Box Culverts

Box Culvert Sections Page

Precast Box Culvert; Single Cell 2

Precast Box Culvert; Multiple Cell 3

Precast Box Culvert; Multi Cell – Composite 4

Box Culvert 3-Sided Boxes Page

Precast Box Culvert 3 Sided Box with Footer Slabs 5

Precast Box Culvert 3 Sided Box with Top Slab 6

Box Culvert Bend Details Page

Precast Box Culvert Bend Details 7

Box Culvert End Details Page

Precast Box Culvert End Treatment Detail 8

Precast Box Culvert Skewed Ends 9

Precast Box Culvert Special End Standards (1) 10

Precast Box Culvert Special End Standards (2) 11

Precast Box Culvert Special End Standards (3) 12

1
DATE:

CAROLINA P. O. Box 1061


Dunn, North Carolina 28335
FEB. 15, 1999

PRECAST (910) 892-6411 fax: (910) 892-4894


1-866-PRECAST
DRAWING No:
BOXCUL-S
Setting the Standard www.carolinaprecast.com

SEE NOTE #5

SEE NOTE #4

(1'-0" INCREMENTS)
TYPICAL RISER
MIN. 3'-0" AND UP

PRECAST BOX CULVERT


SEE NOTE #3

SINGLE CELL
SEE NOTE #5

TYPICAL SPANS
MIN. 6'-0" AND UP
SEE NOTE #5

SEE NOTE #5

(1'-0" INCREMENTS)

E
SE E #6
T
NO
SE
E
AN NO
D D TE
SE ET #8
EN AIL
OT
E#
6

L
PICA
TY
'-6"
O7
UPT
NS
TIO
#7 EC
O TE
IERS
EN RR
SE BA
G TH
EN
YL SE
LA E
NO
TE
#8

GENERAL NOTES:
1. PRECAST BOX CULVERT DESIGN SPECIFICATIONS SHALL BE IN ACCORDANCE WITH ACI-318 "BUILDING REQUIREMENTS
FOR STRUCTURAL CONCRETE", AASHTO "STANDARD SPECIFICATIONS FOR HIGHWAY BRIDGES", ASTM C789 "PRECAST
REINFORCED CONCRETE BOX SECTIONS FOR CULVERTS, STORM DRAINS, AND SEWERS, OR ASTM C850 "PRECAST
REINFORCED CONCRETE BOX SECTIONS FOR CULVERTS, STORM DRAINS, AND SEWERS WITH LESS THAN 2 Ft. OF COVER
SUBJECT TO HIGHWAY LOADINGS", AS APPLICABLE.
2. CONCRETE COMPRESSIVE STRENGTH 5,000 P.S.I. MINIMUM UNLESS OTHERWISE SPECIFIED.
3. STEEL REINFORCING DESIGN TO CONFORM TO THE REQUIREMENTS OUTLINED IN NOTE #1 AND SHALL UTILIZE GRADE
60 RE-BARS CONFORMING TO THE REQUIREMENTS OF ASTM A185, OR WWF CONFORMING TO THE REQUIREMENTS OF
ASTM A185 OR BOTH.
4. TYPICAL HAUNCH DETAIL SHALL BE 8"x8". LARGER HAUNCHES ARE AVAILABLE FOR CULVERTS OF LONGER SPANS,
DEEPER FILLS OR HEAVY LIVE LOAD REQUIREMENTS.
5. WALL, ROOF, AND FLOOR DIMENSIONS SHALL BE DETERMINED BY JOB CONDITIONS. TYPICAL CONFIGURATIONS AS WELL
AS STEEL REQUIREMENTS ARE DETAILED IN ASTM C789 AND C850 AS PER NOTE #1.
6. PENETRATIONS IN ROOF SLAB AND WALLS CAN BE PROVIDED DEPENDENT ON JOB CONDITIONS. ADDITIONAL STEEL
WILL BE REQUIRED AT ALL PENETRATIONS.
7. WEEP HOLES AVAILABLE PER JOB REQUIREMENTS AND ARE TYPICALLY PLACED ONE PER CULVERT SECTION AT EACH
EXTERIOR WALL.
8. TONGUE AND GROOVE SHALL BE SIZED IN PROPORTION TO CULVERT CROSS SECTION. JOINTS SHALL BE SEALED BY
1"x1" CLOSE CELL NEOPRENE SPONGE GASKET MATERIAL WHICH IS FACTORY APPLIED TO THE "BELL" OR "GROOVE"
END OF THE CULVERT SECTION.
9. SEE SPECIAL DETAILS FOR END TREATMENTS, CURVES, AND ADDITIONAL OPTIONS AVAILABLE.
© 2007 Carolina Precast Concrete, Inc. DETAILS PROVIDED BY APPIAN CONSULTING ENGINEERS, P.A.

