Control Circuit
21
Type of Mounting
This consists only of the Circuit Breaker fitted with This consists of a Circuit Breaker and a draw-out
brackets to enable it to be permanently mounted cradle. The Circuit Breaker can be withdrawn to any
inside the Panel and the bus bars are directly of the four draw out positions i.e. "CONNECTED",
connected to its terminals. "TEST", "DISCONNECTED" & "REMOVED".
The Circuit Breaker body is kept connected to earth
6.2 Metal Clad Type through earthing shoes to the draw out frame in
"CONNECT", "TEST" or in between to provide total
The metal clad type consists of a fixed or draw out safety to the Operator. The Panel door can be kept
Circuit Breaker housed in a steel enclosure. This closed in "CONNECTED", "TEST" & "DISCONNECTED"
can be used as a single pole mounted ACB or can position.
be readily constructed in a load centre by simply
placing them one upon another in a tier
arrangement.
6.3 Lifter
Lifter
22
Type of Mounting
23
Other Accessories
This switch closes (ON) when the Air Circuit Breaker is Cause of Operation Resetting Condition
tripped by overcurrent trip, shunt trip, undervoltage trip or
Overcurrent trip-shunt trip
manual operation of PUSH TO TRIP buttons. Turn OFF on completion of
Remote spring charging
opening
The table shown summarizes when the trip indication switch
Undervoltage Turn OFF on recovery of
operates (ON) and when it is reset (OFF). trip Undervoltage
voltage above resettable
below opening
value and on completion of
Use a suitable self hold circuit as necessary for continuous value
spring charging
trip alarm indication. PUSH TO TRIP Turn OFF on completion of
button pressed spring charging after release
of button
7.4 Key Lock & Castle Lock *Rating of TIS are same as of OCR Alarm SW
Key Lock
! LOCK-IN-OPEN TYPE
Locks the Breaker in open position.
! LOCK-IN-CLOSED TYPE
Locks the Breaker in CLOSED position.
(Specify either type when ordering).
Castle Lock
! A device that is ready for use, when a Castle key
lock is fitted is also available (specify type of Castle Key Lock Castle Lock
lock when ordering).
24
Other Accessories
! Application Example
Padlock Facility
25
Other Accessories
7.13 IP Cover
26
Power Consumption
If the Breakers are to be used under abnormal This treatment is recommended when Breakers are
environmental conditions, specify the applicable to be used in highly saline atmosphere or in chemical
treatment given below : plants.
This treatment is recommended for Breakers which This treatment is provided when the Breaker is to
are to be used in areas where both temperature be used in very cold areas i.e. Storage - 40 oC, Use
& humidity are higher i.e. Ambient temperature -25 oC Provided no condensation or freezing.
60 oC or less & relative humidity 95% or less
provided no condensation.
27
Clearance
Arc gases expel out from the arc shown below in reference to the from the Breaker bottom level.
chutes when the Breaker interrupt Breaker bottom level. If the For fixed type air circuit Breakers,
a short circuit fault current. It is provision of such distance is also, provide a sufficient
therefore necessary to keep the impracticable, then provide a maintenance space around the
area above these arc chutes clear barrier of heat and flame resistant beaker.
of any metallic objects, including insulating material and of sufficient
If an arc barrier is provided within
electric devices and earthed size to cover all arc chutes at the
the recommended maintenance
structures, at least by the distance position indicated also as minimum
space, make the Breaker
removable.
12345678901
12345678901
12345678901 Metallic Structure / Electric Devices
Heat/Flame Resistant Insulating Plate
28
29
Outline Dimensions
DRAW-OUT TYPE
295 265
505
247
227
120
105
98
108
158(3P)
158 258(4P) Mounting holes 4-ø10
Projection of the mounting
215(3P) bolt into the draw-out cradle
215 332(4P) should be 13mm max.
(max.) (max.)
PANEL CUTOUT
HL H
L (3P) (4P)
295 265
N
487
227
120
80
105
90
15
12
30
Outline Dimensions
Dimensions of
Metalclad Construction
(3P)
WEIGHT (kg)
575
TYPE AH-6D/8D AH-10D AH-12D AH-16D
No.OF POLES 3 4 3 4 3 4 3 4
MOTOR CHARGING DRAW-OUT TYPE 80 100 82 102 82 102 85 110
TYPE FIXED TYPE 58 74 60 80 60 80 62 86
60
MANUAL CHARGINGDRAW-OUT TYPE 76 95 78 98 78 98 80 105
0
55
0
TYPE FIXED TYPE 54 70 56 76 56 76 58 82
DISCONNECTED
W
TYPE OF ACBS a b d e t w
25
TEST
N
t
505(max.)
482.5
b
100
Ø9 157(3P)
Earth terminal 257 (4P) 157
122 270 117 a
509 Mounting angle steel (not supplied)
25
AH-16D 115 20
15
H
L
Lifting plate ø20 100 154(3P)
Mounting angle steel (not supplied)
254(4P) 154
20
113 N
37
t
334
487
b
397
384
45
100 100 100
187
15
100
379 60
31
Outline Dimensions
DRAW-OUT TYPE
H
L (3P) (4P)
PANEL CUTOUT
HL
363
333
655
308
288
147
137
138 123
208(3P)
208 Mounting holes 4-ø12
338(4P)
Projection of the mounting
270(3P) bolt into the draw-out cradle
270 400(4P) should be 11mm max.
(max.) (max.)
