Date: I S 2026 Part I,II,III,IV Customer : KERALA STATE ELECTRICITY BOARD Purchase Order No: Tender No: 3 PH Transformer Frequency 50 Hz. HV 28 KV RMS Vector BIL : Cooling ANAN LV 3 KV RMS Group Terminals KVA Voltage Current (A) Conn. HV 28 KV SSVT 1U 1V 1W 160 11000V, ±2.5%, ±5% 8.40 Delta LV 3 KV Dyn11 2N 2U 2V 2W 160 433 V 213.35 Star IOVT 866 V
Turns Ratio Test:
Winding Resistance Test Measured Ratio Position of Taps U V W 1U 1V 1W 14.12 Tap 1 46.25 46.25 46.25 2N 2U 2V 2W 14.20 Tap 2 45.15 45.15 45.15 Tap 3 44.00 44.00 44.00 Tap 4 42.90 42.90 42.90 Induced over voltage withstand test: Tap 5 41.85 41.85 41.85 866 V at LV side at 100 Hz for 60 Sec.: - Withstood Insulation Resistance Test Separate Source Voltage withstand test:
HV to Earth 3000 Meg ohms HV to LV and Earth: 28 KV for 60 Sec. @ 50Hz. - Withstood
HV to LV 3000 Meg ohms LV to Earth 3 KV for 60 Sec. @ 50Hz. - Withstood
LV to Earth 3000 Meg ohms Open Circiut Test: Short Circuit Test Terminals 2N 2U 2V 2W Terminals 1U 1V 1W Rated Voltage, V 433 Rated Current, A 8.40 No load Loss - Watts 400 Load Loss , W 1680.00 % impedance 7.01 Efficiency of the transformer At UPF At .8 PF lag % Regulation @ Full load At full Load 98.72 98.40 % UPF 0.8 PF At 3/4 Load 98.99 98.62 % 1.28 5.12 At 1/2 Load 98.99 98.73 % At 1/4 Load 98.75 98.45 % HV KVA 200 KV 11