2
DATE:

CAROLINA P. O. Box 1061


Dunn, North Carolina 28335
FEB. 15, 1999

PRECAST (910) 892-6411 fax: (910) 892-4894


1-866-PRECAST
DRAWING No:
BOXCUL-M
Setting the Standard www.carolinaprecast.com

SEE NOTE #5

(1'-0" INCREMENTS)
SEE NOTE #4

TYPICAL RISER
MIN. 3'-0" AND UP

PRECAST BOX CULVERT


SEE NOTE #3

SEE NOTE #5

MULTIPLE CELL
TYPICAL SPANS
SEE NOTE #5
MIN. 6'-0" AND UP
SEE NOTE #5

SEE NOTE #5

(1'-0" INCREMENTS)

SE
E
AN NO
D D TE
SE ET #8
EN AIL
OT
E#
6
E
SE E #6
T
NO

E
SE E #7
O T AL
N
Y PIC
'-6"T
7
TO
UP
S
TION
EC
RS
RRIE SE
E
BA NO
G TH TE
EN #8
YL
LA

GENERAL NOTES:
1. PRECAST BOX CULVERT DESIGN SPECIFICATIONS SHALL BE IN ACCORDANCE WITH ACI-318 "BUILDING REQUIREMENTS
FOR STRUCTURAL CONCRETE", AASHTO "STANDARD SPECIFICATIONS FOR HIGHWAY BRIDGES", ASTM C789 "PRECAST
REINFORCED CONCRETE BOX SECTIONS FOR CULVERTS, STORM DRAINS, AND SEWERS, OR ASTM C850 "PRECAST
REINFORCED CONCRETE BOX SECTIONS FOR CULVERTS, STORM DRAINS, AND SEWERS WITH LESS THAN 2 Ft. OF COVER
SUBJECT TO HIGHWAY LOADINGS", AS APPLICABLE.
© 2007 Carolina Precast Concrete, Inc.

2. CONCRETE COMPRESSIVE STRENGTH 5,000 P.S.I. MINIMUM UNLESS OTHERWISE SPECIFIED.


3. STEEL REINFORCING DESIGN TO CONFORM TO THE REQUIREMENTS OUTLINED IN NOTE #1 AND SHALL UTILIZE GRADE
60 RE-BARS CONFORMING TO THE REQUIREMENTS OF ASTM A185, OR WWF CONFORMING TO THE REQUIREMENTS OF
ASTM A185 OR BOTH.
4. TYPICAL HAUNCH DETAIL SHALL BE 8"x8". LARGER HAUNCHES ARE AVAILABLE FOR CULVERTS OF LONGER SPANS,
DEEPER FILLS OR HEAVY LIVE LOAD REQUIREMENTS.
5. WALL, ROOF, AND FLOOR DIMENSIONS SHALL BE DETERMINED BY JOB CONDITIONS. TYPICAL CONFIGURATIONS AS WELL
AS STEEL REQUIREMENTS ARE DETAILED IN ASTM C789 AND C850 AS PER NOTE #1.
6. PENETRATIONS IN ROOF SLAB AND WALLS CAN BE PROVIDED DEPENDENT ON JOB CONDITIONS. ADDITIONAL STEEL
WILL BE REQUIRED AT ALL PENETRATIONS.
7. WEEP HOLES AVAILABLE PER JOB REQUIREMENTS AND ARE TYPICALLY PLACED ONE PER CULVERT SECTION AT EACH
EXTERIOR WALL.
8. TONGUE AND GROOVE SHALL BE SIZED IN PROPORTION TO CULVERT CROSS SECTION. JOINTS SHALL BE SEALED BY
1"x1" CLOSE CELL NEOPRENE SPONGE GASKET MATERIAL WHICH IS FACTORY APPLIED TO THE "BELL" OR "GROOVE"
END OF THE CULVERT SECTION.
9. SEE SPECIAL DETAILS FOR END TREATMENTS, CURVES, AND ADDITIONAL OPTIONS AVAILABLE.
10. PRECAST CULVERT SECTIONS CAN BE PRODUCED MONOLITHICALLY IN MULTI-CELL CONFIGURATIONS AND MUST SPECIFY
IN REQUIREMENTS.
DETAILS PROVIDED BY APPIAN CONSULTING ENGINEERS, P.A.

