Wind Zone IV Basic Wind Speed 47 m/s Design wind pressure (Pd) 701 N/M
Reliability level 1 Terrain Category 2 (refer table 4, page 4, IS 802 (Part1 Sec1) : 1995
:
Wind Pressure on Conductors:-
u Height of max Extension above Normal tower [Ext] = 3000 mm
u Min Ground Clearance [Gr] = 5200 mm
u Max. Sag (Max temp, no wind) [Sag] = 2.5 mm
u Suspension insulator length [Ins] = 850 mm
u Sag error (4% or 150 mm) [Err] = 150 mm
u Back mark of crossarm main member [BM] 50 mm
u Hanger [Hng] = 200 mm
u CL to GL distance (no effect) [Cl] = 225 mm
u Height of BXA above CL (no effect) = 9452.5 mm
u Vertical separation TXA - MXA [CG1] = 1500 mm
u Vertical seperation MXA - BXA [CG2] = 1500 mm
u Height of Top conductor [Hc] = 12452.5 mm
u Min Sag (Min. temp no wind) = 900 mm
u Less 2/3 of Min Sag [Hsc] = 600 mm
u Reference height of Conductor Sag [H=Hc-Hsc-ins-BM-Hng] 10753 mm
u Gust response factor for conductor [Gc] for 15m = 1.8
u Drag coefficient for conductor [Cdc] = 1
2
u Design wind pressure [Pd x Cdc x Gc] = 129 Kg/M