TABLE 1 SAFE LOAD FOR VERTICAL BORED CAST IN SITU UNDER REAMED PILES IN SANDY AND CLAYEY SOILS

INCLUDING BLACK COTTON SOILS (IS 2911 – PART III – 1980)


Size Length Compression Safe loads in uplift resistance Lateral thrust
Dia Under Single Double Longitu Rings Single Double Inc. Dec. Singl. Doub. Inc. Dec. Single Double
mete reamed under under dinal spacing under under per 30 per under under per per 30 under under
r of dia reamed reamed rein of 6 reamed reamed cm 30 ream reame 30 cm reamed reamed
pile meter force mm dia length cm ed d cm length
ment rings len. lengt
h
cm cm m m No. Dia (mm) t t t t t t t t t t
20 50 3.5 3.5 3-10# 180 8 12 0.9 0.7 4 6 0.65 0.55 1.0 1.2
25 62.5 3.5 3.5 4-10# 220 12 18 1.15 0.9 6 9 0.85 0.70 1.5 1.8
30 75 3.5 3.5 4-12# 250 16 24 1.4 1.1 8 12 1.05 0.85 2.0 2.4
37.5 94 3.5 3.75 5-12# 300 24 36 1.8 1.4 12 18 1.35 1.10 3.0 3.6
40 100 3.5 4.0 6-12# 300 23 42 1.9 1.58 14 21 1.45 1.15 3.4 4.0
45 112.5 3.5 4.5 7-12# 300 42 63 2.4 1.9 17.5 25.75 1.60 1.30 4.0 4.8
50 125 3.5 5.0 9-12# 300 42 63 2.4 1.9 21 31.5 1.80 1.45 4.5 5.4

NOTES :-
1. Safe loads for Piles having more than two bulbs can be worked out by adding more than 50% of Table value for compression or uplift
as per Clause 1.3 given in Appendix B
2. This table apply to both medium compact sandy soils (10 < N < 30) and clayey soils of medium (4 < N < 8) consistency including
expansive soils as per Clause 1.1 given in Appendix B
3. For dense sandy soils (N ≥ 30) and stiff clayey soils (N ≥ 8), safe loads in compression and uplift may be increased by 25% as per
clause B 1.5 given in Appendix B.
4. For loose sandy (4 < N < 10) and soft clayey soils (2 < N < 4) safe loads should be taken 0.75 times table value as per clause B 1.5
given in Appendix B.
5. For very loose sandy soil (N ≤ 4) and very soft clayey soils (N ≤ 2) the table value should be reduced by 50% as per clause B 1.5
given in Appendix B.
6. For piles with bulb of twice stem dia. instead 2.5 times pile dia, the table value should be reduced by 15% as per clause B 1.7 given in
Appendix B.
7. If the pile is full of sub soil water, safe load shall be reduced by 25% as per clause B 1.6 given in Appendix B.
8. If the spacing between piles is reduced by 1.5 times instead 2 times the under reamed bulb dia as per normal requirement safe load
shall be reduced by 10%.