3
DATE:

CAROLINA P. O. Box 1061


Dunn, North Carolina 28335
FEB. 15, 1999

PRECAST (910) 892-6411 fax: (910) 892-4894


1-866-PRECAST
DRAWING No:
BOXCUL-C
Setting the Standard www.carolinaprecast.com

SEE NOTE #5

(1'-0" INCREMENTS)
SEE NOTE #4

MIN. 3'-0" AND UP


TYPICAL RISER

MULTI CELL - COMPOSITE


PRECAST BOX CULVERT
SEE NOTE #3

TH
SEE NOTE #5 L WI
FIL RTAR
MO
TYPICAL SPANS
SEE NOTE #11
MIN. 6'-0" AND UP
SEE NOTE #5

SEE NOTE #5

(1'-0" INCREMENTS) OP
T
PR ION
EC AL
NO AS
SIN T
G
SE
E
AN NO
D D TE
ET #8 SE
AIL E
SE NO
E TE
NO #7
TE
#6
E
SE E #6
T
NO

E
SE TE #7
NO

TAI
L NS
DE #11 C TIO
E SE
SE OTE R SE
&N RIE E
B AR CAL NO
H I TE
GT YP #8
L EN ' - 6 "T
Y 7
LA TO
UP
GENERAL NOTES:
1. PRECAST BOX CULVERT DESIGN SPECIFICATIONS SHALL BE IN ACCORDANCE WITH ACI-318 "BUILDING REQUIREMENTS
FOR STRUCTURAL CONCRETE", AASHTO "STANDARD SPECIFICATIONS FOR HIGHWAY BRIDGES", ASTM C789 "PRECAST
REINFORCED CONCRETE BOX SECTIONS FOR CULVERTS, STORM DRAINS, AND SEWERS, OR ASTM C850 "PRECAST
REINFORCED CONCRETE BOX SECTIONS FOR CULVERTS, STORM DRAINS, AND SEWERS WITH LESS THAN 2 Ft. OF COVER
SUBJECT TO HIGHWAY LOADINGS", AS APPLICABLE.
2. CONCRETE COMPRESSIVE STRENGTH 5,000 P.S.I. MINIMUM UNLESS OTHERWISE SPECIFIED.
3. STEEL REINFORCING DESIGN TO CONFORM TO THE REQUIREMENTS OUTLINED IN NOTE #1 AND SHALL UTILIZE GRADE
© 2007 Carolina Precast Concrete, Inc.

60 RE-BARS CONFORMING TO THE REQUIREMENTS OF ASTM A185, OR WWF CONFORMING TO THE REQUIREMENTS OF
ASTM A185 OR BOTH.
4. TYPICAL HAUNCH DETAIL SHALL BE 8"x8". LARGER HAUNCHES ARE AVAILABLE FOR CULVERTS OF LONGER SPANS,
DEEPER FILLS OR HEAVY LIVE LOAD REQUIREMENTS.
5. WALL, ROOF, AND FLOOR DIMENSIONS SHALL BE DETERMINED BY JOB CONDITIONS. TYPICAL CONFIGURATIONS AS WELL
AS STEEL REQUIREMENTS ARE DETAILED IN ASTM C789 AND C850 AS PER NOTE #1.
6. PENETRATIONS IN ROOF SLAB AND WALLS CAN BE PROVIDED DEPENDENT ON JOB CONDITIONS. ADDITIONAL STEEL
WILL BE REQUIRED AT ALL PENETRATIONS.
7. WEEP HOLES AVAILABLE PER JOB REQUIREMENTS AND ARE TYPICALLY PLACED ONE PER CULVERT SECTION AT EACH
EXTERIOR WALL.
8. TONGUE AND GROOVE SHALL BE SIZED IN PROPORTION TO CULVERT CROSS SECTION. JOINTS SHALL BE SEALED BY
1"x1" CLOSE CELL NEOPRENE SPONGE GASKET MATERIAL WHICH IS FACTORY APPLIED TO THE "BELL" OR "GROOVE"
END OF THE CULVERT SECTION.
9. SEE SPECIAL DETAILS FOR END TREATMENTS, CURVES, AND ADDITIONAL OPTIONS AVAILABLE.
10. MULTI-CELL CONFIGURATION MAY BE BUT ACCOMPLISHED BY REPEATED ROWS OF SINGLE CELL CROSS SECTIONS.
THIS IS PRIMARILY DUE TO CONSTRAINTS ON SITE DUE TO WEIGHT HANDLING LIMITATIONS.
11. A 1" SPACING BETWEEN ROWS FILLED WITH GRANULAR MATERIAL IS DESIRABLE TO ASSUME PROPER LOAD
DISTRIBUTION. PRECAST NOSING STEMS ARE AS REQUIRED.
DETAILS PROVIDED BY APPIAN CONSULTING ENGINEERS, P.A.