FIXED TYPE
H
L (3P) (4P)
PANEL CUTOUT
HL
363
333
N
575
Terminal blocks
308
288
24 for control
circuits (Left, Right)
Screw M4
135
123
127
117
138
20
233(3P)
15 233 363(4P)
248(3P) 15 Mounting holes 2-ø12
248 378(4P)
32
Outline Dimensions
Dimensions of
Metalclad Construction
(3P)
WEIGHT (kg)
766
TYPE AH-20D AH-25D
No.OF POLES 3 4 3 4
MOTOR CHARGING DRAW-OUT TYPE 135 175 145 185
TYPE FIXED TYPE 90 115 95 120
70
0
62
MANUAL CHARGINGDRAW-OUT TYPE 130 170 140 180
0
TYPE FIXED TYPE 85 110 90 115
DISCONNECTED
50 conductor connection
3-ø12
CONNECTED
80
50
for control circuits L 175 (3P)
TEST
36-M4
25 65
Mounting angle steel (not supplied) 240 240 (4P)
15
20 35
48
Extension rail
15
N
595(max.)
117
630
553
80
289
150
213
20 198(3P) H
L
Lifting plate ø20 328(4P) 198
20
25
N
15
117
575
480
505
80
269
100 296 80
15
33
Outline Dimensions
H
L (3P) (4P)
PANEL CUTOUT
H
L
N
363
333
655
290
308
147
137
93 78
249(3 P)
Mounting holes 4-ø14 249 409(4 P)
Projection of the mounting 311(3 P)
bolt into the draw-out cradle 311 471(4 P)
should be 11mm max. (max.) (max.)
FIXED TYPE
363
333 N
575
308
288
24
127
78
117
135
93
274(3P)
20
34
Outline Dimensions
Dimensions of
Metalclad Construction
(3P)
WEIGHT (kg)
TYPE AH-30D
766
No.OF POLES 3 4
MOTOR CHARGING DRAW-OUT TYPE 215 275
TYPE FIXED TYPE 135 180
MANUAL CHARGINGDRAW-OUT TYPE 210 270
80
0
0
TYPE FIXED TYPE 130 175
70
DISCONNECTED
CONNECTED
25
(not supplied) 80
255 255 (4P)
20 35
48
N
112.5 112.5
140 54 45 45 25
Extension rail
620(max.)
25
578
630
232
15
149
40
160 160 160
30
3-15
599 106
425
Mounting holes Mounting angle steel
4-ø14 (not supplied)
N
25
140 54 45 45
25
577
480
550
530
15
129
3-ø15
100 322 94 Mounting holes 4-ø14
25
422 119
Mounting holes 2-ø12
Mounting angle steel (not supplied) Use when vibration is excessive.
Also make it removable for maintenance purpose.
35
Outline Dimensions
H
L (3P) (4P)
PANEL CUTOUT
H
L
N
363
355
655
288
308
144
134
93 78
249(3 P)
Mounting holes 4-ø14 249 409(4 P)
Projection of the mounting 311(3 P)
bolt into the draw-out cradle 311 471(4 P)
should be 11mm max. (max.) (max.)
N
630
578
20
REAR VIEW
22
160 160 160
30
M8 tapped hole for
earth terminal
200
36
Outline Dimensions
CONNECTED
conductor connection : 55
Mounting angle steel
TEST
(not supplied)
20 35 25
Extension rail
17.5
620(max.)
35
35
35
17.5
630
54
140
232
149
4-ø15
599 106
425
Mounting holes Mounting angle steel
4-ø14 (not supplied)
WEIGHT (kg)
TYPE AH-40D
No.OF POLES 3 4
MOTOR CHARGING DRAW-OUT TYPE 240 280
TYPE FIXED TYPE - -
MANUAL CHARGINGDRAW-OUT TYPE 235 275
TYPE FIXED TYPE - -
37
Outline Dimensions
PANEL CUTOUT
HL
200 N
180 150
685
285
00
275
300
R2
Draw-out
handle
248
146
141
267(3P)
266(4P)
225 225
(3P)
320 320
(4P) Mounting holes 3-ø14
95
48
N
660
619.5
REAR VIEW
16 62 16
30
M8 tapped hole for
190 190 190 earth terminal
246
38
Outline Dimensions
DISCONNECTED
(not supplied)
12.5
Dust plate
25
Front cover 25 35
25
Extension rail
45 45
25
660
70
660
140
231
166
(max) 28
50 125 268 191 121 25 3-ø15
160 5 146
584
WEIGHT (kg)
TYPE AH-50C AH-60C
No.OF POLES 3 4 3 4
MOTOR CHARGING DRAW-OUT TYPE 350 450 360 460
39
Electrical Connection Diagram
40
Electrical Connection Diagram
41
ACB Order Form
NO. OF
3 POLE 4 POLE AMBIENT TEMPERATURE 40OC 50OC
POLES
SAFETY SHUTTER
MOUNTING
WITHOUT RELEASES
TRIP IND. SW. OCR ALARM SW. SPRING CHARGE IND. SW.
ACCESSORIES
SPECIAL REQUIREMENT
(IF ANY)
Notes : For further details of Microprocessor based Releases, Please refer Catalogue/Price-list
- NCT is provided alongwith releases having ground-Fault Protection. This has to be mounted on Earth/
Neutral Bus-bar of Panel.
- Where Under-Voltage Trip or No Volt Coil is provided Shunt Trip can be fitted.
* For Manual Drawout ACB 12 way Auxiliary Contacts assembly is standard fitting
* For Electrical Drawout ACB 24 way Auxiliary Contacts assembly is standard fitting.
Please mention the numbers of Auxiliary Contacts required in addition to the standard fittings.
Please mention if B & C type ACB is required. B & D is upto 630A~1600A, C & D is upto 2000A~4000A