Você está na página 1de 2

8 7 6 5 4 3 2 1

# NAME DESCRIPTION
Q
T
Y
COMMENTS INSTALL METRIC GADCQ1000-00
TOP VIEW
1 CONTAINER ISO SHIPPING CONTAINER 1 40 FT HC, COLOR RAL9003 INST.
2 LIFTING CORNERS ISO LIFTING CORNERS 8 - INST. C C
3 DECAL CAT ELECTRIC POWER 2 MOUNTED ON FLAT METAL SHEET INST.
4 DECAL WWW.CAT.COM 2 MOUNTED ON FLAT METAL SHEET INST. 2' FUEL OUTLET PIPE
5 FUEL CONNECTION FUEL INLET/OUTLET 1 - INST. THREAD WITH SCREWED
6 WARNING DECAL POWER CABLE OUTLET 2 ALLOY GLANDED INST. FLANGE DIN 2566
F F
7 ACCESS DOOR - 5 INDUSTRIAL TYPE INST.
SEE NOTE 1
8 CONTAINER DOOR ISO TYPE 1 DOUBLE HINGED INST.
9 AIR INLET RAIN LOUVER 2 FOR UPS WITH AIR FILTER INST.
10 EMERGENCY STOP BUTTON - 2 - INST.
11 GROUNDING POINT - 2 - INST.
12 AIR OUTLET RAIN LOUVER - 1 FOR GENSET INST.
13 AIR INLET RAIN LOUVER - 2 FOR GENSET INST.

1'1/2 FUEL INLET PIPE


THREAD WITH SCREWED
FLANGE DIN 2566

DETAIL A
E SCALE 1 : 5 E

NOTES: UNLESS OTHERWISE SPECIFIED


1. FUEL CONNECTION SHOWN FOR LOCATION REFERENCE ONLY. SEE MANUAL FOR CONNECTION
DETAILS.

2. THE DRAWING SHOWS NOT ALL AVAILABLE OPTIONS OF THE PRODUCT. FOR THE REAL
DELIVERED EQUIPMENT SEE YOUR ORDER CONTRACT.

3. TOLERANCE EXCEPT OTHERWISE STATED: 2


0-500MM ±1MM REAR VIEW RIGHT VIEW FRONT VIEW
500-2000MM ±2MM
OVER 2000MM ±3MM
STRUCTURAL ±3MM
ANGULAR ±1 DEGREE

4. THIS DRAWING IS COPYRIGHTED AND MAY BE COPIED ONLY FOR PURPOSE OF


MANUFACTURING THE PURCHASED EQUIPMENT BY THE PURCHASER.

5. PRELIMINARY DRAWING FOR INFORMATION ONLY. ORDERED DESIGN


IS CONFIRMED WITH AS BUILD DRAWINGS PROVIDED WITH THE PURCHASED ORDER.
D D

C C

13
8 9
7 12

LEFT VIEW

D D

C C

DETAIL A
4 3 10 6
5
11
MA
TL

HT
SECTION C-C TR

243
8m
m

B B
1

TDDCQ1000-00 TECHNICAL DESCRIPTION


N
O SCDCQ0250-00 SPECIFICATION
09
T
SPECIFICATION. NO. NAME
2990 mm

DRN R. WOLOSZYN 08
CHK S. COQUOZ 07
APPD M. TREBBI 06
05
CON- PRE- PRODU
EXP
CEPT PROD. CTION

04
APPRO FOR FOR PRELI
VED APPRO INFO MINAR
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN MM [INCH]
03
DIMENSIONS W/O TOLERANCE ARE BASIC 02
SCALE 1 = 20 01 13 OCT 2010
0 1 0 mm 20 30
THIR D ANGL E
00 11 OCT 2010
SHEET 1 OF 2 P R OJ E C TION CHG DATE
A A

CATERPILLAR S.A.R.L
m
2m
1219

SCALE 1 : 50 THE INFORMATION HEREON IS THE PROPERTY OF CATERPILLAR SARL AND/OR ITS
SUBSIDIARIES WITHOUT WRITTEN PERMISSION ANY COPYING, TRANSMITTAL TO
PRODUCT DETAIL OTHERS AND ANY USE EXCEPT THAT FOR WHICH IT IS LOANED IS PROHIBITED.
DIMENSIONS ISO HC 40'
GENSET 3512 1400kVA
C R I T I C A L P O WE R M O D U L E P A C K A G E
UPS 300 SERIES 1000kVA CP1000
AMBIENT TEMPERATURE -20...+37 ℃ VER CONTROL
NOISE LEVEL 85 dBA@1m GADCQ1000-00 DES X A0
WEIGHT 37.200 KG
- SUB SIZE
8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1