4
DATE:

CAROLINA P. O. Box 1061


Dunn, North Carolina 28335
FEB. 15, 1999

PRECAST (910) 892-6411 fax: (910) 892-4894


1-866-PRECAST
DRAWING No:
BOXCUL-F
Setting the Standard www.carolinaprecast.com

SEE NOTE #5

3 SIDED BOX WITH FOOTER SLABS


SEE NOTE #4

(1'-0" INCREMENTS)
TYPICAL RISER
MIN. 3'-0" AND UP
SEE NOTE #3

PRECAST BOX CULVERT


FOOTER

TYPICAL SPANS
MIN. 6'-0" AND UP
SEE NOTE #5

SEE NOTE #5

(1'-0" INCREMENTS) E
SE E #6
T
SE NO
E
AN NO
D D TE
SE ET #8
EN AIL
OT
E#
6

S
TION
EC
S
#7 IER
O TE RR AL
EN A
SE H B YPIC
N GT T
Y LE 7 '-6"
LA TO
UP
SE
E
AL NO
TE TE
OR RN #1
A 0
PL POU TE P
AC RE RE
E F D I CA
OO N ST
TE
RS SE
LA E
B NO
TE
#8

GENERAL NOTES:
1. PRECAST BOX CULVERT DESIGN SPECIFICATIONS SHALL BE IN ACCORDANCE WITH ACI-318 "BUILDING REQUIREMENTS
FOR STRUCTURAL CONCRETE", AASHTO "STANDARD SPECIFICATIONS FOR HIGHWAY BRIDGES", ASTM C789 "PRECAST
REINFORCED CONCRETE BOX SECTIONS FOR CULVERTS, STORM DRAINS, AND SEWERS, OR ASTM C850 "PRECAST
REINFORCED CONCRETE BOX SECTIONS FOR CULVERTS, STORM DRAINS, AND SEWERS WITH LESS THAN 2 Ft. OF COVER
SUBJECT TO HIGHWAY LOADINGS", AS APPLICABLE.
© 2007 Carolina Precast Concrete, Inc.

2. CONCRETE COMPRESSIVE STRENGTH 5,000 P.S.I. MINIMUM UNLESS OTHERWISE SPECIFIED.


3. STEEL REINFORCING DESIGN TO CONFORM TO THE REQUIREMENTS OUTLINED IN NOTE #1 AND SHALL UTILIZE GRADE
60 RE-BARS CONFORMING TO THE REQUIREMENTS OF ASTM A185, OR WWF CONFORMING TO THE REQUIREMENTS OF
ASTM A185 OR BOTH.
4. TYPICAL HAUNCH DETAIL SHALL BE 8"x8". LARGER HAUNCHES ARE AVAILABLE FOR CULVERTS OF LONGER SPANS,
DEEPER FILLS OR HEAVY LIVE LOAD REQUIREMENTS.
5. WALL, ROOF, AND FLOOR DIMENSIONS SHALL BE DETERMINED BY JOB CONDITIONS. TYPICAL CONFIGURATIONS AS WELL
AS STEEL REQUIREMENTS ARE DETAILED IN ASTM C789 AND C850 AS PER NOTE #1.
6. PENETRATIONS IN ROOF SLAB AND WALLS CAN BE PROVIDED DEPENDENT ON JOB CONDITIONS. ADDITIONAL STEEL
WILL BE REQUIRED AT ALL PENETRATIONS.
7. WEEP HOLES AVAILABLE PER JOB REQUIREMENTS AND ARE TYPICALLY PLACED ONE PER CULVERT SECTION AT EACH
EXTERIOR WALL.
8. TONGUE AND GROOVE SHALL BE SIZED IN PROPORTION TO CULVERT CROSS SECTION. JOINTS SHALL BE SEALED BY
1"x1" CLOSE CELL NEOPRENE SPONGE GASKET MATERIAL WHICH IS FACTORY APPLIED TO THE "BELL" OR "GROOVE"
END OF THE CULVERT SECTION.
9. SEE SPECIAL DETAILS FOR END TREATMENTS, CURVES, AND ADDITIONAL OPTIONS AVAILABLE.
10. THIS IS A GOOD SOLUTION FOR ENVIRONMENTALLY SENSITIVE AREAS WHERE STREAM BEDS CAN NOT BE DISTURBED.
DETAILS PROVIDED BY APPIAN CONSULTING ENGINEERS, P.A.

5
DATE:

CAROLINA P. O. Box 1061


Dunn, North Carolina 28335
FEB. 15, 1999

PRECAST (910) 892-6411 fax: (910) 892-4894


1-866-PRECAST
DRAWING No:
BOXCUL-T
Setting the Standard www.carolinaprecast.com

PRECAST REMOVABLE TOP SHELF

(1'-0" INCREMENTS)
TYPICAL RISER
MIN. 3'-0" AND UP

3 SIDED BOX WITH TOP SLAB


PRECAST BOX CULVERT
SEE NOTE #3

SEE NOTE #4

SEE NOTE #5

TYPICAL SPANS
MIN. 6'-0" AND UP
SEE NOTE #5

SEE NOTE #5

(1'-0" INCREMENTS)

SE
E
AN NO
D D TE
SE ET #8
EN AIL
OT
E#
6

E
SE E #6
T
NO

NS
CTIO
#7 R SE SE
O TE RIE E
EN B AR ICAL NO
TE
SE GT
H
TY
P #8
L EN 7'-6"
Y TO
LA
UP

GENERAL NOTES:
1. PRECAST BOX CULVERT DESIGN SPECIFICATIONS SHALL BE IN ACCORDANCE WITH ACI-318 "BUILDING REQUIREMENTS
FOR STRUCTURAL CONCRETE", AASHTO "STANDARD SPECIFICATIONS FOR HIGHWAY BRIDGES", ASTM C789 "PRECAST
REINFORCED CONCRETE BOX SECTIONS FOR CULVERTS, STORM DRAINS, AND SEWERS, OR ASTM C850 "PRECAST
REINFORCED CONCRETE BOX SECTIONS FOR CULVERTS, STORM DRAINS, AND SEWERS WITH LESS THAN 2 Ft. OF COVER
SUBJECT TO HIGHWAY LOADINGS", AS APPLICABLE.
© 2007 Carolina Precast Concrete, Inc.