# NAME DESCRIPTION
Q
T
Y
COMMENTS INSTALL METRIC GADCQ1000-00

1 GENSET 3512 1 - INST.


2 FUEL TANK 3000 LITERS 1 SINGLE WALL INST.
3 ATS SWITCHGEAR 1 - INST.
4 GENSTART - 1 GEN START MODULE INST.
5 LIGHT - 6 10W DC LED LIGHT INST.
6 AIR INLET VENTILATION 2 AIR INLET MULLER INST.
F F
7 AIR OUTLET VENTILATION 1 AIR OUTLET MUFLER INST.
TOP VIEW
8 SPIL CONTAINMENT - 1 SIZED FOR FULE TANK INST.
9 EXTRACTION FAN VENTILATION 3 FOR UPS COMPARTMENT INST.
17
10 SILENCER EXHAUST SILENCER 1 INTERNALLY MOUNTED INST.
11 RAIN CAP - 2 OPERATION HEIGHT IS 300 MM HIGHER L.S.
12 LIGHT SWITCH - 6 - INST.

A
13 CUSTOMER CONNECTION BUSBAR 2 ALLOY GLANDED INST. 19 20 3 2 4 6 14
21

B
14 BATTERY - 2 - INST.
15 FLOOR - 1 CHEQUERED STEEL PLATES INST.
16 INSULATION MINERAL WOOL 1 WALLS, ROOF AND DOORS INSULATED INST.
17 VIBRATION ISOLATORS - 8 LOW PROFILE INST.
18 JUNCTION PANEL - 1 - INST.
19 UPS FLYWHEEL CABINET - 4 250kVA INST. MAINS CONNECTION:
20 UPS SYSTEM CABINET - 1 - INST. CUSTOMER CABLE.
21 UPS I/O CABINET - 1 - INST.
SEE NOTE 1

E E

NOTES: UNLESS OTHERWISE SPECIFIED


1. CUSTOMER CABLE CONNECTION SHOWN FOR LOCATION REFERENCE ONLY. SEE
7
MANUAL FOR CONNECTION DETAILS.

2. THE DRAWING SHOWS NOT ALL AVAILABLE OPTIONS OF THE PRODUCT. FOR THE REAL
DELIVERED EQUIPMENT SEE YOUR ORDER CONTRACT.

3. TOLERANCE EXCEPT OTHERWISE STATED:


0-500MM ±1MM
500-2000MM ±2MM
OVER 2000MM ±3MM
STRUCTURAL ±3MM
ANGULAR ±1 DEGREE
DETAIL A

B
A
4. THIS DRAWING IS COPYRIGHTED AND MAY BE COPIED ONLY FOR PURPOSE OF SCALE 1 : 5
MANUFACTURING THE PURCHASED EQUIPMENT BY THE PURCHASER. 12 15 18
5 1
5. PRELIMINARY DRAWING FOR INFORMATION ONLY. ORDERED DESIGN 16
IS CONFIRMED WITH AS BUILD DRAWINGS PROVIDED WITH THE PURCHASED ORDER.
D D

9
REAR VIEW FRONT VIEW

SECTION A-A RIGHT VIEW

C C

D D

SECTION B-B

LEFT VIEW

C C

MA
TL

HT
TR

B B

10
DETAIL A TDDCQ1000-00 TECHNICAL DESCRIPTION
N
O SCDCQ0250-00 SPECIFICATION
13
09
T
SPECIFICATION. NO. NAME
11 E

DRN R. WOLOSZYN 08
CHK S. COQUOZ 07
APPD M. TREBBI 06
05
CON- PRE- PRODU
EXP
CEPT PROD. CTION

04
APPRO FOR FOR PRELI
VED APPRO INFO MINAR
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN MM [INCH]
03
DIMENSIONS W/O TOLERANCE ARE BASIC 02
SCALE 1 = 20 01 13 OCT 2010
0 1 0 mm 20 30
THIR D ANGL E
00 11 OCT 2010
SHEET 2 OF 2 P R OJ E C TION CHG DATE
A A

CATERPILLAR S.A.R.L
THE INFORMATION HEREON IS THE PROPERTY OF CATERPILLAR SARL AND/OR ITS
SUBSIDIARIES WITHOUT WRITTEN PERMISSION ANY COPYING, TRANSMITTAL TO
PRODUCT DETAIL OTHERS AND ANY USE EXCEPT THAT FOR WHICH IT IS LOANED IS PROHIBITED.
DIMENSIONS ISO HC 40'
GENSET 3512 1400kVA
C R I T I C A L P O WE R M O D U L E P A C K A G E
UPS 300 SERIES 1000kVA CP1000
AMBIENT TEMPERATURE -20...+37 ℃ VER CONTROL
NOISE LEVEL 85 dBA@1m GADCQ1000-00 DES X A0
WEIGHT 37.200 KG