2. CONCRETE COMPRESSIVE STRENGTH 5,000 P.S.I. MINIMUM UNLESS OTHERWISE SPECIFIED.


3. STEEL REINFORCING DESIGN TO CONFORM TO THE REQUIREMENTS OUTLINED IN NOTE #1 AND SHALL UTILIZE GRADE
60 RE-BARS CONFORMING TO THE REQUIREMENTS OF ASTM A185, OR WWF CONFORMING TO THE REQUIREMENTS OF
ASTM A185 OR BOTH.
4. TYPICAL HAUNCH DETAIL SHALL BE 8"x8". LARGER HAUNCHES ARE AVAILABLE FOR CULVERTS OF LONGER SPANS,
DEEPER FILLS OR HEAVY LIVE LOAD REQUIREMENTS.
5. WALL, ROOF, AND FLOOR DIMENSIONS SHALL BE DETERMINED BY JOB CONDITIONS. TYPICAL CONFIGURATIONS AS WELL
AS STEEL REQUIREMENTS ARE DETAILED IN ASTM C789 AND C850 AS PER NOTE #1.
6. PENETRATIONS IN ROOF SLAB AND WALLS CAN BE PROVIDED DEPENDENT ON JOB CONDITIONS. ADDITIONAL STEEL
WILL BE REQUIRED AT ALL PENETRATIONS.
7. WEEP HOLES AVAILABLE PER JOB REQUIREMENTS AND ARE TYPICALLY PLACED ONE PER CULVERT SECTION AT EACH
EXTERIOR WALL.
8. TONGUE AND GROOVE SHALL BE SIZED IN PROPORTION TO CULVERT CROSS SECTION. JOINTS SHALL BE SEALED BY
1"x1" CLOSE CELL NEOPRENE SPONGE GASKET MATERIAL WHICH IS FACTORY APPLIED TO THE "BELL" OR "GROOVE"
END OF THE CULVERT SECTION.
9. SEE SPECIAL DETAILS FOR END TREATMENTS, CURVES, AND ADDITIONAL OPTIONS AVAILABLE.
10. THIS SECTION MAY BE USED FOR VARIOUS APPLICATIONS WHERE IT IS DESIRABLE TO GAIN ACCESS TO A TRENCH
OR INSTALL PIPING OR UTILITIES BEFORE CLOSING TOP SECTION.
DETAILS PROVIDED BY APPIAN CONSULTING ENGINEERS, P.A.

6
DATE:

CAROLINA P. O. Box 1061


Dunn, North Carolina 28335
FEB. 15, 1999

PRECAST (910) 892-6411 fax: (910) 892-4894


1-866-PRECAST
DRAWING No:
BOXCUL-B
Setting the Standard www.carolinaprecast.com

PRECAST BOX CULVERT


SWEEP BEND - TAPERED JOINT

BEND DETAILS
TYPICALLY 5° TO 10° PER JOINT
DEPENDING ON JOB CONFIGURATIONS.
MOST COST EFFECTIVE WAY TO
MAKE A TURN.

TIGHT BEND - SPECIAL SECTION


ANGLE AS REQUIRED
SPECIAL CULVERT SECTION REQUIRED TO BE
HAND BUILT INCORPORATING A COLD JOINT AND
WELDING OF REBAR TO PROVIDE CONTINUOUS
STEEL REINFORCING.
MODERATELY EXPENSIVE

TIGHT BEND - MITER JOINT


ANGLES AS REQUIRED UP TO 45°
SPECIAL JOINT SECTION REQUIRED,
LIMITED BY CROSS SECTION CONFIGURATIONS
COULD BE EXPENSIVE DEPENDING ON CONFIGURATION

© 2007 Carolina Precast Concrete, Inc. DETAILS PROVIDED BY APPIAN CONSULTING ENGINEERS, P.A.

7
DATE:

CAROLINA P. O. Box 1061


Dunn, North Carolina 28335
FEB. 15, 1999

PRECAST (910) 892-6411 fax: (910) 892-4894


1-866-PRECAST
DRAWING No:
BOXCUL-E
Setting the Standard www.carolinaprecast.com

PRECAST BOX CULVERT


END TREATMENT DETAIL
2 SE
TE# EN
OT
E NO E#
SE 1

SE
EN
OT
E#
4
© 2007 Carolina Precast Concrete, Inc.

SE
EN
OT
SE E#
EN 3
OT
E#
4

GENERAL NOTES:
1. #4 DOWEL BAR SPLICERS MAY BE CAST IN TO FACILITATE TIE IN TO CAST IN PLACE HEADWALLS, WING WALLS
AND FOOTINGS.
2. REBAR MAY BE EXTENDED TO FACILITATE TIE INS IN LIEU OF NOTE #1.
3. PRECAST END WALL DESIGNS ARE AVAILABLE TO CREATE CONTAINMENT STRUCTURES. CALL C.P.C. ENGINEERING
DEPARTMENT FOR FURTHER DETAILS.
4. EMBEDDED WALL PLATES MAY BE PROVIDED TO ACCOMMODATE SPECIAL JOB CONDITIONS.
DETAILS PROVIDED BY APPIAN CONSULTING ENGINEERS, P.A.

8
DATE:

CAROLINA P. O. Box 1061


Dunn, North Carolina 28335
FEB. 15, 1999

PRECAST (910) 892-6411 fax: (910) 892-4894


1-866-PRECAST
DRAWING No:
BOXCUL-K
Setting the Standard www.carolinaprecast.com

PRECAST BOX CULVERT


E

SKEWED ENDS
SE 1
E #
N OT
SINGLE

S
TION
EC
RS
R RIE L
BA PICA
G TH TY
L EN 7'-6"
Y TO
LA
UP

.
" MIN
1'-6

2
TE#
E NO
SE

NS
C TIO
SER
RIE
B AR ICAL
P
GT
H
EN 7'-6"
TY TWIN
Y L
LA TO
UP

.
" MIN
1'-6
GENERAL NOTES:
1. STANDARD SKEWED ANGLE MAY BE LIMITED DUE TO SECTION LENGTH AS RELATED TO SPAN OF CULVERT.
SPECIAL LENGTH END SECTIONS CAN BE PRODUCED TO INCREASE SKEWED ANGLE.
2. SPECIAL SKEW CONFIGURATION CAN BE ACHIEVED IN SINGLE AND MULTIPLE CELL CULVERTS BY
INCORPORATING A PRECAST HEADWALL INTO THE END DESIGN. CALL CAROLINA PRECAST ENGINEERING
DEPARTMENT FOR FURTHER DETAILS.

© 2007 Carolina Precast Concrete, Inc. DETAILS PROVIDED BY APPIAN CONSULTING ENGINEERS, P.A.

9
DATE:

CAROLINA P. O. Box 1061


Dunn, North Carolina 28335
FEB. 15, 1999

PRECAST (910) 892-6411 fax: (910) 892-4894


1-866-PRECAST
DRAWING No:
BOXCUL-W1
Setting the Standard www.carolinaprecast.com

SPECIAL END STANDARDS


PRECAST BOX CULVERT
PR
E
CA CAS
S T
PA T AS HEA
RT IN D
OF TE WA
EN GRA LL
DS L
EC
TA TIO
P N
IN ERE
L D
PR IEW END
OV OF S
EC IDE W MA
ON A ING Y B
OM PR WA E U
ICA AC LL SE
L A TIC S T D
LTE AL O
RN AND
AT
IVE

PR
EC
AS
TF
OO
TE
R

DR
I
IN LL &
F D
TA IELD OW
PE EL
RE
DE
ND

SECOND POUR

DOWEL BAR SPLICERS

© 2007 Carolina Precast Concrete, Inc. DETAILS PROVIDED BY APPIAN CONSULTING ENGINEERS, P.A.

10
DATE:

CAROLINA P. O. Box 1061


Dunn, North Carolina 28335
FEB. 15, 1999

PRECAST (910) 892-6411 fax: (910) 892-4894


1-866-PRECAST
DRAWING No:
BOXCUL-W2
Setting the Standard www.carolinaprecast.com

SPECIAL END STANDARDS


PRECAST BOX CULVERT
BO
L
CO T AN
NN GL
EC E
TIO
N

DR
I
FIE LL &
LD DO
CO WE
NN L
EC
T ION

© 2007 Carolina Precast Concrete, Inc. DETAILS PROVIDED BY APPIAN CONSULTING ENGINEERS, P.A.

11
DATE:

CAROLINA P. O. Box 1061


Dunn, North Carolina 28335
FEB. 15, 1999

PRECAST (910) 892-6411 fax: (910) 892-4894


1-866-PRECAST
DRAWING No:
BOXCUL-W3
Setting the Standard www.carolinaprecast.com

SPECIAL END STANDARDS


PRECAST BOX CULVERT
PR
E
CA CAS
S T
PA T AS HEA
RT IN D
OF TE WA
EN GRA LL
DS L
EC
TIO
N

DR
I
IN LL &
FIE DO
LD WE
L
PR
EC
AS
TF
OO
TE
R

GENERAL NOTES:
1. PRECAST WING WALL SECTIONS ARE AVAILABLE TO CREATE A TOTAL PRECAST SOLUTION.
THESE SECTIONS ARE READILY AVAILABLE IN PRECAST CONCRETE, HOWEVER, SECTION WEIGHTS AND JOB
CONDITIONS MAY LIMIT THE CONTRACTORS ABILITY TO HANDLE THIS PRODUCT OR LARGER CULVERT SECTIONS.

© 2007 Carolina Precast Concrete, Inc. DETAILS PROVIDED BY APPIAN CONSULTING ENGINEERS, P.A.